Petitions for Modification of Application of Existing Mandatory Safety Standards, 47417-47421 [2020-17018]
Download as PDF
jbell on DSKJLSW7X2PROD with NOTICES
Federal Register / Vol. 85, No. 151 / Wednesday, August 5, 2020 / Notices
(u) The petitioner states that it will
use nonpermissible electronic surveying
equipment when production is
occurring, subject to the following
conditions:
—On a mechanized mining unit (MMU)
where production is occurring,
nonpermissible electronic surveying
equipment will not be used
downwind of the discharge point of
any face ventilation controls, such as
tubing (including controls such as
‘‘baloney skins’’) or curtains.
—Production will continue while
nonpermissible electronic surveying
equipment is used, if such equipment
is used in a separate split of air from
where production is occurring.
—Nonpermissible electronic surveying
equipment will not be used in a split
of air ventilating an MMU if any
ventilation controls will be disrupted
during such surveying. Disruption of
ventilation controls means any change
to the mine’s ventilation system that
causes the ventilation system not to
function in accordance with the
mine’s approved ventilation plan.
—If, while surveying, a surveyor will
disrupt ventilation, the surveyor will
cease surveying and communicate to
the section foreman that ventilation
will be disrupted. Production will
stop while ventilation is disrupted.
Ventilation controls will be
reestablished immediately after the
disruption is no longer necessary.
Production will only resume after all
ventilation controls are reestablished
and are in compliance with approved
ventilation or other plans, and other
applicable laws, standards, or
regulations.
—Any disruption in ventilation will be
recorded in the logbook required by
the petition. The logbook will include
a description of the nature of the
disruption, the location of the
disruption, the date and time of the
disruption and the date and time the
surveyor communicated the
disruption to the section foreman, the
date and time production ceased, the
date and time ventilation was
reestablished, and the date and time
production resumed.
—All surveyors, section foremen,
section crew members, and other
personnel who will be involved with
or affected by surveying operations
will receive training in accordance
with 30 CFR 48.7 on the requirements
of the petition within 60 days of the
date the petition becomes final. The
training will be completed before any
nonpermissible electronic surveying
equipment can be used while
production is occurring. The
VerDate Sep<11>2014
16:55 Aug 04, 2020
Jkt 250001
petitioner will keep a record of the
training and provide the record to
MSHA on request.
—The petitioner will provide annual
retraining to all personnel who will be
involved with or affected by
surveying operations in accordance
with 30 CFR 48.8. The petitioner will
train new miners on the requirements
of the petition in accordance with 30
CFR 48.5, and will train experienced
miners, as defined in 30 CFR 48.6, on
the requirements of the petition in
accordance with 30 CFR 48.6. The
petitioner will keep a record of the
training and provide the record to
MSHA on request.
The petitioner asserts that the
proposed alternative method will at all
times guarantee no less than the same
measure of protection afforded by the
existing standard.
Roslyn Fontaine,
Deputy Director, Office of Standards,
Regulations, and Variances.
[FR Doc. 2020–17017 Filed 8–4–20; 8:45 am]
BILLING CODE 4520–43–P
DEPARTMENT OF LABOR
Mine Safety and Health Administration
Petitions for Modification of
Application of Existing Mandatory
Safety Standards
Mine Safety and Health
Administration, Labor.
ACTION: Notice.
AGENCY:
This notice is a summary of
5 petitions for modification submitted to
the Mine Safety and Health
Administration (MSHA) by the parties
listed below.
DATES: All comments on the petitions
must be received by MSHA’s Office of
Standards, Regulations, and Variances
on or before September 4, 2020.
ADDRESSES: You may submit your
comments, identified by ‘‘docket
number’’ on the subject line, by any of
the following methods:
1. Electronic Mail: zzMSHAcomments@dol.gov. Include the docket
number of the petition in the subject
line of the message.
2. Facsimile: 202–693–9441.
3. Regular Mail or Hand Delivery:
MSHA, Office of Standards,
Regulations, and Variances, 201 12th
Street South, Suite 4E401, Arlington,
Virginia 22202–5452, Attention: Roslyn
B. Fontaine, Deputy Director, Office of
Standards, Regulations, and Variances.
Persons delivering documents are
required to check in at the receptionist’s
SUMMARY:
PO 00000
Frm 00080
Fmt 4703
Sfmt 4703
47417
desk in Suite 4E401. Individuals may
inspect copies of the petition and
comments during normal business
hours at the address listed above.
MSHA will consider only comments
postmarked by the U.S. Postal Service or
proof of delivery from another delivery
service such as UPS or Federal Express
on or before the deadline for comments.
FOR FURTHER INFORMATION CONTACT:
Aromie Noe, Office of Standards,
Regulations, and Variances at 202–693–
9557 (voice), Noe.Song-Ae.A@dol.gov
(email), or 202–693–9441 (facsimile).
[These are not toll-free numbers.]
SUPPLEMENTARY INFORMATION: Section
101(c) of the Federal Mine Safety and
Health Act of 1977 and Title 30 of the
Code of Federal Regulations Part 44
govern the application, processing, and
disposition of petitions for modification.
I. Background
Section 101(c) of the Federal Mine
Safety and Health Act of 1977 (Mine
Act) allows the mine operator or
representative of miners to file a
petition to modify the application of any
mandatory safety standard to a coal or
other mine if the Secretary of Labor
determines that:
1. An alternative method of achieving
the result of such standard exists which
will at all times guarantee no less than
the same measure of protection afforded
the miners of such mine by such
standard; or
2. The application of such standard to
such mine will result in a diminution of
safety to the miners in such mine.
In addition, the regulations at 30 CFR
44.10 and 44.11 establish the
requirements for filing petitions for
modification.
II. Petitions for Modification
Docket Number: M–2020–014–C.
Petitioner: Westmoreland San Juan
Mining LLC, P.O. Box 561, Waterflow,
NM 87421.
Mine: San Juan Mine 1, MSHA I.D.
No. 29–02170, located in San Juan
County, New Mexico.
Regulation Affected: 30 CFR 75.500(d)
(Permissible electric equipment).
Modification Request: The petitioner
requests a modification of the existing
standard to permit an alternative
method of compliance to allow the use
of two Powered Air Purifying Respirator
(PAPR) devices (the 3MTM VersafloTM
TR–800 PAPR and the PAF–0060
CleanSpace EX PAPR) for the
respiratory protection of miners, in or
inby the last open crosscut.
The petitioner states that:
(a) The San Juan Mine 1 is an
underground coal mining operation that
E:\FR\FM\05AUN1.SGM
05AUN1
jbell on DSKJLSW7X2PROD with NOTICES
47418
Federal Register / Vol. 85, No. 151 / Wednesday, August 5, 2020 / Notices
uses longwall and continuous mining to
fuel the nearby San Juan Generating
Station.
(b) The current PAPR model approved
by MSHA is the 3M Airstream Mining
Headgear-Mounted PAPR system, which
was discontinued by 3M on June 1,
2020. There are no other MSHAapproved units. Because of that, the
petitioner is requesting the use of two
alternative PAPR units.
As an alternative to the existing
standard, the petitioner proposes the
following:
(a) The petitioner requests the
approval of the 3MTM VersafloTM TR–
800 PAPR, which is certified by UL
under the ANSI/UL 60079–11 standard
to be used in hazardous locations (it
meets the most onerous intrinsic safety
level and is acceptable for use in mines
with potential firedamp).
(b) The second product is the PAF–
0060 CleanSpace EX PAPR. It holds the
following approvals: EN
12942:1998+A2:2008 TM3 (Europe),
SANS 10338: 2009, (NRCS/8072/0090)
(South Africa), AS/NZS1716:2012
PAPR–P2 (Australia/NZ), ISO 9001
(Quality Management System), IECEx:
IEC 60079–0:2011 Ex ia I Ma, IECEx: IEC
60079–11:2011 Ex ib IIB T4 Gb, IIECEx
Quality Assurance: IEC 80079–34:2011,
ATEX/EN EX: EN 60079–0:2012 I M1 Ex
ia I Ma, ATEX/EN EX: EN 60079–
11:2012 II 2 G Ex ib IIB T4 Gb, ATEX
Quality Assurance: Annex IV of
Directive 94/9/EC (ATEX), EMC
Standard: CISPR 11: 2010: Group 1
Class B.
(c) Before energizing either product,
methane tests will be made in the mine
atmosphere, in accordance with 30 CFR
75.360 and 30 CFR 75.362. The tests
will continue in areas where the devices
are worn.
(d) The above products will be
examined before use and prior to being
taken underground to make sure that
they work according to the equipment
manufacturer’s recommendations and
maintained in safe operating conditions.
The examinations will include the
following:
(1) The instrument will be checked for
physical damage and the integrity of the
case;
(2) Batteries will be removed for
inspection for corrosion;
(3) Contact points will be inspected to
ensure a secure connection to the
battery;
(4) The battery will be reinserted
powered up and shut down to ensure
proper connections; and
(5) Battery compartment covers or
attachments will be checked to make
sure they are securely fastened.
VerDate Sep<11>2014
16:55 Aug 04, 2020
Jkt 250001
(6) If a product uses lithium cells, the
examination must ensure that lithium
cells and/or packs are not damaged (or
swollen in size).
(e) The products will not be put into
service until MSHA has inspected them
and deemed them in compliance with
the terms and conditions of this
petition.
(f) The products will not be used if
methane is found at or above 1.0
percent. If the methane levels are higher
than 1.0 percent while the products are
being used, the equipment will
immediately be deenergized and
withdrawn from affected areas.
(g) Hand-held methane detectors will
be MSHA approved and maintained in
permissible and proper operating
condition in accordance with 30 CFR
75.320(a). Methane detectors will
provide visual and audible warnings
when they detect methane at or above
1.0 percent.
(h) A qualified person, in accordance
with the definition in 30 CFR 75.151,
will continuously monitor for methane
immediately before and during the use
of these products. When crews are
working together, at least one qualified
person will monitor for methane
continuously. If continuous monitoring
systems are installed by a longwall face,
if they have audible and visual alarms
for detecting methane at 1.0 or higher,
this will satisfy the requirement for
monitoring methane.
(i) Batteries for these products will be
‘‘changed out’’ or ‘‘charged’’ in intake
air. Before each shift that these products
will be used, batteries for the equipment
will be charged so as not to need a
replacement during the shift.
(j) The 3MTM VersafloTM TR–800
PAPR will only use the 3M TR–830
Battery pack. This pack meets the
UL1642 or IEC 62133 standards for
safety. The following will be done for
battery packs:
(1) They will be charged on the
surface or in underground not within
150 feet of a worked-out area;
(2) they will be charged by the
following products: 3M Battery Charger
Kit TR–641N, or 3M 4-Station Battery
Charger Kit TR–644N;
(3) they will only be disassembled or
modified by those permitted by the
manufacturer of the equipment;
(4) the battery will not be exposed to
water (or get wet), not including
incidental exposure of sealed battery
packs as a result of overspray from dust
suppression sprays or equipment
cleaning;
(5) they will not be used or stored
near heat sources or placed in direct
sunlight; and
PO 00000
Frm 00081
Fmt 4703
Sfmt 4703
(6) they will not be used when there
is a performance decrease of greater
than 20 percent in battery operated
equipment (at the end of the product’s
life cycle). The battery will be disposed
of properly.
(k) Electromagnetic interference from
the products will be investigated by the
petitioner and all safety devices will be
worn by miners (devices such as
proximity detection system miner
wearable components, gas detectors,
tracking system components, and
communication devices). Before placing
the PAPR systems into service, the
petitioner will inform MSHA if any
interference is identified and how to
eliminate such interference. Miners will
be trained on the above.
(l) Miners using these PAPRs will be
trained to recognize hazards and
limitations associated with PAPRs.
(m) All section foremen, section crew
members, and others involved with
PAPRs will receive training, as required
in 30 CFR 48.7. The training will be
provided before use in this area.
(n) Within 60 days of when the order
becomes final, the petitioner will submit
revisions for their 30 CFR part 48
training plan. This will include using
the Self-Contained Self Rescuer while
using a PAPR, initial training, and
refresher training. For training, the
petitioner will complete the 5000–23
form (MSHA Certificate of Training).
(o) The petitioner asserts that the
proposed alternative method will at all
times guarantee no less than the same
measure of protection afforded by the
existing standard.
Docket Number: M–2020–015–C.
Petitioner: Westmoreland San Juan
Mining LLC, P.O. Box 561, Waterflow,
NM 87421.
Mine: San Juan Mine 1, MSHA I.D.
No. 29–02170, located in San Juan
County, New Mexico.
Regulation Affected: 30 CFR 75.507–
1 (Electric equipment other than powerconnection points; outby the last open
crosscut; return air; permissibility
requirements).
Modification Request: The petitioner
requests a modification of the existing
standard to permit an alternative
method of compliance to allow the use
of two Powered Air Purifying Respirator
(PAPR) devices (the 3MTM VersafloTM
TR–800 PAPR and the PAF–0060
CleanSpace EX PAPR) for the
respiratory protection of miners, in
return air outby the last open crosscut.
The petitioner states that:
(a) The San Juan Mine 1 is an
underground coal mining operation that
uses longwall and continuous mining to
fuel the nearby San Juan Generating
Station.
E:\FR\FM\05AUN1.SGM
05AUN1
jbell on DSKJLSW7X2PROD with NOTICES
Federal Register / Vol. 85, No. 151 / Wednesday, August 5, 2020 / Notices
(b) The current PAPR model approved
by MSHA is the 3M Airstream Mining
Headgear-Mounted PAPR system, which
was discontinued by 3M on June 1,
2020. There are no other MSHAapproved units. Because of that, the
petitioner is requesting the use of two
alternative PAPR units.
As an alternative to the existing
standard, the petitioner proposes the
following:
(a) The petitioner requests the
approval of the 3MTM VersafloTM TR–
800 PAPR, which is certified by UL
under the ANSI/UL 60079–11 standard
to be used in hazardous locations (it
meets the most onerous intrinsic safety
level and is acceptable for use in mines
with potential firedamp).
(b) The second product is the PAF–
0060 CleanSpace EX PAPR. It holds the
following approvals: EN
12942:1998+A2:2008 TM3 (Europe),
SANS 10338: 2009, (NRCS/8072/0090)
(South Africa), AS/NZS1716:2012
PAPR–P2 (Australia/NZ), ISO 9001
(Quality Management System), IECEx:
IEC 60079–0:2011 Ex ia I Ma, IECEx: IEC
60079–11:2011 Ex ib IIB T4 Gb, IIECEx
Quality Assurance: IEC 80079–34:2011,
ATEX/EN EX: EN 60079–0:2012 I M1 Ex
ia I Ma, ATEX/EN EX: EN 60079–
11:2012 II 2 G Ex ib IIB T4 Gb, ATEX
Quality Assurance: Annex IV of
Directive 94/9/EC (ATEX), EMC
Standard: CISPR 11: 2010: Group 1
Class B.
(c) Before energizing either product,
methane tests must be conducted in the
mine atmosphere, in accordance with 30
CFR 75.360 and 30 CFR 75.362. The
tests will continue in areas where the
devices are worn.
(d) The above products will be
examined before use and prior to being
taken underground to make sure that
they work according to the equipment
manufacturer’s recommendations and
maintained in safe operating conditions.
The examinations will include the
following:
(1) The instrument will be checked for
physical damage and the integrity of the
case;
(2) Batteries will be removed for
inspection for corrosion;
(3) Contact points will be inspected to
ensure a secure connection to the
battery;
(4) The battery will be reinserted and
the power up will be shut down to
ensure connections; and
(5) Battery compartment covers or
attachments will be checked to make
sure they are properly fastened.
(6) If a product uses lithium cells, the
examination must ensure that lithium
cells and/or packs are not damaged (or
swollen in size).
VerDate Sep<11>2014
16:55 Aug 04, 2020
Jkt 250001
(e) The products will not be put into
service until MSHA has inspected them
and deemed them in compliance with
the terms and conditions of this
petition.
(f) The products will not be used if
methane is found at or above 1.0
percent. If the methane levels are higher
than 1.0 percent while the products are
being used, the equipment will
immediately be deenergized and
withdrawn from affected areas.
(g) Hand-held methane detectors will
be MSHA approved and maintained in
proper conditions in accordance with 30
CFR 75.320(a). Methane detectors
should provide visual and audible
warnings when they detect methane at
or above 1.0 percent.
(h) A qualified person, in accordance
with the definition in 30 CFR 75.151,
will continuously monitor for methane
immediately before and during the use
of these products. When crews are
working together, at least one qualified
person will monitor for methane
continuously. If continuous monitoring
systems are installed by a longwall face,
if they have audible and visual alarms
for detecting methane at 1.0 or higher,
this will satisfy the requirement for
monitoring methane.
(i) Batteries for these products must
be ‘‘changed out’’ or ‘‘charged’’ in intake
air. Before the shift that these products
will be used during, batteries and
equipment will be charged so as not to
need a replacement during the shift.
(j) The 3MTM VersafloTM TR–800
PAPR will only use the 3M TR–830
Battery pack. This pack meets the
UL1642 or IEC 62133 standards for
safety. The following will be conducted
for battery packs:
(1) They will be charged on the
surface or in underground not within
150 feet of a worked-out area;
(2) they will be charged by the
following products: 3M Battery Charger
Kit TR–641N, or 3M 4-Station Battery
Charger Kit TR–644N;
(3) they will only be disassembled or
modified by those permitted by the
manufacturer of the equipment;
(4) the battery will not be exposed to
water (or get wet), not including
incidental exposure of sealed battery
packs as a result of overspray from dust
suppression sprays or equipment
cleaning;
(5) they will not be used near heat
sources or placed in direct sunlight; and
(6) they will not be used when there
is a performance decrease of greater
than 20 percent in battery operated
equipment (at the end of the product’s
life cycle). The battery will be disposed
of properly.
PO 00000
Frm 00082
Fmt 4703
Sfmt 4703
47419
(k) Electromagnetic interference from
the products will be investigated by the
petitioner and all safety devices will be
worn by miners (devices such as
proximity detection system miner
wearable components, gas detectors,
tracking system components, and
communication devices). Before placing
the PAPR systems into service, the
petitioner will inform MSHA if any
interference is identified and how to
eliminate such interference. Miners will
be trained on the above.
(l) Miners using these PAPRs will be
trained to recognize hazards and
limitations associated with PAPRs.
(m) All section foremen, section crew
members, and others involved with
PAPRs will receive training, as required
in 30 CFR 48.7. The training will be
provided before use in this area.
(n) Within 60 days of when the order
becomes final, the petitioner will submit
revisions for their 30 CFR part 48
training plan. This will include using
the Self-Contained Self Rescuer while
using a PAPR, initial training, and
refresher training. For training, the
petitioner will complete the 5000–23
form (MSHA Certificate of Training).
(o) The petitioner asserts that the
proposed alternative method will at all
times guarantee no less than the same
measure of protection afforded by the
existing standard.
Docket Number: M–2020–016–C.
Petitioner: Westmoreland San Juan
Mining LLC, P.O. Box 561, Waterflow,
NM 87421.
Mine: San Juan Mine 1, MSHA I.D.
No. 29–02170, located in San Juan
County, New Mexico.
Regulation Affected: 30 CFR 75.1002
(Installation of electric equipment and
conductors; permissibility).
Modification Request: The petitioner
requests a modification of the existing
standard to permit an alternative
method of compliance to allow the use
of two Powered Air Purifying Respirator
(PAPR) devices (the 3MTM VersafloTM
TR–800 PAPR and the PAF–0060
CleanSpace EX PAPR) for the
respiratory protection of miners, within
150 feet of pillar workings or longwall
faces.
The petitioner states that:
(a) The San Juan Mine 1 is an
underground coal mining operation that
uses longwall and continuous mining to
fuel the nearby San Juan Generating
Station.
(b) The current PAPR model approved
by MSHA is the 3M Airstream Mining
Headgear-Mounted PAPR system, which
was discontinued by 3M on June 1,
2020. There are no other MSHAapproved units. Because of that, the
E:\FR\FM\05AUN1.SGM
05AUN1
jbell on DSKJLSW7X2PROD with NOTICES
47420
Federal Register / Vol. 85, No. 151 / Wednesday, August 5, 2020 / Notices
petitioner is requesting the use of two
alternative PAPR units.
As an alternative to the existing
standard, the petitioner proposes the
following:
(a) The petitioner requests the
approval of the 3MTM VersafloTM TR–
800 PAPR, which is certified by UL
under the ANSI/UL 60079–11 standard
to be used in hazardous locations (it
meets the most onerous intrinsic safety
level and is acceptable for use in mines
with potential firedamp).
(b) The second product is the PAF–
0060 CleanSpace EX PAPR. It holds the
following approvals: EN
12942:1998+A2:2008 TM3 (Europe),
SANS 10338: 2009, (NRCS/8072/0090)
(South Africa), AS/NZS1716:2012
PAPR–P2 (Australia/NZ), ISO 9001
(Quality Management System), IECEx:
IEC 60079–0:2011 Ex ia I Ma, IECEx: IEC
60079–11:2011 Ex ib IIB T4 Gb, IIECEx
Quality Assurance: IEC 80079–34:2011,
ATEX/EN EX: EN 60079–0:2012 I M1 Ex
ia I Ma, ATEX/EN EX: EN 60079–
11:2012 II 2 G Ex ib IIB T4 Gb, ATEX
Quality Assurance: Annex IV of
Directive 94/9/EC (ATEX), EMC
Standard: CISPR 11: 2010: Group 1
Class B.
(c) Before energizing either product,
methane tests must be conducted in the
mine atmosphere, in accordance with 30
CFR 75.360 and 30 CFR 75.362. The
tests will continue in areas where the
devices are worn.
(d) The above products will be
examined before use and prior to being
taken underground to make sure that
they work according to the equipment
manufacturer’s recommendations and
maintained in safe operating conditions.
The examinations will include the
following:
(1) The instrument will be checked for
physical damage and the integrity of the
case;
(2) Batteries will be removed for
inspection for corrosion;
(3) Contact points will be inspected to
ensure a secure connection to the
battery;
(4) The battery will be reinserted and
the power up will be shut down to
ensure connections; and
(5) Battery compartment covers or
attachments will be checked to make
sure they are properly fastened.
(6) If a product uses lithium cells, the
examination must ensure that lithium
cells and/or packs are not damaged (or
swollen in size).
(e) The products will not be put into
service until MSHA has inspected them
and deemed them in compliance with
the terms and conditions of this
petition.
VerDate Sep<11>2014
16:55 Aug 04, 2020
Jkt 250001
(f) The products will not be used if
methane is found at or above 1.0
percent. If the methane levels are higher
than 1.0 percent while the products are
being used, the equipment will
immediately be deenergized and
withdrawn from affected areas.
(g) Hand-held methane detectors will
be MSHA approved and maintained in
proper conditions in accordance with 30
CFR 75.320(a). Methane detectors
should provide visual and audible
warnings when they detect methane at
or above 1.0 percent.
(h) A qualified person, in accordance
with the definition in 30 CFR 75.151,
will continuously monitor for methane
immediately before and during the use
of these products. When crews are
working together, at least one qualified
person will monitor for methane
continuously. If continuous monitoring
systems are installed by a longwall face,
if they have audible and visual alarms
for detecting methane at 1.0 or higher,
this will satisfy the requirement for
monitoring methane.
(i) Batteries for these products must
be ‘‘changed out’’ or ‘‘charged’’ in intake
air. Before the shift that these products
will be used during, batteries and
equipment will be charged so as not to
need a replacement during the shift.
(j) The 3MTM VersafloTM TR–800
PAPR will only use the 3M TR–830
Battery pack. This pack meets the
UL1642 or IEC 62133 standards for
safety. The following will be conducted
for battery packs:
(1) They will be charged on the
surface or in underground not within
150 feet of a worked-out area;
(2) they will be charged by the
following products: 3M Battery Charger
Kit TR–641N, or 3M 4-Station Battery
Charger Kit TR–644N;
(3) they will only be disassembled or
modified by those permitted by the
manufacturer of the equipment;
(4) the battery will not be exposed to
water (or get wet), not including
incidental exposure of sealed battery
packs as a result of overspray from dust
suppression sprays or equipment
cleaning;
(5) they will not be used near heat
sources or placed in direct sunlight; and
(6) they will not be used when there
is a performance decrease of greater
than 20 percent in battery operated
equipment (at the end of the product’s
life cycle). The battery will be disposed
of properly.
(k) Electromagnetic interference from
the products will be investigated by the
petitioner and all safety devices will be
worn by miners (devices such as
proximity detection system miner
wearable components, gas detectors,
PO 00000
Frm 00083
Fmt 4703
Sfmt 4703
tracking system components, and
communication devices). Before placing
the PAPR systems into service, the
petitioner will inform MSHA if any
interference is identified and how to
eliminate such interference. Miners will
be trained on the above.
(l) Miners using these PAPRs will be
trained to recognize hazards and
limitations associated with PAPRs.
(m) All section foremen, section crew
members, and others involved with
PAPRs will receive training, as required
in 30 CFR 48.7. The training will be
provided before use in this area.
(n) Within 60 days of when the order
becomes final, the petitioner will submit
revisions for their 30 CFR part 48
training plan. This will include using
the Self-Contained Self Rescuer while
using a PAPR, initial training, and
refresher training. For training, the
petitioner will complete the 5000–23
form (MSHA Certificate of Training).
(o) The petitioner asserts that the
proposed alternative method will at all
times guarantee no less than the same
measure of protection afforded by the
existing standard.
Docket Number: M–2020–001–M.
Petitioner: Morton Salt, Inc., PO Box
1496, Weeks Island, LA 70560.
Mine: Weeks Island Mine and Mill,
MSHA I.D. No. 16–00970, located in
Iberia County, Louisiana.
Regulation Affected: 30 CFR 57.22603
(Blasting from the surface (II–A mines)).
Modification Request: The petitioner
is requesting a modification of 30 CFR
57.22603(d) to allow experienced,
competent employees to reenter the
mine after a blasting, following the
proposed guidelines of this petition.
Employees would reenter the mine to
determine if a monitor is not working
properly, to isolate the area affected,
and to make relevant ventilation
changes to reduce methane levels. The
petitioner is requesting a modification
to 30 CFR 57.22603(c) to allow miners
to reenter areas of the mine that are
unaffected after blasting—non-blast
areas when methane levels are below
0.5%.
The petitioner states that:
(a) The Weeks Island mine is a
Category II–A gassy mine. Due to this
status it is required to blast from the
surface without miners underground.
The petition proposes the following:
(a) If monitoring systems show that
methane levels in the mine are at 0.5%
or above then the mine will be
ventilated for at least 45 minutes and
the mine power will remain
deenergized. If methane levels remain
above 0.5% or above, the power will
continue to be deenergized and a
competent person, will enter the mine,
E:\FR\FM\05AUN1.SGM
05AUN1
jbell on DSKJLSW7X2PROD with NOTICES
Federal Register / Vol. 85, No. 151 / Wednesday, August 5, 2020 / Notices
to test for methane and ventilation
changes (for lowering methane levels).
(b) The mine will be entered from the
fresh air intake shaft. The competent
person will check ventilation controls
on the fresh air side to ensure there is
no damage.
(c) A miner is considered competent
if that person is trained on how to use
a hand-held monitor and knows how
and where to test for methane. If
someone is a qualified electrician then
they are competent in addressing
electrical issues underground.
(d) Before going underground, to
ensure the calibration of all instruments,
a bump test will be completed on all
hand-held monitors. All competent
persons will be trained on these
procedures and training will be
recorded on a 5000–23 form.
(e) If there is damage to ventilation
controls, a competent person will repair
them before leaving the mine through
the fresh air intake. Repairs will be
made in fresh air only. The mine power
will continue to be off for an added 45
minutes while ventilation is used to
lower methane levels. If methane is still
at 0.5% or above then a competent
person will enter the mine again from a
fresh air intake to the active landing
using a permissible ride. Methane levels
will be checked via hand-held monitors
and a monitor on a pole against the
ceiling. Every area that reads methane
levels of 0.5% or above will be verified,
barricaded, and posted to restrict entry.
(f) The posted and barricaded areas
affected by methane will be at least 200
feet away from the methane entry point.
Such an area will only be opened when
levels fall below 0.5%. Power to the
affected areas and the out-by exhaust air
route will be disconnected, locked and
tagged out by a competent person. After
that, all competent persons who entered
the mine will return to the surface.
Underground power will be reenergized
outside the affected areas so that
auxiliary fans can help lower methane
levels and the mining operations can
resume (outside of affected areas).
Affected areas will not be opened up
until they are below 0.5%; levels will be
checked beginning at the barricaded
area and working back into the affected
areas once the barricade is in place.
(g) In unaffected areas of the mine,
allowing workers to enter does not
create any greater hazard than using
energized equipment for work in
unaffected areas when methane is below
0.5% in another area. After a blast, all
methane monitors lose battery power
within 24 hours, triggering 30 CFR
57.22603(c) if methane levels are at
0.5% for 24 hours. The petitioner states
that it creates a greater hazard for
VerDate Sep<11>2014
16:55 Aug 04, 2020
Jkt 250001
miners to go underground every 24
hours to change batteries on methane
monitors rather than allowing an entry
where miners can adjust ventilators to
remove gas from the mine effectively.
(h) The petitioner asserts that the
proposed alternative method will at all
times guarantee no less than the same
measure of protection afforded by the
standard, 30 CFR 57.22603.
Docket Number: M–2020–002–M.
Petitioner: U.S. Silica Company, 5263
Edmund Highway, West Columbia,
South Carolina 29170.
Mine: Columbia Plant, MSHA I.D. No.
38–00138, located in Lexington County,
South Carolina.
Regulation Affected: 30 CFR 56.13020
(Use of compressed air).
Modification Request: The petitioner
requests a modification of the existing
standard to permit an alternative
method of an air compression system for
cleaning clothes after mining
operations, which will provide no less
a degree of safety than that provided by
the standard.
The petitioner states that:
(a) The alternative method provides a
direct reduction of miners’ exposure to
respirable dust, thus reducing their
health risks. The proposed alternative
method has been jointly developed
between Unimin Corporation and the
National Institute for Occupational
Safety and Health (NIOSH) and
successfully tested by the NIOSH.
The petition proposes the following:
(a) Only miners trained in the
operation of the clothes cleaning booth
will be permitted to use the booth to
clean their clothes.
(b) Petitioner will incorporate the
NIOSH Clothes Cleaning Process and
manufacturer’s instruction manual into
their MSHA Part 46 training plan and
train affected miners in the process.
(c) Miners entering the booth will
examine valves and nozzles for damage
or malfunction and will close the door
fully before opening the air valve. Any
defects will be repaired prior to the
booth being used.
(d) Miners entering the booth will
wear eye protection, ear plugs or muffs
for hearing protection, and respiratory
protection. Respiratory protection will
consist of a full-face or half-mask
respirator that meets or exceeds the
minimum requirements of a N95 filter to
which the miner has been fit-tested. As
an alternative, the use of a full-face
respirator will meet the requirements for
eye protection. A sign will be
conspicuously posted requiring the use
of the above personal protective
equipment when the booth is entered.
(e) Air flow through the booth will be
at least 2,000 cubic feet per minute to
PO 00000
Frm 00084
Fmt 4703
Sfmt 9990
47421
maintain negative pressure during use
of the cleaning booth in order to prevent
contamination of the environment
outside the booth. Airflow will be in a
downward direction, thereby moving
contaminants away from the miner’s
breathing zone.
(f) Air pressure through the spray
manifold will be limited to 30 pounds
per square inch or less. A lock box with
a single, plant manager controlled key
will be used to prevent regulator
tampering.
(g) The air spray manifold will consist
of schedule 80 steel pipe that has a
failure pressure of 1,300 pounds per
square inch and will be capped at the
base and actuated by an electrically
controlled ball valve at the top.
(h) Air nozzles will not exceed 30
pounds per square inch gauge.
(i) The upper most spray of the spray
manifold will be located below the
booth user’s breathing zone. Some type
of mechanical device can be used to
cover the upper air nozzles to meet the
specific height of the user.
(j) Air nozzles will be guarded to
eliminate the possibility of incidental
contact, which could create mechanical
damage to the air nozzles during the
clothes cleaning process.
(k) Periodic maintenance checks of
the booth will be conducted in
accordance with the recommendations
contained in the manufacturer’s
instruction manual.
(l) The air receiver tank supplying air
to the manifold system will be of
sufficient volume to permit no less than
20 seconds of continuous cleaning time.
(m) An appropriate hazard warning
sign will be posted on the booth to state
at a minimum, ‘‘Compressed Air’’ and
‘‘Respirable Dust’’.
(n) A pressure relief valve designed
for the booth’s air reservoir will be
installed.
(o) The mine will exhaust dust-laden
air from the booth into a local exhaust
ventilation system or duct outside the
facility while ensuring there is no reentrainment back into the structure.
The petitioner asserts that the
proposed alternative method will at all
times guarantee no less than the same
measure of protection afforded by the
standard.
Roslyn Fontaine,
Deputy Director,Office of Standards,
Regulations, and Variances.
[FR Doc. 2020–17018 Filed 8–4–20; 8:45 am]
BILLING CODE 4520–43–P
E:\FR\FM\05AUN1.SGM
05AUN1
Agencies
[Federal Register Volume 85, Number 151 (Wednesday, August 5, 2020)]
[Notices]
[Pages 47417-47421]
From the Federal Register Online via the Government Publishing Office [www.gpo.gov]
[FR Doc No: 2020-17018]
-----------------------------------------------------------------------
DEPARTMENT OF LABOR
Mine Safety and Health Administration
Petitions for Modification of Application of Existing Mandatory
Safety Standards
AGENCY: Mine Safety and Health Administration, Labor.
ACTION: Notice.
-----------------------------------------------------------------------
SUMMARY: This notice is a summary of 5 petitions for modification
submitted to the Mine Safety and Health Administration (MSHA) by the
parties listed below.
DATES: All comments on the petitions must be received by MSHA's Office
of Standards, Regulations, and Variances on or before September 4,
2020.
ADDRESSES: You may submit your comments, identified by ``docket
number'' on the subject line, by any of the following methods:
1. Electronic Mail: [email protected]. Include the docket
number of the petition in the subject line of the message.
2. Facsimile: 202-693-9441.
3. Regular Mail or Hand Delivery: MSHA, Office of Standards,
Regulations, and Variances, 201 12th Street South, Suite 4E401,
Arlington, Virginia 22202-5452, Attention: Roslyn B. Fontaine, Deputy
Director, Office of Standards, Regulations, and Variances. Persons
delivering documents are required to check in at the receptionist's
desk in Suite 4E401. Individuals may inspect copies of the petition and
comments during normal business hours at the address listed above.
MSHA will consider only comments postmarked by the U.S. Postal
Service or proof of delivery from another delivery service such as UPS
or Federal Express on or before the deadline for comments.
FOR FURTHER INFORMATION CONTACT: Aromie Noe, Office of Standards,
Regulations, and Variances at 202-693-9557 (voice), [email protected] (email), or 202-693-9441 (facsimile). [These are not toll-
free numbers.]
SUPPLEMENTARY INFORMATION: Section 101(c) of the Federal Mine Safety
and Health Act of 1977 and Title 30 of the Code of Federal Regulations
Part 44 govern the application, processing, and disposition of
petitions for modification.
I. Background
Section 101(c) of the Federal Mine Safety and Health Act of 1977
(Mine Act) allows the mine operator or representative of miners to file
a petition to modify the application of any mandatory safety standard
to a coal or other mine if the Secretary of Labor determines that:
1. An alternative method of achieving the result of such standard
exists which will at all times guarantee no less than the same measure
of protection afforded the miners of such mine by such standard; or
2. The application of such standard to such mine will result in a
diminution of safety to the miners in such mine.
In addition, the regulations at 30 CFR 44.10 and 44.11 establish
the requirements for filing petitions for modification.
II. Petitions for Modification
Docket Number: M-2020-014-C.
Petitioner: Westmoreland San Juan Mining LLC, P.O. Box 561,
Waterflow, NM 87421.
Mine: San Juan Mine 1, MSHA I.D. No. 29-02170, located in San Juan
County, New Mexico.
Regulation Affected: 30 CFR 75.500(d) (Permissible electric
equipment).
Modification Request: The petitioner requests a modification of the
existing standard to permit an alternative method of compliance to
allow the use of two Powered Air Purifying Respirator (PAPR) devices
(the 3MTM VersafloTM TR-800 PAPR and the PAF-0060
CleanSpace EX PAPR) for the respiratory protection of miners, in or
inby the last open crosscut.
The petitioner states that:
(a) The San Juan Mine 1 is an underground coal mining operation
that
[[Page 47418]]
uses longwall and continuous mining to fuel the nearby San Juan
Generating Station.
(b) The current PAPR model approved by MSHA is the 3M Airstream
Mining Headgear-Mounted PAPR system, which was discontinued by 3M on
June 1, 2020. There are no other MSHA-approved units. Because of that,
the petitioner is requesting the use of two alternative PAPR units.
As an alternative to the existing standard, the petitioner proposes
the following:
(a) The petitioner requests the approval of the 3MTM
VersafloTM TR-800 PAPR, which is certified by UL under the
ANSI/UL 60079-11 standard to be used in hazardous locations (it meets
the most onerous intrinsic safety level and is acceptable for use in
mines with potential firedamp).
(b) The second product is the PAF-0060 CleanSpace EX PAPR. It holds
the following approvals: EN 12942:1998+A2:2008 TM3 (Europe), SANS
10338: 2009, (NRCS/8072/0090) (South Africa), AS/NZS1716:2012 PAPR-P2
(Australia/NZ), ISO 9001 (Quality Management System), IECEx: IEC 60079-
0:2011 Ex ia I Ma, IECEx: IEC 60079-11:2011 Ex ib IIB T4 Gb, IIECEx
Quality Assurance: IEC 80079-34:2011, ATEX/EN EX: EN 60079-0:2012 I M1
Ex ia I Ma, ATEX/EN EX: EN 60079-11:2012 II 2 G Ex ib IIB T4 Gb, ATEX
Quality Assurance: Annex IV of Directive 94/9/EC (ATEX), EMC Standard:
CISPR 11: 2010: Group 1 Class B.
(c) Before energizing either product, methane tests will be made in
the mine atmosphere, in accordance with 30 CFR 75.360 and 30 CFR
75.362. The tests will continue in areas where the devices are worn.
(d) The above products will be examined before use and prior to
being taken underground to make sure that they work according to the
equipment manufacturer's recommendations and maintained in safe
operating conditions. The examinations will include the following:
(1) The instrument will be checked for physical damage and the
integrity of the case;
(2) Batteries will be removed for inspection for corrosion;
(3) Contact points will be inspected to ensure a secure connection
to the battery;
(4) The battery will be reinserted powered up and shut down to
ensure proper connections; and
(5) Battery compartment covers or attachments will be checked to
make sure they are securely fastened.
(6) If a product uses lithium cells, the examination must ensure
that lithium cells and/or packs are not damaged (or swollen in size).
(e) The products will not be put into service until MSHA has
inspected them and deemed them in compliance with the terms and
conditions of this petition.
(f) The products will not be used if methane is found at or above
1.0 percent. If the methane levels are higher than 1.0 percent while
the products are being used, the equipment will immediately be
deenergized and withdrawn from affected areas.
(g) Hand-held methane detectors will be MSHA approved and
maintained in permissible and proper operating condition in accordance
with 30 CFR 75.320(a). Methane detectors will provide visual and
audible warnings when they detect methane at or above 1.0 percent.
(h) A qualified person, in accordance with the definition in 30 CFR
75.151, will continuously monitor for methane immediately before and
during the use of these products. When crews are working together, at
least one qualified person will monitor for methane continuously. If
continuous monitoring systems are installed by a longwall face, if they
have audible and visual alarms for detecting methane at 1.0 or higher,
this will satisfy the requirement for monitoring methane.
(i) Batteries for these products will be ``changed out'' or
``charged'' in intake air. Before each shift that these products will
be used, batteries for the equipment will be charged so as not to need
a replacement during the shift.
(j) The 3MTM VersafloTM TR-800 PAPR will only
use the 3M TR-830 Battery pack. This pack meets the UL1642 or IEC 62133
standards for safety. The following will be done for battery packs:
(1) They will be charged on the surface or in underground not
within 150 feet of a worked-out area;
(2) they will be charged by the following products: 3M Battery
Charger Kit TR-641N, or 3M 4-Station Battery Charger Kit TR-644N;
(3) they will only be disassembled or modified by those permitted
by the manufacturer of the equipment;
(4) the battery will not be exposed to water (or get wet), not
including incidental exposure of sealed battery packs as a result of
overspray from dust suppression sprays or equipment cleaning;
(5) they will not be used or stored near heat sources or placed in
direct sunlight; and
(6) they will not be used when there is a performance decrease of
greater than 20 percent in battery operated equipment (at the end of
the product's life cycle). The battery will be disposed of properly.
(k) Electromagnetic interference from the products will be
investigated by the petitioner and all safety devices will be worn by
miners (devices such as proximity detection system miner wearable
components, gas detectors, tracking system components, and
communication devices). Before placing the PAPR systems into service,
the petitioner will inform MSHA if any interference is identified and
how to eliminate such interference. Miners will be trained on the
above.
(l) Miners using these PAPRs will be trained to recognize hazards
and limitations associated with PAPRs.
(m) All section foremen, section crew members, and others involved
with PAPRs will receive training, as required in 30 CFR 48.7. The
training will be provided before use in this area.
(n) Within 60 days of when the order becomes final, the petitioner
will submit revisions for their 30 CFR part 48 training plan. This will
include using the Self-Contained Self Rescuer while using a PAPR,
initial training, and refresher training. For training, the petitioner
will complete the 5000-23 form (MSHA Certificate of Training).
(o) The petitioner asserts that the proposed alternative method
will at all times guarantee no less than the same measure of protection
afforded by the existing standard.
Docket Number: M-2020-015-C.
Petitioner: Westmoreland San Juan Mining LLC, P.O. Box 561,
Waterflow, NM 87421.
Mine: San Juan Mine 1, MSHA I.D. No. 29-02170, located in San Juan
County, New Mexico.
Regulation Affected: 30 CFR 75.507-1 (Electric equipment other than
power-connection points; outby the last open crosscut; return air;
permissibility requirements).
Modification Request: The petitioner requests a modification of the
existing standard to permit an alternative method of compliance to
allow the use of two Powered Air Purifying Respirator (PAPR) devices
(the 3MTM VersafloTM TR-800 PAPR and the PAF-0060
CleanSpace EX PAPR) for the respiratory protection of miners, in return
air outby the last open crosscut.
The petitioner states that:
(a) The San Juan Mine 1 is an underground coal mining operation
that uses longwall and continuous mining to fuel the nearby San Juan
Generating Station.
[[Page 47419]]
(b) The current PAPR model approved by MSHA is the 3M Airstream
Mining Headgear-Mounted PAPR system, which was discontinued by 3M on
June 1, 2020. There are no other MSHA-approved units. Because of that,
the petitioner is requesting the use of two alternative PAPR units.
As an alternative to the existing standard, the petitioner proposes
the following:
(a) The petitioner requests the approval of the 3MTM
VersafloTM TR-800 PAPR, which is certified by UL under the
ANSI/UL 60079-11 standard to be used in hazardous locations (it meets
the most onerous intrinsic safety level and is acceptable for use in
mines with potential firedamp).
(b) The second product is the PAF-0060 CleanSpace EX PAPR. It holds
the following approvals: EN 12942:1998+A2:2008 TM3 (Europe), SANS
10338: 2009, (NRCS/8072/0090) (South Africa), AS/NZS1716:2012 PAPR-P2
(Australia/NZ), ISO 9001 (Quality Management System), IECEx: IEC 60079-
0:2011 Ex ia I Ma, IECEx: IEC 60079-11:2011 Ex ib IIB T4 Gb, IIECEx
Quality Assurance: IEC 80079-34:2011, ATEX/EN EX: EN 60079-0:2012 I M1
Ex ia I Ma, ATEX/EN EX: EN 60079-11:2012 II 2 G Ex ib IIB T4 Gb, ATEX
Quality Assurance: Annex IV of Directive 94/9/EC (ATEX), EMC Standard:
CISPR 11: 2010: Group 1 Class B.
(c) Before energizing either product, methane tests must be
conducted in the mine atmosphere, in accordance with 30 CFR 75.360 and
30 CFR 75.362. The tests will continue in areas where the devices are
worn.
(d) The above products will be examined before use and prior to
being taken underground to make sure that they work according to the
equipment manufacturer's recommendations and maintained in safe
operating conditions. The examinations will include the following:
(1) The instrument will be checked for physical damage and the
integrity of the case;
(2) Batteries will be removed for inspection for corrosion;
(3) Contact points will be inspected to ensure a secure connection
to the battery;
(4) The battery will be reinserted and the power up will be shut
down to ensure connections; and
(5) Battery compartment covers or attachments will be checked to
make sure they are properly fastened.
(6) If a product uses lithium cells, the examination must ensure
that lithium cells and/or packs are not damaged (or swollen in size).
(e) The products will not be put into service until MSHA has
inspected them and deemed them in compliance with the terms and
conditions of this petition.
(f) The products will not be used if methane is found at or above
1.0 percent. If the methane levels are higher than 1.0 percent while
the products are being used, the equipment will immediately be
deenergized and withdrawn from affected areas.
(g) Hand-held methane detectors will be MSHA approved and
maintained in proper conditions in accordance with 30 CFR 75.320(a).
Methane detectors should provide visual and audible warnings when they
detect methane at or above 1.0 percent.
(h) A qualified person, in accordance with the definition in 30 CFR
75.151, will continuously monitor for methane immediately before and
during the use of these products. When crews are working together, at
least one qualified person will monitor for methane continuously. If
continuous monitoring systems are installed by a longwall face, if they
have audible and visual alarms for detecting methane at 1.0 or higher,
this will satisfy the requirement for monitoring methane.
(i) Batteries for these products must be ``changed out'' or
``charged'' in intake air. Before the shift that these products will be
used during, batteries and equipment will be charged so as not to need
a replacement during the shift.
(j) The 3MTM VersafloTM TR-800 PAPR will only
use the 3M TR-830 Battery pack. This pack meets the UL1642 or IEC 62133
standards for safety. The following will be conducted for battery
packs:
(1) They will be charged on the surface or in underground not
within 150 feet of a worked-out area;
(2) they will be charged by the following products: 3M Battery
Charger Kit TR-641N, or 3M 4-Station Battery Charger Kit TR-644N;
(3) they will only be disassembled or modified by those permitted
by the manufacturer of the equipment;
(4) the battery will not be exposed to water (or get wet), not
including incidental exposure of sealed battery packs as a result of
overspray from dust suppression sprays or equipment cleaning;
(5) they will not be used near heat sources or placed in direct
sunlight; and
(6) they will not be used when there is a performance decrease of
greater than 20 percent in battery operated equipment (at the end of
the product's life cycle). The battery will be disposed of properly.
(k) Electromagnetic interference from the products will be
investigated by the petitioner and all safety devices will be worn by
miners (devices such as proximity detection system miner wearable
components, gas detectors, tracking system components, and
communication devices). Before placing the PAPR systems into service,
the petitioner will inform MSHA if any interference is identified and
how to eliminate such interference. Miners will be trained on the
above.
(l) Miners using these PAPRs will be trained to recognize hazards
and limitations associated with PAPRs.
(m) All section foremen, section crew members, and others involved
with PAPRs will receive training, as required in 30 CFR 48.7. The
training will be provided before use in this area.
(n) Within 60 days of when the order becomes final, the petitioner
will submit revisions for their 30 CFR part 48 training plan. This will
include using the Self-Contained Self Rescuer while using a PAPR,
initial training, and refresher training. For training, the petitioner
will complete the 5000-23 form (MSHA Certificate of Training).
(o) The petitioner asserts that the proposed alternative method
will at all times guarantee no less than the same measure of protection
afforded by the existing standard.
Docket Number: M-2020-016-C.
Petitioner: Westmoreland San Juan Mining LLC, P.O. Box 561,
Waterflow, NM 87421.
Mine: San Juan Mine 1, MSHA I.D. No. 29-02170, located in San Juan
County, New Mexico.
Regulation Affected: 30 CFR 75.1002 (Installation of electric
equipment and conductors; permissibility).
Modification Request: The petitioner requests a modification of the
existing standard to permit an alternative method of compliance to
allow the use of two Powered Air Purifying Respirator (PAPR) devices
(the 3MTM VersafloTM TR-800 PAPR and the PAF-0060
CleanSpace EX PAPR) for the respiratory protection of miners, within
150 feet of pillar workings or longwall faces.
The petitioner states that:
(a) The San Juan Mine 1 is an underground coal mining operation
that uses longwall and continuous mining to fuel the nearby San Juan
Generating Station.
(b) The current PAPR model approved by MSHA is the 3M Airstream
Mining Headgear-Mounted PAPR system, which was discontinued by 3M on
June 1, 2020. There are no other MSHA-approved units. Because of that,
the
[[Page 47420]]
petitioner is requesting the use of two alternative PAPR units.
As an alternative to the existing standard, the petitioner proposes
the following:
(a) The petitioner requests the approval of the 3MTM
VersafloTM TR-800 PAPR, which is certified by UL under the
ANSI/UL 60079-11 standard to be used in hazardous locations (it meets
the most onerous intrinsic safety level and is acceptable for use in
mines with potential firedamp).
(b) The second product is the PAF-0060 CleanSpace EX PAPR. It holds
the following approvals: EN 12942:1998+A2:2008 TM3 (Europe), SANS
10338: 2009, (NRCS/8072/0090) (South Africa), AS/NZS1716:2012 PAPR-P2
(Australia/NZ), ISO 9001 (Quality Management System), IECEx: IEC 60079-
0:2011 Ex ia I Ma, IECEx: IEC 60079-11:2011 Ex ib IIB T4 Gb, IIECEx
Quality Assurance: IEC 80079-34:2011, ATEX/EN EX: EN 60079-0:2012 I M1
Ex ia I Ma, ATEX/EN EX: EN 60079-11:2012 II 2 G Ex ib IIB T4 Gb, ATEX
Quality Assurance: Annex IV of Directive 94/9/EC (ATEX), EMC Standard:
CISPR 11: 2010: Group 1 Class B.
(c) Before energizing either product, methane tests must be
conducted in the mine atmosphere, in accordance with 30 CFR 75.360 and
30 CFR 75.362. The tests will continue in areas where the devices are
worn.
(d) The above products will be examined before use and prior to
being taken underground to make sure that they work according to the
equipment manufacturer's recommendations and maintained in safe
operating conditions. The examinations will include the following:
(1) The instrument will be checked for physical damage and the
integrity of the case;
(2) Batteries will be removed for inspection for corrosion;
(3) Contact points will be inspected to ensure a secure connection
to the battery;
(4) The battery will be reinserted and the power up will be shut
down to ensure connections; and
(5) Battery compartment covers or attachments will be checked to
make sure they are properly fastened.
(6) If a product uses lithium cells, the examination must ensure
that lithium cells and/or packs are not damaged (or swollen in size).
(e) The products will not be put into service until MSHA has
inspected them and deemed them in compliance with the terms and
conditions of this petition.
(f) The products will not be used if methane is found at or above
1.0 percent. If the methane levels are higher than 1.0 percent while
the products are being used, the equipment will immediately be
deenergized and withdrawn from affected areas.
(g) Hand-held methane detectors will be MSHA approved and
maintained in proper conditions in accordance with 30 CFR 75.320(a).
Methane detectors should provide visual and audible warnings when they
detect methane at or above 1.0 percent.
(h) A qualified person, in accordance with the definition in 30 CFR
75.151, will continuously monitor for methane immediately before and
during the use of these products. When crews are working together, at
least one qualified person will monitor for methane continuously. If
continuous monitoring systems are installed by a longwall face, if they
have audible and visual alarms for detecting methane at 1.0 or higher,
this will satisfy the requirement for monitoring methane.
(i) Batteries for these products must be ``changed out'' or
``charged'' in intake air. Before the shift that these products will be
used during, batteries and equipment will be charged so as not to need
a replacement during the shift.
(j) The 3MTM VersafloTM TR-800 PAPR will only
use the 3M TR-830 Battery pack. This pack meets the UL1642 or IEC 62133
standards for safety. The following will be conducted for battery
packs:
(1) They will be charged on the surface or in underground not
within 150 feet of a worked-out area;
(2) they will be charged by the following products: 3M Battery
Charger Kit TR-641N, or 3M 4-Station Battery Charger Kit TR-644N;
(3) they will only be disassembled or modified by those permitted
by the manufacturer of the equipment;
(4) the battery will not be exposed to water (or get wet), not
including incidental exposure of sealed battery packs as a result of
overspray from dust suppression sprays or equipment cleaning;
(5) they will not be used near heat sources or placed in direct
sunlight; and
(6) they will not be used when there is a performance decrease of
greater than 20 percent in battery operated equipment (at the end of
the product's life cycle). The battery will be disposed of properly.
(k) Electromagnetic interference from the products will be
investigated by the petitioner and all safety devices will be worn by
miners (devices such as proximity detection system miner wearable
components, gas detectors, tracking system components, and
communication devices). Before placing the PAPR systems into service,
the petitioner will inform MSHA if any interference is identified and
how to eliminate such interference. Miners will be trained on the
above.
(l) Miners using these PAPRs will be trained to recognize hazards
and limitations associated with PAPRs.
(m) All section foremen, section crew members, and others involved
with PAPRs will receive training, as required in 30 CFR 48.7. The
training will be provided before use in this area.
(n) Within 60 days of when the order becomes final, the petitioner
will submit revisions for their 30 CFR part 48 training plan. This will
include using the Self-Contained Self Rescuer while using a PAPR,
initial training, and refresher training. For training, the petitioner
will complete the 5000-23 form (MSHA Certificate of Training).
(o) The petitioner asserts that the proposed alternative method
will at all times guarantee no less than the same measure of protection
afforded by the existing standard.
Docket Number: M-2020-001-M.
Petitioner: Morton Salt, Inc., PO Box 1496, Weeks Island, LA 70560.
Mine: Weeks Island Mine and Mill, MSHA I.D. No. 16-00970, located
in Iberia County, Louisiana.
Regulation Affected: 30 CFR 57.22603 (Blasting from the surface
(II-A mines)).
Modification Request: The petitioner is requesting a modification
of 30 CFR 57.22603(d) to allow experienced, competent employees to
reenter the mine after a blasting, following the proposed guidelines of
this petition. Employees would reenter the mine to determine if a
monitor is not working properly, to isolate the area affected, and to
make relevant ventilation changes to reduce methane levels. The
petitioner is requesting a modification to 30 CFR 57.22603(c) to allow
miners to reenter areas of the mine that are unaffected after
blasting--non-blast areas when methane levels are below 0.5%.
The petitioner states that:
(a) The Weeks Island mine is a Category II-A gassy mine. Due to
this status it is required to blast from the surface without miners
underground.
The petition proposes the following:
(a) If monitoring systems show that methane levels in the mine are
at 0.5% or above then the mine will be ventilated for at least 45
minutes and the mine power will remain deenergized. If methane levels
remain above 0.5% or above, the power will continue to be deenergized
and a competent person, will enter the mine,
[[Page 47421]]
to test for methane and ventilation changes (for lowering methane
levels).
(b) The mine will be entered from the fresh air intake shaft. The
competent person will check ventilation controls on the fresh air side
to ensure there is no damage.
(c) A miner is considered competent if that person is trained on
how to use a hand-held monitor and knows how and where to test for
methane. If someone is a qualified electrician then they are competent
in addressing electrical issues underground.
(d) Before going underground, to ensure the calibration of all
instruments, a bump test will be completed on all hand-held monitors.
All competent persons will be trained on these procedures and training
will be recorded on a 5000-23 form.
(e) If there is damage to ventilation controls, a competent person
will repair them before leaving the mine through the fresh air intake.
Repairs will be made in fresh air only. The mine power will continue to
be off for an added 45 minutes while ventilation is used to lower
methane levels. If methane is still at 0.5% or above then a competent
person will enter the mine again from a fresh air intake to the active
landing using a permissible ride. Methane levels will be checked via
hand-held monitors and a monitor on a pole against the ceiling. Every
area that reads methane levels of 0.5% or above will be verified,
barricaded, and posted to restrict entry.
(f) The posted and barricaded areas affected by methane will be at
least 200 feet away from the methane entry point. Such an area will
only be opened when levels fall below 0.5%. Power to the affected areas
and the out-by exhaust air route will be disconnected, locked and
tagged out by a competent person. After that, all competent persons who
entered the mine will return to the surface. Underground power will be
reenergized outside the affected areas so that auxiliary fans can help
lower methane levels and the mining operations can resume (outside of
affected areas). Affected areas will not be opened up until they are
below 0.5%; levels will be checked beginning at the barricaded area and
working back into the affected areas once the barricade is in place.
(g) In unaffected areas of the mine, allowing workers to enter does
not create any greater hazard than using energized equipment for work
in unaffected areas when methane is below 0.5% in another area. After a
blast, all methane monitors lose battery power within 24 hours,
triggering 30 CFR 57.22603(c) if methane levels are at 0.5% for 24
hours. The petitioner states that it creates a greater hazard for
miners to go underground every 24 hours to change batteries on methane
monitors rather than allowing an entry where miners can adjust
ventilators to remove gas from the mine effectively.
(h) The petitioner asserts that the proposed alternative method
will at all times guarantee no less than the same measure of protection
afforded by the standard, 30 CFR 57.22603.
Docket Number: M-2020-002-M.
Petitioner: U.S. Silica Company, 5263 Edmund Highway, West
Columbia, South Carolina 29170.
Mine: Columbia Plant, MSHA I.D. No. 38-00138, located in Lexington
County, South Carolina.
Regulation Affected: 30 CFR 56.13020 (Use of compressed air).
Modification Request: The petitioner requests a modification of the
existing standard to permit an alternative method of an air compression
system for cleaning clothes after mining operations, which will provide
no less a degree of safety than that provided by the standard.
The petitioner states that:
(a) The alternative method provides a direct reduction of miners'
exposure to respirable dust, thus reducing their health risks. The
proposed alternative method has been jointly developed between Unimin
Corporation and the National Institute for Occupational Safety and
Health (NIOSH) and successfully tested by the NIOSH.
The petition proposes the following:
(a) Only miners trained in the operation of the clothes cleaning
booth will be permitted to use the booth to clean their clothes.
(b) Petitioner will incorporate the NIOSH Clothes Cleaning Process
and manufacturer's instruction manual into their MSHA Part 46 training
plan and train affected miners in the process.
(c) Miners entering the booth will examine valves and nozzles for
damage or malfunction and will close the door fully before opening the
air valve. Any defects will be repaired prior to the booth being used.
(d) Miners entering the booth will wear eye protection, ear plugs
or muffs for hearing protection, and respiratory protection.
Respiratory protection will consist of a full-face or half-mask
respirator that meets or exceeds the minimum requirements of a N95
filter to which the miner has been fit-tested. As an alternative, the
use of a full-face respirator will meet the requirements for eye
protection. A sign will be conspicuously posted requiring the use of
the above personal protective equipment when the booth is entered.
(e) Air flow through the booth will be at least 2,000 cubic feet
per minute to maintain negative pressure during use of the cleaning
booth in order to prevent contamination of the environment outside the
booth. Airflow will be in a downward direction, thereby moving
contaminants away from the miner's breathing zone.
(f) Air pressure through the spray manifold will be limited to 30
pounds per square inch or less. A lock box with a single, plant manager
controlled key will be used to prevent regulator tampering.
(g) The air spray manifold will consist of schedule 80 steel pipe
that has a failure pressure of 1,300 pounds per square inch and will be
capped at the base and actuated by an electrically controlled ball
valve at the top.
(h) Air nozzles will not exceed 30 pounds per square inch gauge.
(i) The upper most spray of the spray manifold will be located
below the booth user's breathing zone. Some type of mechanical device
can be used to cover the upper air nozzles to meet the specific height
of the user.
(j) Air nozzles will be guarded to eliminate the possibility of
incidental contact, which could create mechanical damage to the air
nozzles during the clothes cleaning process.
(k) Periodic maintenance checks of the booth will be conducted in
accordance with the recommendations contained in the manufacturer's
instruction manual.
(l) The air receiver tank supplying air to the manifold system will
be of sufficient volume to permit no less than 20 seconds of continuous
cleaning time.
(m) An appropriate hazard warning sign will be posted on the booth
to state at a minimum, ``Compressed Air'' and ``Respirable Dust''.
(n) A pressure relief valve designed for the booth's air reservoir
will be installed.
(o) The mine will exhaust dust-laden air from the booth into a
local exhaust ventilation system or duct outside the facility while
ensuring there is no re-entrainment back into the structure.
The petitioner asserts that the proposed alternative method will at
all times guarantee no less than the same measure of protection
afforded by the standard.
Roslyn Fontaine,
Deputy Director,Office of Standards, Regulations, and Variances.
[FR Doc. 2020-17018 Filed 8-4-20; 8:45 am]
BILLING CODE 4520-43-P