Petitions for Modification, 12796-12800 [2010-5787]
Download as PDF
wwoods2 on DSK1DXX6B1PROD with NOTICES_PART 1
12796
Federal Register / Vol. 75, No. 51 / Wednesday, March 17, 2010 / Notices
examining the trailing cables to ensure
the cables are in safe operating
condition; (c) training in hazards of
settings the instantaneous circuit
breakers too high to adequately protect
the trailing cables; and (d) training in
how to verify the circuit interrupting
device(s) protecting the trailing cable(s)
are properly set and maintained. The
petitioner asserts that the procedures of
30 CFR 48.3 for approval of proposed
revisions to already approved training
plans will apply, and the proposed
alternative method will at all times
guarantee no less than the same measure
of protection to all miners at Blue
Diamond Coal Company provided by
the existing standard.
Docket Number: M–2010–010–C.
Petitioner: Leeco Coal Company, P.O.
Box 47, Slemp, Kentucky 41763.
Mine: No. 68 Mine, MSHA I. D. No.
15–17497, located in Perry County,
Kentucky.
Regulation Affected: 30 CFR 75.503
(Permissible electric face equipment;
maintenance)
Modification Request: The petitioner
requests a modification of the existing
standard to permit an increase in the
maximum length of trailing cables
supplying power to permissible pumps.
The petitioner states that: (1) This
petition will apply only to trailing
cables supplying three-phase, 480-volt
power for permissible pumps; (2) the
maximum length of the 480-volt power
for permissible pumps will be 4,400
feet; (3) all circuit breakers used to
protect trailing cables exceeding the
pump approval length or Table 9 of Part
18 will have an instantaneous trip unit
calibrated to trip at 75% of phase to
phase short-circuit current. The trip
setting of these circuit breakers will be
sealed or locked, and will have
permanent, legible labels. Each label
will identify the circuit breaker as being
suitable for protecting the trailing
cables, and the label will be maintained
legible. In instances where 75%
instantaneous set point will not allow a
pump to start due to motor inrush, a
thermal magnetic breaker will be
furnished. The thermal rating of the
circuit breaker will be no greater than
75% of the available short-circuit
current and the instantaneous setting
will be adjusted one setting above the
motor inrush trip point. This setting
will also be sealed or locked; (4)
replacement instantaneous trip units
used to protect pump trailing cables
exceeding the length of item #4 will be
calibrated to trip at 75% of the available
phase to phase short-circuit current and
this setting will be sealed or locked; (5)
permanent warning labels will be
installed and maintained on the cover(s)
VerDate Nov<24>2008
15:08 Mar 16, 2010
Jkt 220001
of the power center to identify the
location of each sealed or locked shortcircuit protection device. These labels
will warn miners not to change or alter
these short-circuit settings; (6) all future
pump installations with excessive cable
lengths will have a short-circuit survey
conducted and items 1–6 will be
implemented. A copy of each pumps
short-circuit survey will be available at
the mine site for inspection; (7) the
petitioner’s alternative method will not
be implemented until miners who have
been designated to examine the integrity
of seals or locks, verify the short-circuit
settings, and proper procedures for
examining trailing cables for defects and
damage have received the elements of
training herein; (8) within sixty (60)
days after this petition is granted,
proposed revisions for approved 30 CFR
Part 48 training plan will be submitted
to the District Manager for the area in
which the mine is located. The training
will include the following elements: (a)
Training in mining methods and
operating procedures that will protect
the trailing cables against damage; (b)
training in the proper procedures for
examining the trailing cables to ensure
the cables are in safe operating
condition; (c) training in hazards of
settings the instantaneous circuit
breakers too high to adequately protect
the trailing cables; and (d) training in
how to verify the circuit interrupting
device(s) protecting the trailing cable(s)
are properly set and maintained. The
petitioner asserts that the procedures of
30 CFR 48.3 for approval of proposed
revisions to already approved training
plans will apply, and the proposed
alternative method will at all times
guarantee no less than the same measure
of protection to all miners at Leeco Coal
Company provided by the existing
standard.
Dated: March 12, 2010.
Patricia W. Silvey,
Director, Office of Standards, Regulations and
Variances.
[FR Doc. 2010–5785 Filed 3–16–10; 8:45 am]
BILLING CODE 4510–43–P
DEPARTMENT OF LABOR
Mine Safety and Health Administration
Petitions for Modification
AGENCY: Mine Safety and Health
Administration (MSHA), Labor.
ACTION: Notice of petitions for
modification of existing mandatory
safety standards.
SUMMARY: Section 101(c) of the Federal
Mine Safety and Health Act of 1977 and
PO 00000
Frm 00074
Fmt 4703
Sfmt 4703
30 CFR Part 44 govern the application,
processing, and disposition of petitions
for modification. This notice is a
summary of petitions for modification
filed by the parties listed below to
modify the application of existing
mandatory safety standards published
in Title 30 of the Code of Federal
Regulations.
DATES: All comments on the petitions
must be received by the Office of
Standards, Regulations and Variances
on or before April 16, 2010.
ADDRESSES: You may submit your
comments, identified by ‘‘docket
number’’ on the subject line, by any of
the following methods:
1. Electronic Mail: StandardsPetitions@dol.gov.
2. Facsimile: 1–202–693–9441.
3. Regular Mail: MSHA, Office of
Standards, Regulations and Variances,
1100 Wilson Boulevard, Room 2350,
Arlington, Virginia 22209, Attention:
Patricia W. Silvey, Director, Office of
Standards, Regulations and Variances.
4. Hand-Delivery or Courier: MSHA,
Office of Standards, Regulations and
Variances, 1100 Wilson Boulevard,
Room 2350, Arlington, Virginia 22209–
3939, Attention: Patricia W. Silvey,
Director, Office of Standards,
Regulations and Variances.
MSHA will consider only comments
postmarked by the U.S. Postal Service or
proof of delivery from another delivery
service such as UPS or Federal Express
on or before the deadline for comments.
Individuals who submit comments by
hand-delivery are required to check in
at the receptionist desk on the 21st
floor.
Individuals may inspect copies of the
petitions and comments during normal
business hours at the address listed
above.
FOR FURTHER INFORMATION CONTACT:
Barbara Barron, Office of Standards,
Regulations and Variances at 202–693–
9447 (Voice), barron.barbara@dol.gov
(E-mail), or 202–693–9441 (Telefax).
[These are not toll-free numbers.]
SUPPLEMENTARY INFORMATION:
I. Background
Section 101(c) of the Federal Mine
Safety and Health Act of 1977 (Mine
Act) allows the mine operator or
representative of miners to file a
petition to modify the application of any
mandatory safety standard to a coal or
other mine if the Secretary determines
that: (1) An alternative method of
achieving the result of such standard
exists which will at all times guarantee
no less than the same measure of
protection afforded the miners of such
mine by such standard; or (2) that the
E:\FR\FM\17MRN1.SGM
17MRN1
Federal Register / Vol. 75, No. 51 / Wednesday, March 17, 2010 / Notices
wwoods2 on DSK1DXX6B1PROD with NOTICES_PART 1
application of such standard to such
mine will result in a diminution of
safety to the miners in such mine. In
addition, the regulations at 30 CFR
44.10 and 44.11 establish the
requirements and procedures for filing
petitions for modification.
II. Petitions for Modification
Docket Number: M–2010–001–C.
Petitioner: Lone Mountain Processing,
Inc., Drawer C, St. Charles, Virginia
24282.
Mine: Huff Creek No. 1 Mine, MSHA
I. D. No. 15–17234, located in Harlan
County, Kentucky.
Regulation Affected: 30 CFR
75.364(b)(1) (Weekly examination).
Modification Request: The petitioner
requests a modification of the existing
standard to permit an alternative
method for weekly examinations on the
out by A-Mains panel due to bad roof,
rib sloughage, and floor heave. The
petitioner proposes to: (1) Establish two
evaluation points for weekly evaluation
of the affected area. The evaluation
points will be located at break 71 and
break 40 on the A-Mains panel to
monitor air quality and quantity
entering and exiting the hazardous area;
(2) Place an atmospheric monitoring
system (AMS) sensor at each evaluation
point to continuously monitor the
quality of air in the effective area as
follows: (a) An AMS meeting all of the
applicable requirements of 30 CFR
75.351(a), (b), (c), (d), (k), and (l) will be
used to continuously monitor methane,
oxygen and carbon monoxide
concentrations at the specified
monitoring stations. The AMS will be
calibrated and maintained in
accordance with 30 CFR 75.351(n), (o),
(p), and (q); (b) the AMS sensor will be
located such that the air flowing over
the sensor is representative of the air
flowing through the inaccessible belt air
entry; (c) the AMS sensors will be
capable of providing both visual and
audible signals as follows: (i) A visual
and audible alert signal will be activated
for the following initial levels: (1)
Oxygen: 19.4%; (2) Methane: 1.5%; (3)
Carbon Monoxide: 8 ppm; (ii) an
audible and visual alarm signal will be
activated for the following initial levels;
(1) Oxygen: 19.0%: (2) Methane: 2.0%;
and (3) Carbon Monoxide: 13 ppm; (d)
if an AMS sensor indicates an alert
signal, a qualified person will
immediately be dispatched to the
affected area to determine the reason for
the alarm and what action must be taken
to correct the condition. If it is
determined that a fire exists, all persons
not required for firefighting activities
will be evacuated from the mine; (e) if
an AMS sensor indicates an alarm
VerDate Nov<24>2008
15:08 Mar 16, 2010
Jkt 220001
signal, all persons in by that sensor in
the same split of air will be withdrawn
out by to the next sensor not in an alarm
mode. All persons will remain at that
location, or be withdrawn from the
mine, until the reason for the alarm has
been determined and action has been
taken to correct the condition. If it is
determined that a fire exists, all persons
not required for firefighting activities
will be evacuated from the mine; (3) A
certified person will: (a) Examine each
of the evaluation points at least every 7
days, including: (i) Examine for hazards
on the approaches to and at the
evaluation points; (ii) perform visual
examinations of the AMS sensors; and
(iii) evaluate and measure the quality
and quantity of air flowing past the
evaluation points. Air quality
measurements will determine the
methane, oxygen, and carbon monoxide
concentrations using a MSHA approved
hand-held device. Air quantity
measurements will be made using an
appropriately calibrated anemometer.
Methane gas or other harmful, noxious,
or poisonous gases will not be permitted
to accumulate in excess of legal limits
for an intake aircourse. At these
evaluations points, an increase of 0.3
percent methane above the previous
reading or a 10 percent change in the
airflow quantity from the previous
reading will cause an immediate
investigation of the affected area, with
prompt remedial action being taken as
needed; and (iv) at each evaluation
point, a date board will be provided
where the certified examiner will record
the date, time, his or her initials, and
the measured quantity and quality of the
air entering the affected area; and (v)
record the results of each weekly
examination in a book maintained on
the surface. The certification,
recordkeeping, and retention period
requirements of 30 CFR 75.364(g), (h),
and (i) will be met, (4) The permanent
ventilation controls, evaluation points,
and AMS sensor locations will be
shown on the annual mine ventilation
map submitted in accordance with 30
CFR 75.372; (5) All evaluation points
and approaches to evaluation points
will be maintained in a safe condition
at all times. The roof will be adequately
supported by suitable means to prevent
deterioration of the roof in the vicinity
of the evaluation points. The petitioner
asserts that the proposed alternative
method will at all times guarantee no
less than the same measure of protection
afforded by the appropriate portion of
30 CFR 75.364.
Docket Number: M–2010–002–C.
PO 00000
Frm 00075
Fmt 4703
Sfmt 4703
12797
Petitioner: Bridger Coal Company,
P.O. Box 68, Point of Rocks, Wyoming
82942.
Mine: Bridger Underground Mine,
MSHA I.D. No. 48–01646, located in
Sweetwater County, Wyoming.
Regulation Affected: 30 CFR 75.1700
(Oil and gas wells).
Modification Request: The petitioner
requests a modification of the existing
standard to allow mining through
abandoned oil and gas wells. The
petitioner states that: (1) Bridger Coal
Company expects to plug and mine
through wells intersecting three coal
seams: (a) Deadman D41 (the lowermost
mineable seam, currently being mined),
Deadman D5 Seam (not being mined),
and Deadman D6 Seam (not being
mined); (b) Bridger Coal Company is
currently mining the Deadman D41
Seam. This seam varies from 7 to 17-feet
in thickness, and liberates little to no
methane in seam; (c) the Deadman D5
seam is approximately 70-feet above the
active mine workings. This seam is
approximately 5-feet thick. Bridger Coal
Company has no current plans to mine
this seam; (d) the Deadman D6 Seam is
approximately 170-feet above the active
mine workings. This seam is
approximately 2.5-feet thick. Bridger
Coal Company has no current plans to
mine this seam; (2) there are two
abandoned gas wells, #41–35 (P & A
July 28, 1964) and Pierce #1 (P & A
December 23, 1960). The drilled depth
of #41–35 is 2793 feet; that of Pierce #1
is 3276 feet. Both of these wells were
already professionally plugged and
abandoned. Copies of geologic logs have
been secured for each well and have
been interpreted to identify coal bed
horizons; and (3) the interval of all three
seams is approximately 210 feet so the
total expansive cement interval would
be 510 feet to meet the minimum
proposed plugging requirements set
forth below. Plugging to the surface is
planned for each abandoned and
plugged gas well. The two abandoned
and plugged gas wells will be cut
through by longwall shear. Mine
development occurs near the three
hundred (300) foot diameter barrier of
#41–35 in December 2010. As an
alternative method of achieving the
results of 30 CFR 75.1700, the petitioner
proposes the following: (1) Bridger Coal
Company will provide the District
Manager with a map showing the
location of all known oil and gas wells
within the lease boundaries of the mine;
(2) At least 30 days prior to mining
within 150 feet of any oil or gas well,
written certification will be provided to
the District Manager that such well was
cleaned out, prepared, and plugged
using methods that meet or exceed the
E:\FR\FM\17MRN1.SGM
17MRN1
wwoods2 on DSK1DXX6B1PROD with NOTICES_PART 1
12798
Federal Register / Vol. 75, No. 51 / Wednesday, March 17, 2010 / Notices
following techniques and procedures:
(a) A diligent effort will be made to
clean the boreholes to a depth which
would permit the placement of
expanding cement to at least 200 feet
below the base of the lowest mineable
coal seam; (b) If the cleaned out
borehole produces an excessive amount
of methane gas, a mechanical bridge
plug will be set in the borehole in a
stratum of at least 200 feet below the
base of the lowest mineable coal seam.
If it is not feasible to set a mechanical
bridge plug, an appropriately sized
substantial brush plug may be used; and
(c) A suite of logs will be made and
maintained consisting of caliper survey,
directional deviation survey, and log(s)
suitable for determining the top and
bottom of the mineable coal seams.
Invoices, work orders, and other records
relating to all work on the well will also
be maintained. This information will be
provided to MSHA upon request.
The following procedures will be
followed when plugging oil and gas
wells to the surface: (1) Using open-end
tubing, a gel will be pumped into the
borehole to a point approximately 20
feet above the bottom of the cleaned-out
area of the borehole, or 20 feet above the
mechanical bridge plug or substantial
brush plug. The gel should circulate
around the borehole, completely filling
the cavity, so that the gel inhibits any
flow of gas, supports the walls of the
borehole, and densifies the expanding
cement that will be pumped into the
borehole; (2) using open-ended tubing, a
cement plug will be set in the well by
pumping expanding cement slurry to a
point at least 200 feet below the lowest
mineable coal seam up to a point
approximately 100 feet above the top of
the lowest mineable coal seam. There
will be at least 200 feet of expanding
cement below the base of the lowest
mineable coal bed; (3) the remainder of
the borehole will be filled to the surface,
either with expanding cement slurry, or
beginning from the point approximately
100 feet above the top of the lowest
mineable coal seam, with Portland
cement or a Portland cement-fly ash
mixture; (4) a small quantity of steel
turnings, or other magnetic particles
will be imbedded in the top of the
cement near the surface to serve as a
permanent magnetic monument of the
borehole. The following procedures will
apply to mining through an oil or gas
well: (1) The operator will notify the
District Manager or designee prior to
mining within 150 feet of the well, and
when a specific plan is developed for
mining through each well; (2) The
petitioner will participate in a
conference with the District Manager
VerDate Nov<24>2008
15:08 Mar 16, 2010
Jkt 220001
prior to mining-through the plugged
well to review the specific procedures
for mining through the well.
Representatives of miners, miners on
the section, and the appropriate State
agency will be informed within a
reasonable time prior to the conference,
and all persons who will be present
during the mining through will attend
and participate. The conference may be
called by the operator and may be
conducted by teleconference; (3) Mining
through a plugged well will be done on
a shift approved by the District Manager
or designee; (4) The District Manager or
designee, representatives of the miners,
the miners on the section, and the
appropriate State agency will be notified
by the operator in sufficient time prior
to the mining through operation in order
to have an opportunity to have
representatives present; (5) When using
continuous mining or conventional
mining methods, drivage sights not
more than 50 feet from the well, will be
installed at the last open crosscut near
the place to be mined to assure
intersection of the well. When using
longwall mining methods, drivage sights
will be installed on 10-foot centers for
a distance of 50 feet in advance of the
well bore. The drivage sights will be
installed in the headgate and tailgate; (6)
Firefighting equipment, including fire
extinguishers, rock dust, and sufficient
fire hose to reach the working face will
be available. The fire hose will be
located near the working face. The fire
hose will be extended to the face area
of the mine-through when the longwall
mining method is implemented. All fire
hoses will be ready for operation during
the mine-through; (7) Sufficient
supplies of roof support and ventilation
materials will be available and located
not more than two crosscuts outby the
mining-through location on intake air;
(8) During the mine-through operation,
the quantity of air required by the
ventilation plan, but not less than
10,800 cfm, will reach each working
face where coal is being cut, mined or
loaded by continuous mining or
conventional mining methods being
employed during a mining through of a
plugged well. The quantity of air
required by the ventilation plan, but not
less than 65,000 cfm, will reach the
working face of the longwall during the
mine-through operation; (9) Equipment
will be checked for permissibility and
serviced on the maintenance shift prior
to mining through the well and the
waterline maintained up to the tail
piece with a sufficient amount of fire
hose to reach the farthest point of
penetration on the section; (10) The
methane monitor(s) on the continuous
PO 00000
Frm 00076
Fmt 4703
Sfmt 4703
mining machine, cutting machine and
loading machine or longwall will be
calibrated on the maintenance shift
prior to mining through the well; (11)
When mining is in progress, tests for
methane will be made with a hand-held
methane detector at least every 10
minutes from the time mining is within
30 feet of the well until the well is
intersected and immediately prior to
mining through. During the actual
cutting through process, no individual
will be allowed on the return side until
mining through has been completed and
the area has been examined and
declared safe; (12) When using
continuous or conventional mining
methods, the working place will be free
of accumulations of coal dust and coal
spillages, and rock dusting will be
conducted and placed on the roof, rib
and floor to within 20 feet of the face
when mining through the well. On
longwall sections, rock dusting will be
conducted and placed on the roof, rib
and floor up to both the headgate and
tailgate gob; (13) When the well bore is
intersected, all equipment will be deenergized and the place thoroughly
examined and determined safe before
mining is resumed. Any well casing will
be removed and no open flame will be
permitted in the area until adequate
ventilation has been established around
the well bore; (14) After a well has been
intersected and the working place
determined safe, mining will continue
inby the well a sufficient distance to
permit adequate ventilation around the
area of the well bore; (15) No person
will be permitted in the area of the well
mining-through operation except those
actually engaged in the operation,
company personnel, representatives of
the miners, personnel from MSHA, and
personnel from the appropriate State
agency; (16) The mining-through
operation will be under the direct
supervision of a certified individual;
(17) Instructions concerning the miningthrough operation will be issued only by
the certified individual in charge; and
(18) MSHA personnel may interrupt or
halt the mining-through operation when
it is necessary for the safety of miners.
The petitioner states that: (1) A copy of
the Proposed Decision and Order will be
maintained at the mine office and be
available to the Secretary’s
representatives, miners’ representatives,
and miners; and (2) within 60 days after
the Proposed Decision and Order
becomes final, the petitioner will submit
proposed revisions to the approved Part
48 training plans to the District
Manager. These proposed revisions will
include initial and refresher training
regarding compliance with the terms
E:\FR\FM\17MRN1.SGM
17MRN1
wwoods2 on DSK1DXX6B1PROD with NOTICES_PART 1
Federal Register / Vol. 75, No. 51 / Wednesday, March 17, 2010 / Notices
and conditions stated in the Proposed
Decision and Order. The petitioner
asserts that the proposed alternative
method of achieving the results of the
standard proposed by Bridger Coal
Company will at all times guarantee no
less than the same measure of protection
afforded the miner under the existing
standard.
Docket Number: M–2010–003–C.
Petitioner: Brooks Run Mining
Company, LLC, 208 Business Street,
Beckley, West Virginia 25801.
Mine: Wyoming No. 2 Mine, MSHA I.
D. No. 46–06263, located in Wyoming
County, West Virginia.
Regulation Affected: 30 CFR 75.1101–
1(b) (Deluge-type water systems).
Modification Request: The petitioner
requests a modification of the existing
standard to permit nozzles to be used
without blow-off dust covers for its
deluge-type water spray system. The
petitioner proposes to continue its
weekly inspection and functional
testing of the complete deluge-type
water spray system, and remove blowoff dust covers from the nozzles. The
petitioner states that: (1) Currently each
nozzle is provided with a blow-off dust
cover. In view of the frequent
inspections and functional testing of the
system, the dust covers are not
necessary because the nozzles can be
maintained in an unclogged condition
through weekly use; and (2) it is
burdensome to recap the large number
of covers weekly after each inspection
and functional test. The petitioner
asserts that the proposed alternative
method will at all times guarantee no
less than the same measure of protection
afforded the miners employed by said
standard.
Docket Number: M–2010–004–C.
Petitioner: Jim Walter Resources, P.O.
Box 133, Brookwood, Alabama 35444.
Mine: No. 7 Mine, MSHA I. D. No. 01–
01401, located in Tuscaloosa County,
Alabama.
Regulation Affected: 30 CFR 75.507
(Power connection points).
Modification Request: The petitioner
requests a modification of the existing
standard to permit the use of one or
more three-phase, 2,400-volt or 4,160volt alternating current submersible
pumps installed in return and bleeder
entries in the No. 7 Mine. The petitioner
states that: (1) The three-phase, 2, 400volt or 4,160-volt, alternating current
electric power circuit for each pump
will be designed and installed to: (a)
Contain either a direct or derived
neutral, which will be grounded
through a suitable resistor at the source
transformer or power center. A
grounding circuit originating at the
VerDate Nov<24>2008
15:08 Mar 16, 2010
Jkt 220001
grounded side of the grounding resistor
must extend along with the power
conductors and serve as the grounding
conductor for the frame of each pump
and all associated electric equipment
that may be supplied power from each
such circuit. The borehole casing will be
bonded to the system grounding
medium; and (b) contain a grounding
resistor that limits the ground-fault
current to not more than 6.5 amperes.
The grounding resistor must be rated for
the maximum fault current available
and must be insulated from ground for
a voltage equal to the phase-to-phase
voltage of the system. (2) The following
protections for each pump power circuit
will be provided by a suitable circuit
interrupting device of adequate
interrupting capacity with devices to
provide protection against undervoltage,
grounded phase, short-circuit, and
overload: (a) The undervoltage
protection device will operate on a loss
of voltage to prevent automatic
restarting of the equipment; (b) the
grounded phase protection device will
be set not to exceed fifty percent (50%)
of the current rating of the neutral
grounding resistor; (c) the short circuit
protection device will not be set to
exceed the required short circuit
protection for the power cable or
seventy-five percent (75%) of the
minimum available phase-to-phase
short circuit current, whichever is less;
(d) each power circuit will contain a
disconnecting device located on the
surface and installed to provide visual
evidence that the power is
disconnected; (e) each disconnecting
device will include a means to visually
determine the relevant pump power
circuit is disconnected and be provided
with a means to lock, tag-out, and
ground the system; (f) each
disconnecting device shall be designed
to prevent entry unless the disconnect
handle is in the ‘‘off’’ position and the
circuit is grounded; and (g) each
disconnecting device will be clearly
identified and provided with a warning
sign stating, ‘‘Danger do not enter unless
the circuit is opened, locked, tagged-out,
and grounded’’. (3) Each three-phase,
alternating current system will be
provided with a low resistance
grounding medium for the grounding of
the lightning/surge arrestors for the
high-voltage pump power circuit that is
separated from the neutral grounding
medium by a distance of not less than
twenty-five (25) feet. (4) The electric
control circuit(s) for each pump will
meet the following requirements: (a)
The control circuit will be equipped
with a circuit that determines a high
and low water level; (b) when the water
PO 00000
Frm 00077
Fmt 4703
Sfmt 4703
12799
level is reached, the pump will cease
operation and will not start in either the
manual or automatic mode; (c) when the
high water level is reached, the pump
will be capable of operation; (d) the high
and low water levels will be determined
by a differential pressure switch located
at the surface; (e) the grounded-phase
protective circuit for each pump will be
able to be tested by injecting a test
current through the grounded-phase
current transformer; and (f) a remote
control and monitoring system can be
used with a pump system for condition
monitoring and for remote startup and
shutdown control of the pump. The
remote control and monitoring system
will not allow remote reset of the pump
power system when any fault condition
(e.g., grounded phase, short circuit, or
overload) exists on the system. (5) Each
surface pump control and power circuit
will be examined as required by 30 CFR
77.502. (6) The power cable to each
submersible pump motor must be
suitable for this application, have a
current carrying capacity not less than
one-hundred twenty-five percent
(125%) of the full load motor current of
the submersible pump motor, and have
an outer jacket suitable for a wet
location. The power cable must be
supported at the entrance to the
borehole and throughout its length by
securing it with clamps, spaced
approximately twenty-five feet (25’)
apart, affixed to the discharge pipe
casing. (7) A device will be installed to
monitor ground continuity from the
starter box to the well head. (8) The
starter will be equipped with ground
fault ‘‘look-ahead’’ device to prevent the
motor from being energized during a
fault condition. (9) Each pump
installation must comply with all other
applicable requirement of 30 CFR. (10)
Within sixty (60) days after this petition
is granted, petitioner will submit
proposed revisions for their approved
Part 48 training plan to the District 11
Manager. These provisions will specify
task training for all qualified mine
electricians who perform electric work,
monthly examinations as required by 30
CFR 77.502, and refresher training
regarding the alternative method
outlined in the petition. The procedures
of 30 CFR 48.3 for approval of proposed
revisions to already approved training
plans will apply. The petitioner asserts
that the alternate method of achieving
the result of the existing standard will
at all times guarantee no less than the
same measure of protection afforded the
miners by the present application of the
standard.
E:\FR\FM\17MRN1.SGM
17MRN1
12800
Federal Register / Vol. 75, No. 51 / Wednesday, March 17, 2010 / Notices
Dated: March 12, 2010.
Patricia W. Silvey,
Director, Office of Standards, Regulations and
Variances.
[FR Doc. 2010–5787 Filed 3–16–10; 8:45 am]
BILLING CODE 4510–43–P
DEPARTMENT OF LABOR
Mine Safety and Health Administration
Petitions for Modification
AGENCY: Mine Safety and Health
Administration, Labor.
ACTION: Notice of petitions for
modification of existing mandatory
safety standards.
wwoods2 on DSK1DXX6B1PROD with NOTICES_PART 1
SUMMARY: Section 101(c) of the Federal
Mine Safety and Health Act of 1977 and
30 CFR Part 44 govern the application,
processing, and disposition of petitions
for modification. This notice is a
summary of petitions for modification
filed by the parties listed below to
modify the application of existing
mandatory safety standards published
in Title 30 of the Code of Federal
Regulations.
DATES: All comments on the petitions
must be received by the Office of
Standards, Regulations and Variances
on or before April 16, 2010.
ADDRESSES: You may submit your
comments, identified by ‘‘docket
number’’ on the subject line, by any of
the following methods:
1. Electronic Mail: StandardsPetitions@dol.gov.
2. Facsimile: 1–202–693–9441.
3. Regular Mail: MSHA, Office of
Standards, Regulations and Variances,
1100 Wilson Boulevard, Room 2350,
Arlington, Virginia 22209, Attention:
Patricia W. Silvey, Director, Office of
Standards, Regulations and Variances.
4. Hand-Delivery or Courier: MSHA,
Office of Standards, Regulations and
Variances, 1100 Wilson Boulevard,
Room 2350, Arlington, Virginia 22209,
Attention: Patricia W. Silvey, Director,
Office of Standards, Regulations and
Variances.
MSHA will consider only comments
postmarked by the U.S. Postal Service or
proof of delivery from another delivery
service such as UPS or Federal Express
on or before the deadline for comments.
Individuals who submit comments by
hand-delivery are required to check in
at the receptionist desk on the 21st
floor.
Individuals may inspect copies of the
petitions and comments during normal
business hours at the address listed
above.
VerDate Nov<24>2008
15:08 Mar 16, 2010
Jkt 220001
FOR FURTHER INFORMATION CONTACT:
Barbara Barron, Office of Standards,
Regulations and Variances at 202–693–
9447 (Voice), barron.barbara@dol.gov
(E-mail), or 202–693–9441 (Telefax).
[These are not toll-free numbers.]
SUPPLEMENTARY INFORMATION:
I. Background
Section 101(c) of the Federal Mine
Safety and Health Act of 1977 (Mine
Act) allows the mine operator or
representative of miners to file a
petition to modify the application of any
mandatory safety standard to a coal or
other mine if the Secretary determines
that: (1) An alternative method of
achieving the result of such standard
exists which will at all times guarantee
no less than the same measure of
protection afforded the miners of such
mine by such standard; or (2) that the
application of such standard to such
mine will result in a diminution of
safety to the miners in such mine. In
addition, the regulations at 30 CFR
44.10 and 44.11 establish the
requirements and procedures for filing
petitions for modification.
II. Petitions for Modification
Docket Number: M–2009–064–C.
Petitioner: Omega Mining, Inc., P.O.
Box 929, Honaker, Virginia 24260.
Mine: Beehive Mine, MSHA I.D. No.
44–05411 and Hatfield Mine, MSHA I.D.
No. 44–07104, located in Russell
County, Virginia.
Regulation Affected: 30 CFR
75.1506(c)(1) (Refuge alternatives).
Modification Request: The petitioner
requests a modification of the existing
standard to permit an alternative
method to maintain a refuge alternative
to within 1,000 feet of the working face
but be allowed to develop a maximum
200 feet inby the 1,000 foot location
prior to the installation of the refuge
alternative to its Beehive and Hatfield
Mines. This will allow the refuge
alternative to be installed adjacent to the
loading point of the active section while
not interfering with ventilation or
haulage. The petitioner states that: (1)
Both the aforementioned underground
mining operations have an approved
Emergency Response Plan with MSHA
through District 5; (2) the mining height
at both operations averages 42 to 48
inches in overall height; (3) each mine
utilizes refuge alternatives (safe havens)
constructed of 15 psi block stoppings
provided with 15 psi rated metal doors
to access the internal area of the refuge
alternative; (4) breathable air is supplied
by a surface mounted portable fan to
each established refuge alternative
through pre-drilled vertical boreholes;
(5) the breathable air system is a forced
PO 00000
Frm 00078
Fmt 4703
Sfmt 4703
air system designed to maintain positive
pressure within the refuge alternative at
all times; (6) this system is designed to
sustain personnel for an indefinite
period of time, easily exceeding 96
hours; (7) the borehole design allows for
introduction of additional
communications, water, food, and
correspondence between the surface and
underground through letters or other
means; (8) the depth of the vertical
boreholes should not exceed 300 to 400
feet; (9) strategic surface locations are
necessary for providing adequate
placement of the boreholes in relation to
active underground workings.
Flexibility for positioning surface to
mine location is very important; (10)
constructed refuge alternatives are
located in a crosscut entry between the
primary and secondary escapeways; (11)
each person on the working section is
provided with an approved 1 hour SCSR
(self-contained self-rescuer) and an
approved 10 minute SCSR. An
additional approved 1 hour SCSR is
provided in the refuge alternative; (12)
the modification to the timing of the
installation for the working section
refuge alternative will not interfere or
affect the service and maintenance of
the outby refuge alternatives; (13) both
of these mines have been in operation
for over 5 years and has no record of
methane liberation at any time; and (14)
all other requirements of the Emergency
Response Plan and the Mine Emergency
Evacuation and Firefighting Program of
Instruction will be complied with. The
petitioner asserts that the alternative
method will at all times provide the
same measure of protection for the
miners as the existing standard while
eliminating the need for portable type
refuge alternatives, and will also allow
for safe and sound development of the
working face in a limited amount of
time and distance where ventilation and
haulage will not be interfered upon.
Docket Number: M–2009–065–C.
Petitioner: Blue Diamond Coal
Company, P.O. Box 47, Slemp,
Kentucky 41763.
Mine: No. 75 Mine, MSHA I. D. No.
15–17478, located in Perry County,
Kentucky.
Regulation Affected: 30 CFR 75.513
(Electric conductor; capacity and
insulation).
Modification Request: The petitioner
requests a modification of the existing
standard to permit use of smaller cables
than allowed by the National Electric
Code for 480 Volt AC 250 H.P. and 300
H.P. head drive motors. The petitioner
states that: (1) In lieu of a 350 MCM
cable for a 300 H.P. Head Drive motor
and a 250 MCM cable for a 250 H.P.
E:\FR\FM\17MRN1.SGM
17MRN1
Agencies
[Federal Register Volume 75, Number 51 (Wednesday, March 17, 2010)]
[Notices]
[Pages 12796-12800]
From the Federal Register Online via the Government Printing Office [www.gpo.gov]
[FR Doc No: 2010-5787]
-----------------------------------------------------------------------
DEPARTMENT OF LABOR
Mine Safety and Health Administration
Petitions for Modification
AGENCY: Mine Safety and Health Administration (MSHA), Labor.
ACTION: Notice of petitions for modification of existing mandatory
safety standards.
-----------------------------------------------------------------------
SUMMARY: Section 101(c) of the Federal Mine Safety and Health Act of
1977 and 30 CFR Part 44 govern the application, processing, and
disposition of petitions for modification. This notice is a summary of
petitions for modification filed by the parties listed below to modify
the application of existing mandatory safety standards published in
Title 30 of the Code of Federal Regulations.
DATES: All comments on the petitions must be received by the Office of
Standards, Regulations and Variances on or before April 16, 2010.
ADDRESSES: You may submit your comments, identified by ``docket
number'' on the subject line, by any of the following methods:
1. Electronic Mail: Standards-Petitions@dol.gov.
2. Facsimile: 1-202-693-9441.
3. Regular Mail: MSHA, Office of Standards, Regulations and
Variances, 1100 Wilson Boulevard, Room 2350, Arlington, Virginia 22209,
Attention: Patricia W. Silvey, Director, Office of Standards,
Regulations and Variances.
4. Hand-Delivery or Courier: MSHA, Office of Standards, Regulations
and Variances, 1100 Wilson Boulevard, Room 2350, Arlington, Virginia
22209-3939, Attention: Patricia W. Silvey, Director, Office of
Standards, Regulations and Variances.
MSHA will consider only comments postmarked by the U.S. Postal
Service or proof of delivery from another delivery service such as UPS
or Federal Express on or before the deadline for comments. Individuals
who submit comments by hand-delivery are required to check in at the
receptionist desk on the 21st floor.
Individuals may inspect copies of the petitions and comments during
normal business hours at the address listed above.
FOR FURTHER INFORMATION CONTACT: Barbara Barron, Office of Standards,
Regulations and Variances at 202-693-9447 (Voice),
barron.barbara@dol.gov (E-mail), or 202-693-9441 (Telefax). [These are
not toll-free numbers.]
SUPPLEMENTARY INFORMATION:
I. Background
Section 101(c) of the Federal Mine Safety and Health Act of 1977
(Mine Act) allows the mine operator or representative of miners to file
a petition to modify the application of any mandatory safety standard
to a coal or other mine if the Secretary determines that: (1) An
alternative method of achieving the result of such standard exists
which will at all times guarantee no less than the same measure of
protection afforded the miners of such mine by such standard; or (2)
that the
[[Page 12797]]
application of such standard to such mine will result in a diminution
of safety to the miners in such mine. In addition, the regulations at
30 CFR 44.10 and 44.11 establish the requirements and procedures for
filing petitions for modification.
II. Petitions for Modification
Docket Number: M-2010-001-C.
Petitioner: Lone Mountain Processing, Inc., Drawer C, St. Charles,
Virginia 24282.
Mine: Huff Creek No. 1 Mine, MSHA I. D. No. 15-17234, located in
Harlan County, Kentucky.
Regulation Affected: 30 CFR 75.364(b)(1) (Weekly examination).
Modification Request: The petitioner requests a modification of the
existing standard to permit an alternative method for weekly
examinations on the out by A-Mains panel due to bad roof, rib
sloughage, and floor heave. The petitioner proposes to: (1) Establish
two evaluation points for weekly evaluation of the affected area. The
evaluation points will be located at break 71 and break 40 on the A-
Mains panel to monitor air quality and quantity entering and exiting
the hazardous area; (2) Place an atmospheric monitoring system (AMS)
sensor at each evaluation point to continuously monitor the quality of
air in the effective area as follows: (a) An AMS meeting all of the
applicable requirements of 30 CFR 75.351(a), (b), (c), (d), (k), and
(l) will be used to continuously monitor methane, oxygen and carbon
monoxide concentrations at the specified monitoring stations. The AMS
will be calibrated and maintained in accordance with 30 CFR 75.351(n),
(o), (p), and (q); (b) the AMS sensor will be located such that the air
flowing over the sensor is representative of the air flowing through
the inaccessible belt air entry; (c) the AMS sensors will be capable of
providing both visual and audible signals as follows: (i) A visual and
audible alert signal will be activated for the following initial
levels: (1) Oxygen: 19.4%; (2) Methane: 1.5%; (3) Carbon Monoxide: 8
ppm; (ii) an audible and visual alarm signal will be activated for the
following initial levels; (1) Oxygen: 19.0%: (2) Methane: 2.0%; and (3)
Carbon Monoxide: 13 ppm; (d) if an AMS sensor indicates an alert
signal, a qualified person will immediately be dispatched to the
affected area to determine the reason for the alarm and what action
must be taken to correct the condition. If it is determined that a fire
exists, all persons not required for firefighting activities will be
evacuated from the mine; (e) if an AMS sensor indicates an alarm
signal, all persons in by that sensor in the same split of air will be
withdrawn out by to the next sensor not in an alarm mode. All persons
will remain at that location, or be withdrawn from the mine, until the
reason for the alarm has been determined and action has been taken to
correct the condition. If it is determined that a fire exists, all
persons not required for firefighting activities will be evacuated from
the mine; (3) A certified person will: (a) Examine each of the
evaluation points at least every 7 days, including: (i) Examine for
hazards on the approaches to and at the evaluation points; (ii) perform
visual examinations of the AMS sensors; and (iii) evaluate and measure
the quality and quantity of air flowing past the evaluation points. Air
quality measurements will determine the methane, oxygen, and carbon
monoxide concentrations using a MSHA approved hand-held device. Air
quantity measurements will be made using an appropriately calibrated
anemometer. Methane gas or other harmful, noxious, or poisonous gases
will not be permitted to accumulate in excess of legal limits for an
intake aircourse. At these evaluations points, an increase of 0.3
percent methane above the previous reading or a 10 percent change in
the airflow quantity from the previous reading will cause an immediate
investigation of the affected area, with prompt remedial action being
taken as needed; and (iv) at each evaluation point, a date board will
be provided where the certified examiner will record the date, time,
his or her initials, and the measured quantity and quality of the air
entering the affected area; and (v) record the results of each weekly
examination in a book maintained on the surface. The certification,
recordkeeping, and retention period requirements of 30 CFR 75.364(g),
(h), and (i) will be met, (4) The permanent ventilation controls,
evaluation points, and AMS sensor locations will be shown on the annual
mine ventilation map submitted in accordance with 30 CFR 75.372; (5)
All evaluation points and approaches to evaluation points will be
maintained in a safe condition at all times. The roof will be
adequately supported by suitable means to prevent deterioration of the
roof in the vicinity of the evaluation points. The petitioner asserts
that the proposed alternative method will at all times guarantee no
less than the same measure of protection afforded by the appropriate
portion of 30 CFR 75.364.
Docket Number: M-2010-002-C.
Petitioner: Bridger Coal Company, P.O. Box 68, Point of Rocks,
Wyoming 82942.
Mine: Bridger Underground Mine, MSHA I.D. No. 48-01646, located in
Sweetwater County, Wyoming.
Regulation Affected: 30 CFR 75.1700 (Oil and gas wells).
Modification Request: The petitioner requests a modification of the
existing standard to allow mining through abandoned oil and gas wells.
The petitioner states that: (1) Bridger Coal Company expects to plug
and mine through wells intersecting three coal seams: (a) Deadman D41
(the lowermost mineable seam, currently being mined), Deadman D5 Seam
(not being mined), and Deadman D6 Seam (not being mined); (b) Bridger
Coal Company is currently mining the Deadman D41 Seam. This seam varies
from 7 to 17-feet in thickness, and liberates little to no methane in
seam; (c) the Deadman D5 seam is approximately 70-feet above the active
mine workings. This seam is approximately 5-feet thick. Bridger Coal
Company has no current plans to mine this seam; (d) the Deadman D6 Seam
is approximately 170-feet above the active mine workings. This seam is
approximately 2.5-feet thick. Bridger Coal Company has no current plans
to mine this seam; (2) there are two abandoned gas wells, 41-
35 (P & A July 28, 1964) and Pierce 1 (P & A December 23,
1960). The drilled depth of 41-35 is 2793 feet; that of Pierce
1 is 3276 feet. Both of these wells were already
professionally plugged and abandoned. Copies of geologic logs have been
secured for each well and have been interpreted to identify coal bed
horizons; and (3) the interval of all three seams is approximately 210
feet so the total expansive cement interval would be 510 feet to meet
the minimum proposed plugging requirements set forth below. Plugging to
the surface is planned for each abandoned and plugged gas well. The two
abandoned and plugged gas wells will be cut through by longwall shear.
Mine development occurs near the three hundred (300) foot diameter
barrier of 41-35 in December 2010. As an alternative method of
achieving the results of 30 CFR 75.1700, the petitioner proposes the
following: (1) Bridger Coal Company will provide the District Manager
with a map showing the location of all known oil and gas wells within
the lease boundaries of the mine; (2) At least 30 days prior to mining
within 150 feet of any oil or gas well, written certification will be
provided to the District Manager that such well was cleaned out,
prepared, and plugged using methods that meet or exceed the
[[Page 12798]]
following techniques and procedures: (a) A diligent effort will be made
to clean the boreholes to a depth which would permit the placement of
expanding cement to at least 200 feet below the base of the lowest
mineable coal seam; (b) If the cleaned out borehole produces an
excessive amount of methane gas, a mechanical bridge plug will be set
in the borehole in a stratum of at least 200 feet below the base of the
lowest mineable coal seam. If it is not feasible to set a mechanical
bridge plug, an appropriately sized substantial brush plug may be used;
and (c) A suite of logs will be made and maintained consisting of
caliper survey, directional deviation survey, and log(s) suitable for
determining the top and bottom of the mineable coal seams. Invoices,
work orders, and other records relating to all work on the well will
also be maintained. This information will be provided to MSHA upon
request.
The following procedures will be followed when plugging oil and gas
wells to the surface: (1) Using open-end tubing, a gel will be pumped
into the borehole to a point approximately 20 feet above the bottom of
the cleaned-out area of the borehole, or 20 feet above the mechanical
bridge plug or substantial brush plug. The gel should circulate around
the borehole, completely filling the cavity, so that the gel inhibits
any flow of gas, supports the walls of the borehole, and densifies the
expanding cement that will be pumped into the borehole; (2) using open-
ended tubing, a cement plug will be set in the well by pumping
expanding cement slurry to a point at least 200 feet below the lowest
mineable coal seam up to a point approximately 100 feet above the top
of the lowest mineable coal seam. There will be at least 200 feet of
expanding cement below the base of the lowest mineable coal bed; (3)
the remainder of the borehole will be filled to the surface, either
with expanding cement slurry, or beginning from the point approximately
100 feet above the top of the lowest mineable coal seam, with Portland
cement or a Portland cement-fly ash mixture; (4) a small quantity of
steel turnings, or other magnetic particles will be imbedded in the top
of the cement near the surface to serve as a permanent magnetic
monument of the borehole. The following procedures will apply to mining
through an oil or gas well: (1) The operator will notify the District
Manager or designee prior to mining within 150 feet of the well, and
when a specific plan is developed for mining through each well; (2) The
petitioner will participate in a conference with the District Manager
prior to mining-through the plugged well to review the specific
procedures for mining through the well. Representatives of miners,
miners on the section, and the appropriate State agency will be
informed within a reasonable time prior to the conference, and all
persons who will be present during the mining through will attend and
participate. The conference may be called by the operator and may be
conducted by teleconference; (3) Mining through a plugged well will be
done on a shift approved by the District Manager or designee; (4) The
District Manager or designee, representatives of the miners, the miners
on the section, and the appropriate State agency will be notified by
the operator in sufficient time prior to the mining through operation
in order to have an opportunity to have representatives present; (5)
When using continuous mining or conventional mining methods, drivage
sights not more than 50 feet from the well, will be installed at the
last open crosscut near the place to be mined to assure intersection of
the well. When using longwall mining methods, drivage sights will be
installed on 10-foot centers for a distance of 50 feet in advance of
the well bore. The drivage sights will be installed in the headgate and
tailgate; (6) Firefighting equipment, including fire extinguishers,
rock dust, and sufficient fire hose to reach the working face will be
available. The fire hose will be located near the working face. The
fire hose will be extended to the face area of the mine-through when
the longwall mining method is implemented. All fire hoses will be ready
for operation during the mine-through; (7) Sufficient supplies of roof
support and ventilation materials will be available and located not
more than two crosscuts outby the mining-through location on intake
air; (8) During the mine-through operation, the quantity of air
required by the ventilation plan, but not less than 10,800 cfm, will
reach each working face where coal is being cut, mined or loaded by
continuous mining or conventional mining methods being employed during
a mining through of a plugged well. The quantity of air required by the
ventilation plan, but not less than 65,000 cfm, will reach the working
face of the longwall during the mine-through operation; (9) Equipment
will be checked for permissibility and serviced on the maintenance
shift prior to mining through the well and the waterline maintained up
to the tail piece with a sufficient amount of fire hose to reach the
farthest point of penetration on the section; (10) The methane
monitor(s) on the continuous mining machine, cutting machine and
loading machine or longwall will be calibrated on the maintenance shift
prior to mining through the well; (11) When mining is in progress,
tests for methane will be made with a hand-held methane detector at
least every 10 minutes from the time mining is within 30 feet of the
well until the well is intersected and immediately prior to mining
through. During the actual cutting through process, no individual will
be allowed on the return side until mining through has been completed
and the area has been examined and declared safe; (12) When using
continuous or conventional mining methods, the working place will be
free of accumulations of coal dust and coal spillages, and rock dusting
will be conducted and placed on the roof, rib and floor to within 20
feet of the face when mining through the well. On longwall sections,
rock dusting will be conducted and placed on the roof, rib and floor up
to both the headgate and tailgate gob; (13) When the well bore is
intersected, all equipment will be de-energized and the place
thoroughly examined and determined safe before mining is resumed. Any
well casing will be removed and no open flame will be permitted in the
area until adequate ventilation has been established around the well
bore; (14) After a well has been intersected and the working place
determined safe, mining will continue inby the well a sufficient
distance to permit adequate ventilation around the area of the well
bore; (15) No person will be permitted in the area of the well mining-
through operation except those actually engaged in the operation,
company personnel, representatives of the miners, personnel from MSHA,
and personnel from the appropriate State agency; (16) The mining-
through operation will be under the direct supervision of a certified
individual; (17) Instructions concerning the mining-through operation
will be issued only by the certified individual in charge; and (18)
MSHA personnel may interrupt or halt the mining-through operation when
it is necessary for the safety of miners. The petitioner states that:
(1) A copy of the Proposed Decision and Order will be maintained at the
mine office and be available to the Secretary's representatives,
miners' representatives, and miners; and (2) within 60 days after the
Proposed Decision and Order becomes final, the petitioner will submit
proposed revisions to the approved Part 48 training plans to the
District Manager. These proposed revisions will include initial and
refresher training regarding compliance with the terms
[[Page 12799]]
and conditions stated in the Proposed Decision and Order. The
petitioner asserts that the proposed alternative method of achieving
the results of the standard proposed by Bridger Coal Company will at
all times guarantee no less than the same measure of protection
afforded the miner under the existing standard.
Docket Number: M-2010-003-C.
Petitioner: Brooks Run Mining Company, LLC, 208 Business Street,
Beckley, West Virginia 25801.
Mine: Wyoming No. 2 Mine, MSHA I. D. No. 46-06263, located in
Wyoming County, West Virginia.
Regulation Affected: 30 CFR 75.1101-1(b) (Deluge-type water
systems).
Modification Request: The petitioner requests a modification of the
existing standard to permit nozzles to be used without blow-off dust
covers for its deluge-type water spray system. The petitioner proposes
to continue its weekly inspection and functional testing of the
complete deluge-type water spray system, and remove blow-off dust
covers from the nozzles. The petitioner states that: (1) Currently each
nozzle is provided with a blow-off dust cover. In view of the frequent
inspections and functional testing of the system, the dust covers are
not necessary because the nozzles can be maintained in an unclogged
condition through weekly use; and (2) it is burdensome to recap the
large number of covers weekly after each inspection and functional
test. The petitioner asserts that the proposed alternative method will
at all times guarantee no less than the same measure of protection
afforded the miners employed by said standard.
Docket Number: M-2010-004-C.
Petitioner: Jim Walter Resources, P.O. Box 133, Brookwood, Alabama
35444.
Mine: No. 7 Mine, MSHA I. D. No. 01-01401, located in Tuscaloosa
County, Alabama.
Regulation Affected: 30 CFR 75.507 (Power connection points).
Modification Request: The petitioner requests a modification of the
existing standard to permit the use of one or more three-phase, 2,400-
volt or 4,160-volt alternating current submersible pumps installed in
return and bleeder entries in the No. 7 Mine. The petitioner states
that: (1) The three-phase, 2, 400-volt or 4,160-volt, alternating
current electric power circuit for each pump will be designed and
installed to: (a) Contain either a direct or derived neutral, which
will be grounded through a suitable resistor at the source transformer
or power center. A grounding circuit originating at the grounded side
of the grounding resistor must extend along with the power conductors
and serve as the grounding conductor for the frame of each pump and all
associated electric equipment that may be supplied power from each such
circuit. The borehole casing will be bonded to the system grounding
medium; and (b) contain a grounding resistor that limits the ground-
fault current to not more than 6.5 amperes. The grounding resistor must
be rated for the maximum fault current available and must be insulated
from ground for a voltage equal to the phase-to-phase voltage of the
system. (2) The following protections for each pump power circuit will
be provided by a suitable circuit interrupting device of adequate
interrupting capacity with devices to provide protection against
undervoltage, grounded phase, short-circuit, and overload: (a) The
undervoltage protection device will operate on a loss of voltage to
prevent automatic restarting of the equipment; (b) the grounded phase
protection device will be set not to exceed fifty percent (50%) of the
current rating of the neutral grounding resistor; (c) the short circuit
protection device will not be set to exceed the required short circuit
protection for the power cable or seventy-five percent (75%) of the
minimum available phase-to-phase short circuit current, whichever is
less; (d) each power circuit will contain a disconnecting device
located on the surface and installed to provide visual evidence that
the power is disconnected; (e) each disconnecting device will include a
means to visually determine the relevant pump power circuit is
disconnected and be provided with a means to lock, tag-out, and ground
the system; (f) each disconnecting device shall be designed to prevent
entry unless the disconnect handle is in the ``off'' position and the
circuit is grounded; and (g) each disconnecting device will be clearly
identified and provided with a warning sign stating, ``Danger do not
enter unless the circuit is opened, locked, tagged-out, and grounded''.
(3) Each three-phase, alternating current system will be provided with
a low resistance grounding medium for the grounding of the lightning/
surge arrestors for the high-voltage pump power circuit that is
separated from the neutral grounding medium by a distance of not less
than twenty-five (25) feet. (4) The electric control circuit(s) for
each pump will meet the following requirements: (a) The control circuit
will be equipped with a circuit that determines a high and low water
level; (b) when the water level is reached, the pump will cease
operation and will not start in either the manual or automatic mode;
(c) when the high water level is reached, the pump will be capable of
operation; (d) the high and low water levels will be determined by a
differential pressure switch located at the surface; (e) the grounded-
phase protective circuit for each pump will be able to be tested by
injecting a test current through the grounded-phase current
transformer; and (f) a remote control and monitoring system can be used
with a pump system for condition monitoring and for remote startup and
shutdown control of the pump. The remote control and monitoring system
will not allow remote reset of the pump power system when any fault
condition (e.g., grounded phase, short circuit, or overload) exists on
the system. (5) Each surface pump control and power circuit will be
examined as required by 30 CFR 77.502. (6) The power cable to each
submersible pump motor must be suitable for this application, have a
current carrying capacity not less than one-hundred twenty-five percent
(125%) of the full load motor current of the submersible pump motor,
and have an outer jacket suitable for a wet location. The power cable
must be supported at the entrance to the borehole and throughout its
length by securing it with clamps, spaced approximately twenty-five
feet (25') apart, affixed to the discharge pipe casing. (7) A device
will be installed to monitor ground continuity from the starter box to
the well head. (8) The starter will be equipped with ground fault
``look-ahead'' device to prevent the motor from being energized during
a fault condition. (9) Each pump installation must comply with all
other applicable requirement of 30 CFR. (10) Within sixty (60) days
after this petition is granted, petitioner will submit proposed
revisions for their approved Part 48 training plan to the District 11
Manager. These provisions will specify task training for all qualified
mine electricians who perform electric work, monthly examinations as
required by 30 CFR 77.502, and refresher training regarding the
alternative method outlined in the petition. The procedures of 30 CFR
48.3 for approval of proposed revisions to already approved training
plans will apply. The petitioner asserts that the alternate method of
achieving the result of the existing standard will at all times
guarantee no less than the same measure of protection afforded the
miners by the present application of the standard.
[[Page 12800]]
Dated: March 12, 2010.
Patricia W. Silvey,
Director, Office of Standards, Regulations and Variances.
[FR Doc. 2010-5787 Filed 3-16-10; 8:45 am]
BILLING CODE 4510-43-P