CT Values for Inactivation of Giardia lamblia Cysts by Chloramine pH 6-9

Inactivation Temperature, °C
[LESS than]= 1 5 10 15 20 25
0.5-log 635 365 310 250 185 125
1-log 1,270 736 615 500 370 250
1.5-log 1,900 1,100 930 750 550 375
2-log 2,535 1,470 1,230 1,000 735 500
2.5-log 3,170 1,830 1,540 1,250 915 625
3-log 3,800 2,200 1,850 1,500 1,100 750

Disclaimer: These regulations may not be the most recent version. Wisconsin may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.