New Hampshire Code of Administrative Rules
We - Water Well Board
Chapter We 600 - STANDARDS FOR THE CONSTRUCTION, MAINTENANCE AND ABANDONMENT OF WELLS
Part We 602 - NEW WELL CONSTRUCTION
Section We 602.38 - Open Loop Geothermal Wells
Current through Register No. 40, October 3, 2024
(a) A withdrawal, return or standing column well shall be located:
(b) During advancement of the borehole, the licensed contractor shall follow the observation and record keeping requirements of We 602.20.
(c) An open-loop geothermal well shall be cased as specified in We 602.21 and We 602.22 or, if a reduced setback is required, as specified in We 602.13 through We 602.17.
(d) For system designs with separate return and withdrawal wells, the return water shall be re-injected into the same aquifer as the withdrawal well.
(e) For the purposes of (d) above:
(f) Return water shall be discharged below the static water level in return wells or below the draw down level in standing column wells.
(g) An owner of an open loop geothermal well shall obtain a groundwater discharge permit in accordance with Env-Wq 402.33 through Env-Wq 402.36.