Oklahoma Administrative Code
Title 252 - Department of Environmental Quality
Chapter 656 - Water Pollution Control Facility Construction Standards
Subchapter 19 - Sludge Facility Standards
Section 252:656-19-4 - Sludge pumps and piping

Universal Citation: OK Admin Code 252:656-19-4

Current through Vol. 41, No. 13, March 15, 2024

(a) Sludge pumps.

(1) Duplicate units. Provide duplicate units.

(2) Minimum head. Pumps must provide at least 24 inches of positive head.

(3) Sampling facilities. Provide a means to sample sludge. All sampling pipes and valves must be at least 1.5 inches.

(b) Sludge piping. Sludge withdrawal piping must be at least 8 inches in diameter for gravity systems and 6 inches for pump suction and discharge lines. A minimum velocity of 3.0 fps for gravity lines is required.

Added at 17 Ok Reg 1140, eff 6-1-00; Amended at 23 Ok Reg 937, eff 6-15-06

Disclaimer: These regulations may not be the most recent version. Oklahoma may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.