Wyoming Administrative Code
Agency 020 - Environmental Quality, Dept. of
Sub-Agency 0011 - Water Quality
Chapter 12 - DESIGN AND CONSTRUCTION STANDARDS FOR PUBLIC WATER SUPPLIES
Section 12-16 - Distribution Systems
Current through September 21, 2024
(a) 2018 TSS, parts 8.2-8.2.4(b), system design; 8.3, valves; 8.4-8.4.4(d), hydrants; 8.5-8.5.2(c), air relief valves; 8.6, valve, meter, and blow-off chambers; 8.7.3, installation of water mains, cover; 8.7.4, installation of water mains, blocking; 8.7.6, installation of water mains, pressure and leakage testing; 8.7.7, installation of water mains, disinfection; 8.7.8, installation of water mains, external corrosion; 8.7.9, installation of water mains, separation from other utilities; 8.8.2-8.8.2(b), separation distances from contamination sources, parallel installation; 8.8.3-8.8.3(b), separation distances from contamination sources, crossings; 8.8.6, separation distances from contamination sources, sewer manholes, inlets, and structures; 8.9-8.9.1, surface water crossings, above-water crossings; 8.9.2-8.9.2(c); surface water crossings, under water crossings; 8.11.1, water services and plumbing, plumbing; 8.12, service meters; are herein incorporated by reference.
(b) Distribution systems shall be constructed of commercial pipe that conforms to the following standards:
(c) Flanged piping shall not be allowed for buried pipe except for connection to valves.
(d) New water mains shall be sized after the hydraulic analysis required by Section 9(l)(i) of this Chapter and the design shall demonstrate that:
(e) When fire protection is provided, the water main system shall be designed to also serve fire flows.
(f) Hydrants shall:
(g) Fire hydrants or active service taps may be substituted for air relief in 6- and 8-inch lines.
(h) Where excavation is performed for distribution systems:
(i) Distribution system bedding for rigid pipe shall be designed in accordance with ASTM C12 Classes A, B, or C. Flexible pipe bedding shall be designed in accordance with ASTM D2321 Class I, II, or III.
(j) Distribution system pipe shall be joined to ensure a watertight fitting and installed in accordance with the following standards, as applicable:
(k) Backfill for distribution systems shall:
(l) Distribution systems shall meet the following requirements for separation of water mains from sanitary and storm sewers:
(m) Cross-connections shall comply with the following requirements:
Table 4. Backflow Prevention Devices, Assemblies and Methods
Degree of Hazard |
|||||
Device, Assembly, or Method |
Low Hazard |
High Hazard |
Notes |
||
Back-Siphonage | Back-Pressure | Back-Siphonage | Back-Pressure | ||
Airgap |
X |
X |
X |
X |
See Note 1 and Note 2 |
Atmospheric Vacuum Breaker |
X |
X |
Not allowed under continuous pressure |
||
Spill-proof Pressure-type Vacuum |
X |
X |
|||
Double Check Valve Backflow Preventer |
X |
X |
|||
Pressure Vacuum Breaker |
X |
X |
|||
Reduced Pressure Principal Backflow |
X |
X |
X |
X |
See Note 2, |
Dual Check |
X |
Restricted to residential services |
Note 1: Minimum Airgap for Water Distribution. For spouts with an effective opening diameter of 1/2 inch or less, the minimum airgap when the discharge is not affected by side walls shall be one inch. The minimum airgap when the discharge is affected by sidewalls shall be 1 1/2 inches. For effective openings greater than 1/2 inch, the minimum airgap shall be two times the effective opening diameter when the discharge is not affected by sidewalls. The minimum airgap when the discharge is affected by sidewalls shall be three times the effective opening diameter.
Note 2: Extreme Hazards. In the case of any water user's system where, in the opinion of the water supplier or the Administrator, an undue health threat is posed because of the presence of extremely toxic substances or potential back pressures in excess of the design working pressure of the device, the water supplier may require an airgap at the water service connection to protect the public water system.