Current through August 26, 2024
(1) NUMBER OF FEEDERS. If chemical feed, such
as chlorination, coagulation or other essential processes, is necessary to
produce a water quality meeting the primary maximum contaminant levels, a
minimum of 2 feeders shall be provided so that a standby unit or combination of
units will be available to replace the largest unit during shut-downs. Spare
parts shall be available for all feeders to replace parts which are subject to
wear and damage.
(2) DESIGN AND
CAPACITY. The design and capacity of chemical feed equipment shall meet all of
the following requirements:
(a)
Separate chemical feed systems. Separate chemical feed systems
shall be provided in accordance with the following requirements:
1. A separate feed system shall be provided
for each chemical.
2. Separate
disinfection chemical feed systems shall be provided if pre- and post- water
treatment disinfection application points are installed.
3. Each chemical feed pump or gas feeder
shall take suction from its own dedicated chemical solution tank or gas
cylinders. The department may approve multiple chemical feed pumps or gas
feeders for the same process application point taking suction from the same
chemical solution tank or gas cylinders in the following situations:
a. Where multiple water sources are
discharging to the same location. In this case, a means shall be provided for
determining the flow from each individual water source.
b. Where multiple pumps are pumping from the
same water source and discharging to the same location through a combined
header pipe. In this case, a means shall be provided for measuring total
flow.
c. For the situations in
subd. 3. a. and b., a single chemical feeder with a single feed point or
multiple chemical feeders with multiple feed points may be used, provided the
installation meets the other requirements of this subchapter.
Note: An example of subd. 3. a. would be
multiple wells discharging to a single reservoir or water treatment plant. An
example of subd. 3. b. would be multiple high-lift pumps taking suction from a
single reservoir and discharging to a combined pump discharge
pipe.
(b)
Acceptable chemical feed
pumps. Positive displacement diaphragm metering pumps, peristaltic
chemical feed pumps or other pumps, as approved by the department, shall be
used to feed liquid chemicals. Pumps shall be sized to match or exceed maximum
head conditions found at the point of injection.
(c)
Chemical feeder
settings. Feeders shall be able to supply, at all times, the necessary
amounts of chemical at an accurate rate, throughout the range of feed. All
positive displacement diaphragm metering pumps shall be operated at a minimum
speed setting of 12 strokes per minute. For positive displacement diaphragm
metering pumps with an adjustable stroke length the pumps shall be operated at
a minimum of 20 percent of the maximum stroke length. Peristaltic chemical feed
pumps shall be operated at a minimum of 10 percent of the maximum feeder output
for the given interior diameter of the feed tube installed. If these operating
requirements cannot be met using stock chemical solution, dilution of the
chemical shall be required.
(d)
Flow paced chemical feed. Automatic proportioning of chemical
feed to rate of water flow shall be provided when water flow rates will vary.
Chemical feed pumps shall be proportionally flow paced by a signal from a water
meter when discharge rates from a well or service pump will be variable over
the pump cycle. When applicable, this includes variable output control devices
as required by s.
NR 811.34 (5).
(e)
Anti-siphon devices.
Chemical feed pumps shall be provided with anti-siphon devices meeting all of
the following requirements:
1. All electronic
positive displacement diaphragm metering pumps shall be provided with a
spring-opposed diaphragm type anti-siphon device or a spring opposed diaphragm
type anti-siphon and back pressure valve device installed in the discharge
piping of the chemical feed pump. The anti-siphon and back pressure functions
may be part of a common device or separate devices. Any back pressure valve
shall be set to open at a pressure greater than the maximum pressure in the
piping or facilities into which the chemical feed pump will discharge. When a
back pressure valve is installed on the discharge piping of a chemical feed
pump, it shall be preceded by a pressure relief valve and a pressure gauge or
other department approved means to verify that the back pressure valve is
operating satisfactory.
3.
Peristaltic chemical feed pumps shall be provided with a back pressure valve
device installed in the discharge piping of the chemical feed pump in
accordance with the requirements under subd. 1. The department may allow
exceptions to the requirements under subd. 1. for peristaltic chemical feed
pumps when the installation meets all of the following requirements:
a. The pump has 3 rollers.
b. The pump has a sealed roller
housing.
c. A check valve is
installed at the point of chemical injection.
d. The pump is installed above the top of the
chemical solution tank.
e. The
chemical injection location is at a point of continuous positive
pressure.
4. The
department may be contacted to request approval of an equivalent anti-siphon
device or equivalent means of providing anti-siphon protection if the
installation of the anti-siphon devices as required in subds. 1. to 3. is not
practical given the properties of the chemical to be fed. Adequate
justification shall be provided to the department for the request.
(f)
Location of chemical
injection.1. Chemical solutions
shall be prevented from being siphoned into the water supply. Anti-siphon
protection shall be provided by discharging chemicals at points of positive
pressure and by providing anti-siphon devices in accordance with par. (e), or
through a suitable air gap or other effective means approved by the
department.
2. All chemicals shall
be fed downstream of the check valve. Strong acids and bases such as
fluorosilicic acid and sodium hydroxide shall be fed downstream of both the
check valve and the shut-off valve.
Note: It is recommended that all chemicals be
fed downstream of both the check valve and the shutoff valve. If a second
shut-off valve is provided downstream of the primary shut-off valve, the point
of injection may be between the 2 shut-off valves.
3. If chemical feeding is at a location
without continuous positive pressure, one of the following installation
requirements shall be met to prevent siphoning of chemical solutions:
a. A suitable air gap shall be provided which
is at a higher elevation than the chemical solution tank.
b. A dual head feeder with a small break tank
located higher than the chemical solution tank shall be provided.
c. A chemical feed pump discharging without
any air gap or break box may be approved by the department on a case-by-case
basis if the installation is provided with a spring opposed diaphragm type
anti-siphon and back pressure valve device. The back pressure valve shall be
installed as close as possible to the point of chemical addition. The spring
opposed diaphragm type anti-siphon and back pressure valve device shall be
installed in accordance with the requirements of par. (e) 1.
(g)
Makeup
water lines. The makeup water supply lines to chemical feed tanks
shall be protected from contamination by chemical solutions either by equipping
the supply line with backflow or backsiphonage prevention devices, or by
providing an air gap between the supply line and the top of the solution
tank.
(h)
Chemical
resistance. Materials and surfaces coming in contact with chemicals
shall be resistant to the aggressiveness of the chemical solution.
(i)
Dry chemical feeders.
Dry chemical feeders shall meet the following requirements:
1. Measure chemicals volumetrically or
gravimetrically.
2. Provide
effective dissolving and mixing of the chemical in the solution pot and provide
gravity feed from solution pots, if possible.
3. Completely enclose chemicals to prevent
emission of dust to the operating room.
(j)
Direct sewer connections
prohibited. No direct connection shall be made between any sanitary or
storm sewer and a drain or overflow from any feeder or solution chamber or
tank.
(3) LOCATION.
Chemical feed equipment shall meet the following requirements:
(a) Be located near points of application to
minimize length of feed lines.
(b)
Be readily accessible for servicing or repair and observation of
operation.
(c) Be located and have
protective containment curbs so that chemicals from equipment failure,
spillage, or accidental drainage may not enter the water in conduits,
treatment, or storage basins.
(d)
Be located within a containment basin capable of receiving accidental spills,
drainage, or overflows without an uncontrolled discharge outside of the
containment basin. At minimum, the containment basin shall be sized to contain
the volume of the largest tank that could fail. Chemical containment basins
shall not be provided with floor drains. Trapped and vented floor drains
discharging to sanitary sewers, holding tanks, or the ground surface in
accordance with s.
NR 811.25 (1)
(h) may be installed for chemical rooms
outside of containment basins. Chemical feed pumps shall be located within the
containment basin. Piping shall be designed to minimize or contain chemical
spills in the event of pipe ruptures.
(e) Be located above grade, except if this
requirement is waived by the department.
(f) Be located in accordance with s.
NR 811.48 (5) if gas chlorine feeders are
used.
(g) Be located in accordance
with s.
NR 811.51 (2) if fluorosilicic acid is used.
(4) CONTROL. Chemical feeders
shall be controlled in accordance with the following requirements:
(a) Feeders may be manually or automatically
controlled if the water supply pumps are manually controlled. Where pumps are
automatically controlled, the feeders shall be automatically controlled. In all
cases, automatic control shall be capable of reverting to manual control when
necessary.
(b) The operation of the
chemical feed pumps shall be interlocked with the operation of the appropriate
well or service pump. Any controlled electrical outlet used for any chemical
feed pump shall be clearly marked.
(c) Secondary control of chemical feed
equipment shall be provided for fluoride chemical feed equipment in accordance
with s.
NR 811.51 (4) or when required by the
department.
(d) Feeders shall be
designed and controlled to provide chemical feed rates proportional to flow and
for variable flow rates shall be paced by a water meter.
(e) Automatic chemical feed rate control in
combination with residual analyzers which have alarms for critical values and
SCADA system reporting or recording charts may be used.
(5) SOLUTION TANKS. The requirements for
solution tanks, in s.
NR 811.40 on storage and handling apply.
(6) CHEMICAL USE MEASUREMENT. The
determination of chemical usage when using chemical feeders shall meet all of
the following requirements:
(a) Weighing
scales shall be provided for weighing cylinders at all plants utilizing
chlorine gas.
Note: It is recommended that indicating and
recording type scales be used.
(b) Weighing scales are required for liquid
solution feed unless comparable means for determining usage is approved by the
department.
(c) Weighing scales are
required for volumetric dry chemical feeders.
(d) Weighing scales shall be accurate enough
to measure increments of 0.5 percent of load.
(e) Graduated lines on chemical tanks shall
be displayed in units of volume and be in maximum increments of 3 percent of
tank capacity.
(f) Radar and sonic
level sensors that are programmed to display in pounds of chemical and that are
accurate enough to measure increments of 0.5 percent of load may be used to
determine chemical use.
(7) FEED LINES. Feed lines shall meet the
following requirements:
(a) Be as short as
possible in length of run, of durable, corrosion resistant material, easily
accessible throughout the entire length, protected against freezing, and
readily cleanable.
(b) Slope upward
from chemical source to feeder when conveying gases.
(c) Introduce corrosive chemicals in a manner
to minimize potential for corrosion.
(d) Be designed consistent with scale-forming
or solids-depositing properties of the water, chemical, solution, or mixture
conveyed.
(e) Not carry chlorine
gas under pressure beyond the chlorine feeder room.
(f) Include injection taps constructed of
metal or SCH 80 PVC components and check valves. Removable injection quills
shall be provided when application is into a pipe of adequate diameter.
Injection quills installed in a horizontal section of pipe shall be installed
up into the bottom half of the pipe.
(g) Be color coded in accordance with s.
NR 811.28 (6).
(8) SERVICE AND CARRIER WATER SUPPLY. Water
used for dissolving dry chemicals, diluting liquid chemicals, operating
chemical feeders or as carrier water to deliver chemicals to injection
locations shall be from a safe, approved source with appropriate backflow
prevention provided. The department may grant an exception in cases where the
finished water quality will not be affected by addition of the chemical mixed
with untreated water.