(1) MONITORING.
Note: Sections NR 809.974 and 809.975 were repealed by CR 15-049. Corrections will be made in future rulemaking.
Table Y
Stage 2 DBP - Disinfection byproducts monitoring frequency, locations, and sample type
Source water type |
Population size category |
Monitoring frequency |
Distribution system monitoring location total per monitoring period |
Sample type |
Surface water and GWUDI: |
||||
<500 |
Annual |
2 |
Individual; option of one dual sample at one location if highest DBP concentrations are at the same location and month |
|
500-3,300 |
quarterly |
2 |
Individual |
|
3,301-9,999 |
quarterly |
2 |
Dual |
|
10,000-49,999 |
quarterly |
4 |
Dual |
|
50,000-249,999 |
quarterly |
8 |
Dual |
|
250,000-999,999 |
quarterly |
12 |
Dual |
|
1,000,000-4,999,999 |
quarterly |
16 |
Dual |
|
>= 5,000,000 |
quarterly |
20 |
Dual |
|
Groundwater: |
||||
<500 |
Annual |
2 |
Individual; option of one dual sample at one location if highest DBP concentrations are at the same location and month |
|
500-9,999 |
Annual |
2 |
Dual |
|
10,000-99,999 |
quarterly |
4 |
Dual |
|
100,000-499,999 |
quarterly |
6 |
Dual |
|
>= 500,000 |
quarterly |
8 |
Dual |
(2) ANALYTICAL METHODS AND LABORATORIES.