Oklahoma Administrative Code
Title 310 - Oklahoma State Department of Health
Chapter 600 - Abortion Facility Regulations
Subchapter 11 - Physical Plant
Section 310:600-11-1 - Facility design and construction
Universal Citation: OK Admin Code 310:600-11-1
Current through Vol. 42, No. 1, September 16, 2024
(a) The operational program narrative shall include scaled drawings of facility construction. The drawings shall locate and identify the following:
(1) An entrance, located at grade level, able
to accommodate wheelchairs.
(2) A
reception and waiting area, and information counter or desk.
(3) Conveniently accessible public
toilet.
(4) Conveniently accessible
public telephone.
(5) Interview
space(s) for private interviews related to social service, credit, and
counseling.
(6) Secure general or
individual office(s) for business transactions, records, administrative, and
professional staff.
(7) Clerical
space or rooms separated from public areas for confidentiality.
(8) Storage space for staff personal effects
with locking drawers, cabinets or desks near individual work-stations that are
staff controlled.
(9) General
storage facilities for supplies and equipment needed for continuing
operation.
(10) General purpose
examination room(s) equipped to perform pelvic and medical examinations. Rooms
shall have a minimum floor area of eighty (80) square feet, excluding
vestibules, toilets, and closets. Room arrangement shall permit at least two
(2) feet and eight (8) inches clearance at each side and at the foot of the
examination table. A handwashing fixture and counter or shelf for writing shall
be provided.
(11) Nurses station(s)
with work counter, communication system, space for supplies, and provisions for
charting.
(12) Drug distribution
station which may be part of the nurse station but shall include a work
counter, sink, refrigerator, and locked storage for biologicals and
drugs.
(13) A separate clean
storage room or closet for storing clean and sterile supplies. This area shall
be in addition to cabinets and shelves.
(14) A soiled holding area for separate
collection, storage, and disposal of soiled materials.
(15) A sterilizing room or area if
instruments and supplies are sterilized on-site. If sterilizing is accomplished
off-site or if disposable sterile supplies are used, the facility shall provide
a system for processing and storage.
(16) Wheelchair storage space out of the
direct line of traffic.
(17)
Procedure room(s) with a minimum area of one hundred forty-four (144) square
feet, exclusive of vestibule, toilets, or closets. The minimum room dimension
shall be twelve (12) feet. A handwashing fixture and counter or shelf for
writing shall be provided. The sink may be within the procedure room or
immediately outside. An emergency communication system connected to the nurse
station shall be provided.
(18) A
designated supervised recovery patient lounge. This lounge shall contain a
control station, space for family members, and provisions for privacy. It shall
have convenient patient access to toilets large enough to accommodate a patient
and an assistant. Handwashing and nourishment facilities shall be
included.
(19) Clothing change
areas for staff which shall contain lockers, toilets, lavatories for
handwashing.
(20) A housekeeping
room containing a floor receptor or service sink and storage space for
housekeeping supplies and equipment.
(b) The Department shall review the scaled drawings for compliance and return the drawings to the facility upon licensure.
Added at 15 Ok Reg 3172, eff 7-13-98
Disclaimer: These regulations may not be the most recent version. Oklahoma may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.