Wyoming Administrative Code
Agency 020 - Environmental Quality, Dept. of
Sub-Agency 0011 - Water Quality
Chapter 12 - DESIGN AND CONSTRUCTION STANDARDS FOR PUBLIC WATER SUPPLIES
Section 12-14 - Pumping Facilities

Universal Citation: WY Code of Rules 12-14

Current through September 21, 2024

(a) 2018 TSS, parts 6.1-6.1.1(e), location; 6.2, 6.2(b)-(e), pumping stations; 6.2.1-6.2.1(d), pumping stations, suction well; 6.2.2-6.2.2(b), pumping stations, equipment servicing; 6.3.2, pumps, pump priming; 6.6.1, appurtenances, valves; 6.6.3-6.6.3(d), appurtenances, gauges and meters; 6.6.4-6.6.4(b), appurtenances, water seals; 6.6.5, appurtenances, controls; 6.6.6, appurtenances, standby power; are herein incorporated by reference.

(b) Stairways or ladders shall be provided between all floors and in pits or compartments that must be entered.

(c) Pumping facilities shall be heated to maintain a minimum temperature of 40 degrees Fahrenheit if typically unoccupied and 50 degrees Fahrenheit if normally occupied.

(d) Pumping station ventilation designs shall demonstrate that:

(i) All areas of the pumping station that are accessible shall be ventilated;

(ii) Ventilation may be continuous or intermittent;

(iii) Drywell ventilation shall provide:
(A) At least six air changes per hour if continuous; and

(B) At least 30 air changes per hour if intermittent with an automatic start upon operator entry into the area.

(iv) Wetwell ventilation shall provide 12 continuous air changes per hour or 60 intermittent air changes per hour and be designed to permit the use of portable blowers that will exhaust the space and supply fresh air during the access periods.

(e) Dehumidification equipment shall be provided in below-ground pumping stations. The equipment shall be sized to maintain a dewpoint at least two degrees Fahrenheit below the coldest anticipated temperature of the water to be conveyed in the pipes.

(f) All pumping stations that are manned four or more hours per day shall be provided with potable water, lavatory, and toilet facilities. The waste shall be discharged to the sanitary sewer or an on-site waste treatment system.

(g) Pump design shall comply with the following requirements:

(i) At least two pumps shall be provided. With the largest pump out of service, the remaining pump or pumps shall be capable of providing the maximum pumping capacity of the system.

(ii) Pumps shall be selected such that the net positive suction head required (NPSHR) is less than the net positive suction head available (NPSHA) minus four feet based on hydraulic conditions and the altitude of the pump installation. If this condition cannot be satisfied, a means of priming shall be provided.

(iii) A surge analysis shall be provided to demonstrate if surge protection devices will be needed to protect the piping. Pressure relief valves are not acceptable as surge control.

(iv) The calculated total dynamic head for pumping units shall be based on pipe friction, pressure losses from pipe entrances, exits, appurtenances (such as valves and bends), and static head at the design flow.

(v) The station shall have a flow rate indicator and totalizing meter, and a method of recording the total water pumped.

(h) Booster pumps shall comply with the following requirements:

(i) Booster pumps shall not produce less than 5 psi in suction lines. If the suction line has service connections, the pressure shall be at least 35 psi during normal operation and shall have a low-pressure cutoff switch to maintain at least 20 psi.

(ii) For booster pumps used for fire suppression, no person shall install or maintain a water service connection to any premises where a fire pump has been installed on the service line to or within such premises unless the pump is equipped with one of the following:
(A) A low suction throttling valve or pilot-operated valve installed in the discharge piping that maintains positive pressure in the suction piping while monitoring pressure in the suction piping through a sensing line. The valve shall throttle the discharge of the pump when necessary so that suction pressure will not be reduced below 20 psi gauge when the pump is operating; or

(B) A variable-speed suction limiting control that is used to maintain a minimum positive suction pressure at the pump inlet by reducing the pump driver speed while monitoring pressure in the suction piping through a sensing line. The limiting control shall be set so that the suction pressure will not be reduced below 20 psi gauge while the pump is operating.

(iii) Automatic or remote-controlled pumps shall have a range between the start and cutoff pressure that will prevent the pump from cycling more than one start every 15 minutes.

(iv) In-line booster pumps shall be accessible for maintenance. There shall be access openings, as needed, to allow the removal of the pump.

(v) Individual home booster pumps shall not be allowed for any individual service from the public water supply main.

(vi) Un-manned or remotely controlled pump stations shall have an alarm at an operator attended location for any conditions that may affect the continuous delivery of water.

(i) Pumping facility valves shall comply with the following requirements:

(i) Air release valves shall be provided where the pipe crown is dropped in elevation. The discharge pipe from the valve shall have a minimum of an 8-inch air gap and shall be covered with a #24 mesh non-corrodible screen.

(ii) Each pump shall either have an individual suction line or the suction lines shall be manifolded such that they demonstrate similar hydraulic and operating conditions.

Disclaimer: These regulations may not be the most recent version. Wyoming may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.