Wyoming Administrative Code
Agency 010 - Agriculture, Dept. of
Sub-Agency 0008 - Public Swimming Pools
Chapter 3 - GENERAL AND STRUCTURAL DESIGN; EQUIPMENT STANDARDS
Section 3-23 - Air Blower and Air Induction Systems; Entry Devices
Current through September 21, 2024
(a) This section pertains to all devices and systems which induce or allow air to enter the spa either by means of a power pump or passive design.
(b) Integral air passages shall be pressure tested at the time of manufacture to provide structural integrity to a value of one and one-half (11/2) times the intended working pressure.
(c) An air induction system shall totally prevent water back-up that could cause electrical shock hazards.
(d) A hydrotherapy pump and air blower in a spa pool shall be connected to a maximum fifteen (15) minute time switch located no closer than ten (10) feet (3m) from the spa water's edge.
(e) Air blower and air induction systems must be separate from the recirculation system.