(a) 2018 TSS, parts
2.10, sample taps; 3.1.4.1-3.1.4.1(i), surface water, structures, design of
intake structures; 3.1.4.3-3.1.4.3(f) surface water, structures, offstream raw
water storage reservoir; 3.1.6-3.1.6.3, surface water, impoundments and
reservoirs; 3.2.3.2, groundwater, location, continued sanitary protection;
3.2.4-3.2.4.14(b)(4), groundwater, general well construction; 3.2.5-3.2.5.4,
groundwater, testing and records; 3.2.6.1-3.2.6.1(c), groundwater, aquifer
types and construction methods--special conditions, sand or gravel wells;
3.2.6.2-3.2.6.2(b)(7), groundwater, aquifer types and construction
methods--special conditions, gravel pack material;
3.2.6.4-3.2.6.4(d),groundwater, aquifer types and construction methods--special
conditions, infiltration lines; 3.2.6.5-3.2.6.5(b), groundwater, aquifer types
and construction methods--special conditions, limestone or sandstone wells;
3.2.7.3-3.2.7.3(c)(3), groundwater, well pumps, discharge piping and
appurtenances, discharge piping; 3.2.7.4-3.2.7.4(d), groundwater, well pumps,
discharge piping and appurtenances, pitless well units; 3.2.7.6, groundwater,
well pumps, discharge piping and appurtenances, casing vent;
3.2.7.7-3.2.7.7(b), groundwater, well pumps, discharge piping and
appurtenances, water level measurement; 3.2.7.8-3.2.7.8(b), groundwater, well
pumps, discharge piping and appurtenances, observation wells; are herein
incorporated by reference.
(b)
Surface water intake structures that operate in the winter shall be capable of
minimizing the formation of ice on the intake.
(c) Transmission lines and interconnecting
process piping shall be capable of withstanding the forces and conditions they
will be subject to and comply with the following specifications for water
service, as applicable:
(i) AWWA
C200;
(ii) AWWA C207;
(iii) AWWA C208;
(iv) AWWA C220;
(v) AWWA C228;
(vi) AWWA C300;
(vii) AWWA C301;
(viii) AWWA C302;
(ix) AWWA C303;
(x) AWWA C304;
(xi) AWWA C900;
(xii) AWWA C901;
(xiii) AWWA C903;
(xiv) AWWA C904;
(xv) AWWA C906;
(xvi) AWWA C907;
(xvii) AWWA C909;
(xviii) AWWA C950;
(xix) ASTM A53;
(xx) ASTM A134;
(xxi) ASTM A135;
(xxii) ASTM A139;
(xxiii) ASTM D2846;
(xxiv) ASTM F480;
(xxv) ASTM F645;
(xxvi) ASTM F877;
(xxvii) ASTM F23891;
(xxviii) ASTM F2806;
(xxix) ASTM F2855;
(xxx) ASTM F2969;
(xxxi) API 5L:
(A) Grade B;
(B) Grade X42;
(C) Grade X46;
(D) Grade X52;
(E) Grade X56;
(F) Grade X60;
(G) Grade X65;
(H) Grade X70; or
(I) Grade X80.
(d) Designs shall not include any customer
service connection from the raw water transmission line to the treatment plant
unless there are provisions to treat the water to meet the requirements of this
Chapter, or the sole purpose of the service is for irrigation or agricultural
water use. For irrigation agricultural services, applicants shall conduct a
hazard classification and implement appropriate backflow prevention.
(e) Designs that include groundwater source
development shall comply with the following requirements:
(i) Proposed designs shall have a water
sample tap installed on groundwater sources prior to treatment or water storage
and shall include:
(A) Two wells that are each
capable of supplying the average daily demand with the largest producing well
out of service; or
(B) One well and
finished water storage that together equal twice the maximum daily demand;
or
(C) For public water supplies
that, as determined by the Administrator, are neither community water systems
nor nontransient noncommunity water systems, one well that is capable of
supplying the maximum daily demand.
(ii) Wells shall maintain the following
minimum isolation distances:
(A) If domestic
wastewater is the only wastewater present and the design domestic sewage flow
is less than 2,000 gpd, the following minimum isolation distance shall be
maintained:
Table 1. Isolation Distances for Domestic Sewage Flows Less
than 2,000 gpd
Source of Domestic
Wastewater |
Minimum Distance to Well |
Storm and Sanitary Sewer Collection Systems
|
50 feet |
Septic tank
|
100 feet
|
Absorption system
|
200 feet
|
(B)
If domestic wastewater is the only wastewater present and the design domestic
sewage flow is greater than 2,000 gpd but less than 10,000 gpd, the following
minimum isolation distances shall be maintained:
Table 2. Isolation Distances for Domestic Sewage Flows
Greater than 2,000 gpd
Source of Domestic
Wastewater |
Minimum Distance to Well |
Storm and Sanitary Sewer Collection Systems
|
0 feet |
Septic tank
|
100 feet
|
Absorption system
|
500 feet
|
(C)
If domestic wastewater is the only wastewater present and the design domestic
sewage flow is greater than 10,000 gallons per day or non-domestic wastewater
is present the required isolation distance shall be determined by a subsurface
study, in accordance with the requirements of Water Quality Rules Chapter 3,
Section 4, but shall not be
less than those required in Tables 1 and 2 of this Section.
(iii) Wells shall maintain the
following minimum isolation distances from buildings and property lines:
(A) When a well is outside of a building, the
well shall be located so that the surface casing has a clearance radius of a
minimum of 10 feet horizontally and will clear any projection from the
building;
(B) When a well is
located inside a building:
(I) The top of the
casing and any other well opening shall not terminate in the basement of the
building, or in any pit or space that is below natural ground surface unless
the well is completed with a properly protected submersible pump or provided
with provisions for drainage to the ground surface that is not subject to
flooding by surface water;
(II)
Wells located in a structure shall be accessible to pull the casing, pipe, or
pump; and
(III) The structure shall
have overhead access.
(C)
Wells shall be located at least 50 feet from any property
line.
(iv) Applicants for
wells shall complete testing and maintain records as follows:
(A) Yield and drawdown tests shall be
performed on every production well after construction or subsequent treatment
and prior to placement of the permanent pump. The test methods shall be clearly
indicated in the specifications. The test pump capacity, at maximum anticipated
drawdown, shall be at least 1.5 times the design rate anticipated. The well
shall be test pumped at the desired yield (design capacity) of the well for at
least 24 consecutive hours after stabilized drawdown. Alternatively, the well
may be pumped at a rate of 150 percent of the desired yield for at least six
continuous hours after stabilized drawdown.
(B) Every well shall be tested for plumbness
and alignment in accordance with AWWA A100.
(v) In addition to meeting the requirements
of Section
8 of this Chapter, plans for wells
developed through acidizing activities shall also include the following
elements:
(A) Information on the geology of
the area that contains descriptions of:
(I)
Known or potential faults, fractures, springs, karst features (such as
sinkholes and other similar features) within a one-mile radius of the proposed
well; and
(II) Faults and fractures
that may extend from the acidized zone into overlying and underlying geologic
formations and a description of any measures that will be taken to ensure that
the acidized solution does not migrate into any of those geologic
formations.
(B) For wells
developed within a radius of one mile of existing wells, applicants shall
submit plans that analyze the risk and mitigation measures to be taken to
prevent impacts to those wells and the risk and mitigation measures for any
potential effects to each existing well;
(C) Existing information on the location of
other wells (such as water supply, oil and gas, mineral development wells)
within a one-mile radius of the proposed well, including any wells that
intercept the acidized zone, and for wells that intercept the acidized zone:
(I) An analysis of whether or not those wells
that intercept the acidized zone have been properly plugged and
abandoned;
(II) An analysis of
whether or not those wells have been properly cased and cemented; and
(III) A description of what measures will be
or have been taken to prevent the acidized solution from migrating vertically
in the annular space or casing of the existing wells into overlying or
underlying geologic formations.
(D) A description of the borehole drilling
phase and what measures will be taken to minimize the introduction of lost
circulation materials into aquifers when encountering under-pressured geologic
formations or other factors that may lead to a loss of circulation;
(E) A description of the acid injection
process and the measures that will be taken to ensure that injection pressures
do not create fractures in the overlying and underlying geologic formations and
through which the acidized solution may migrate;
(F) A description of the volume and content
of the acid and any other chemical compounds to be used during acidizing
activities, including the management of the acid and chemical compounds prior
to acidizing and final disposition of any acid, water, or chemical mixtures
recovered from the well after acidizing activities are completed;
(G) A description of the measures that will
be or have been taken to ensure that the recovery of the acidized solution is
of sufficient duration and volume to eliminate the potential for acidic impacts
to other wells completed within the injection zone; and
(H) A description of the methods to be
performed to establish the placement and integrity of the annular seal and
casing prior to acidization of the well.
(vi) During any well construction or
modification, the well and surrounding area shall be adequately protected to
prevent any groundwater contamination. Surface water shall be diverted away
from the construction area.
(vii)
All wells shall comply with the following construction standards:
(A) Dug wells shall be constructed according
to the State Engineer's standards;
(B) Drilled, driven, jetted, or bored wells
shall have an unperforated casing that extends from a minimum of 12 inches
above the concrete surface and 18 inches above natural ground surface and the
design shall demonstrate compliance with Water Quality Rules, Chapter 26,
Section 8;
(C) In gravel-packed wells or artificial
filter-packed wells, aquifers containing inferior quality water shall be sealed
by pressure grouting, or with special packers or seals, to prevent such water
from moving vertically in gravel-packed portions of the well. Gravel-packed
wells shall meet the following sealing requirements:
(I) If a permanent surface casing is not
installed, the annular opening between the casing and the drill hole shall be
sealed in the top 10 feet with concrete or cement grout; or
(II) If a permanent surface casing is
installed, it shall extend to a depth of at least 10 feet. The annular opening
between this outer casing and the inner casing shall be covered with a metal or
cement seal.
(D) When
naturally flowing water is encountered in a well, unperforated casing shall
extend into the confining layer overlying the water-bearing zone. This casing
shall be adequately sealed with cement grout into the confining zone and shall
extend at least 10 feet into the target aquifer to prevent both surface and
subsurface leakage from the water-bearing zone. The method of construction
shall be such that during the placing of the grout and the time required for it
to set, no water shall flow through or around the annular space outside the
casing, and no water pressure sufficient to disturb the grout prior to final
set shall occur. Drilling operations shall not be continued into the
water-bearing zone until the grout has set completely. If leakage occurs around
the well casing or adjacent to the well, the well shall be recompleted with any
seals, packers, or casing necessary to eliminate the leakage completely.
(I) Flowing wells shall be constructed to
control the flow of water from the well. The well grouting shall be engineered
to prevent the movement of water along the well casing and to prevent the
migration of pressurized water into upper aquifers. A flow control device shall
be installed into the wellhead to control the flow of water from the well. The
well discharge or overflow line installations must connect to the well casing
at least 12 inches above ground and be valved. The size of the air gap between
the overflow line from the well to drainage structure shall be twice the
diameter of the well overflow pipe. Overflow water must be drained and diverted
to prevent ponding around the well casing.
(II) There shall be no direct connection
between any discharge pipe and a sewer or other source of pollution and all
terminations shall provide for an air gap of 3 pipe diameters for drain or
overflow above an opening to a sanitary or storm sewer.
(E) If mineralized water or water known to be
polluted is encountered during the construction of a well, the aquifer or
aquifers containing such inferior quality of water shall be adequately cased or
sealed off to prevent water from entering the well and to prevent water from
moving up or down the annular space.
(I) For
wells that penetrate multiple aquifers, mineralized water shall be excluded
from the well if water is taken from other, non-mineralized aquifers.
(II) Applicants that propose to use
mineralized water as a public water supply shall demonstrate that any necessary
treatment will comply with the drinking water quality standards required by 40
CFR Part 141.
(F)
Existing oil or gas wells, private water wells, or exploration test holes that
can be completed to conform to all minimum construction standards required by
this Chapter may be converted for use as a public water supply well. The permit
application shall identify all actions to be completed to achieve compliance
with this Chapter.
(viii)
The minimum grout thickness for public water supply wells shall be determined
in accordance with AWWA Standard A100, part 4.7.8.3.
(ix) Well seals shall meet the following
requirements:
(A) The annular space shall be
sealed to protect against contamination or pollution by the entrance of surface
or shallow subsurface waters; and
(B) Annular seals shall be installed to
provide protection for the casing against corrosion, to ensure the structural
integrity of the casing, and to stabilize the upper formation.
(x) Upper terminal well designs
that include a concrete floor shall demonstrate a slope of one inch per foot
away from the casing.
(xi) Well
pumps shall be located at a point above the top of the well screen.
(xii) An accessible check valve that is not
located in the pump column shall be installed in the discharge line of each
well between the pump and the shut-off valve. Additional check valves shall be
located in the pump column as necessary to prevent negative pressures on the
discharge piping.
(xiii) A pitless
adaptor or well house shall be used where needed to protect the water system
from freezing.
(xiv) A frost pit
may be used only in conjunction with a properly protected pitless
adaptor.
(xv) Wells with diameters
that are greater than four inches shall be equipped with an air line for water
level measurements or, in the case of a flowing artesian well, with a pressure
gauge that will indicate pressure.
(xvi) An instantaneous and totalizing flow
meter equipped with nonvolatile memory shall be installed on the discharge line
of each well in accordance with the manufacturer's specifications. Meters
installed on systems with variable frequency drives shall be capable of
accurately reading the full range of flow rates.
(xvii) Test wells and groundwater sources
that are sealed for plugging and abandonment in accordance with requirements of
Water Quality Rules Chapter 26, Section
11 shall be sealed by filling with neat
cement grout. The filling materials shall be applied to the well hole through a
pipe, or tremie.
(xviii) Designs
for groundwater sources that are subject to
40 CFR
141.402(a)(1)(i) and either
40 CFR
141.402(a)(1)(ii) or 40 CFR
141.402(a)(1)(iii) shall demonstrate compliance with
40 CFR
141.402(e).
(f) Facilities that include spring
development shall meet the following requirements:
(i) Spring collection systems shall be
constructed to collect spring water while preventing contamination of the
source from the ground surface or other contaminant sources.
(ii) Seepage springs shall have a trench for
the collection site that extends at least six inches into the impervious layer,
but not entirely through the impervious layer. Concentrated springs shall be
developed down to bedrock.
(iii) A
bed of clean and disinfected rock that extends the width of the spring from
which water is being collected shall be installed at the collection
site.
(iv) The collection site
shall:
(A) Be covered with 60 mil plastic
sheeting or an equivalent puncture-proof and water-proof barrier; and
(B) Be protected from damage during back-fill
and re-grading of the site to the original surface elevation with protective
fabric or sand.
(v)
Collecting walls shall be:
(A) Constructed
immediately downstream of the collection site; and
(B) Made of concrete, or other material that
meets the requirements of Section
15(b)(ii) of this
Chapter;
(vi) The spring
water collection pipe shall be installed in accordance with the USDA NRCS Part
631 National Engineering Handbook, Chapter 32, part 631.3201(b)(iii) for
delivery pipes and shall meet the following requirements:
(A) The size of the collection pipe shall be
sufficient to convey the flow of the spring; and
(B) Pipe material and appurtenances shall
comply with allowable well construction material for water distribution in
accordance with the standards listed in paragraph (c) of this
Section.
(vii)
Appropriate bedding and cover material shall protect the spring collection
system from damage and freezing.
(viii) The Administrator shall determine the
spring protection area, based on the information submitted in the engineering
design report required by Section
8 of this Chapter, which shall be no less
than the isolation distances in (e)(ii) of this Section. The Administrator may
require additional setback distances if the engineering design report
demonstrates the additional distance is required to prevent contamination of
the source from the ground surface or other contaminant sources.
(ix) All potential sources of contamination
shall be removed from the spring protection area.
(x) The spring collection site shall include
fencing or other protective features that are constructed and secured to
exclude large animals and unauthorized persons from entering the protection
area.
(A) Fencing shall be designed to
withstand animals and snow loading. Other protective systems may be
proposed.
(B) Fencing shall include
an entry point to allow access by authorized persons for inspection and
maintenance activities.
(xi) The spring collection site shall include
a diversion ditch that is constructed on the upstream side of the spring
collection site to route surface water flows away from the collection area. The
diversion ditch shall be located a minimum of 10 feet away from the collection
wall.
(xii) The spring collection
site shall be equipped to disinfect water prior to distribution and shall
include sampling ports before and after the disinfection application point. The
equipment shall be maintained and available to operate for its intended
use.
(xiii) Spring box designs
shall comply Section
15(a), (b), (f-j), and
(l) of this Chapter. Combined spring box and
finished water storage designs shall comply with Section
15 of this Chapter.
(xiv) All designs for the spring collector
box and collecting walls shall be performed by a Wyoming registered
professional engineer. The plans or contractor furnished information shall be
signed and sealed by a Wyoming registered professional engineer.