(1) REPORTING
REQUIREMENTS. Water suppliers for public water systems required to be sampled
quarterly or more frequently shall report to the department within 10 days
after the end of each quarter in which samples were collected, notwithstanding
the provisions of s.
NR 809.563. Water suppliers for public water systems
required to be sampled less frequently than quarterly shall report to the
department within 10 days after the end of each monitoring period in which
samples were collected.
(2)
REPORTING AND RECORDKEEPING REQUIREMENTS FOR DISINFECTION BYPRODUCTS. Water
suppliers for public water systems monitored for disinfection byproducts shall
report the information specified in the following requirements:
(a) Water supplier for public water systems
monitored for TTHM and HAA5 under the requirements of s.
NR 809.565(2) on a quarterly or more
frequent basis shall report all of the following:
1. The number of samples taken during the
last quarter.
2. The location, date
and result of each sample taken during the last quarter.
3. The arithmetic average of all samples
taken in the last quarter.
4. The
annual arithmetic average of the quarterly arithmetic averages for the last 4
quarters.
5. Whether the MCL was
exceeded, as determined according to s.
NR 809.566(2).
(b) Water supplier for public water systems
monitored for TTHMs and HAA5s under the requirements of s.
NR 809.565(2) less frequently than
quarterly but at least annually shall report all of the following:
1. The number of samples taken during the
last year.
2. The location, date
and result of each sample taken during the last quarter.
3. The arithmetic average of all samples
taken over the last year.
4.
Whether the MCL was exceeded, as determined according to s.
NR 809.566(2).
(c) Water supplier for public water systems
monitored for TTHMs and HAA5s under the requirements of s.
NR 809.565(2) less frequently than
annually shall report all of the following:
1. The location, date and result of the last
sample taken.
2. Whether the MCL
was exceeded, as determined according to s.
NR 809.566(2).
(d) Water supplier for public water systems
monitored for chlorite under the requirements of s.
NR 809.565(3) (a) shall report all of
the following:
1. The number of samples taken
each month for the last 3 months.
2. The location, date and result of each
sample taken during the last quarter.
3. For each month in the reporting period,
the arithmetic average of all samples taken in each 3 sample set collected in
the distribution system.
4.
Whether, based on s.
NR 809.566(2) (c), the MCL was exceeded,
and how many times it was exceeded each month.
(e) Water supplier for public water systems
monitored for bromate under the requirements of s.
NR 809.565(3) (b) shall report all of
the following:
1. The number of samples taken
during the last quarter.
2. The
location, date and result of each sample taken during the last
quarter.
3. The arithmetic average
of the monthly arithmetic averages of all samples taken in the last
year.
4. Whether the MCL was
exceeded, as determined according to s.
NR 809.566(2) (b).
(3) REPORTING AND RECORDKEEPING
REQUIREMENTS FOR DISINFECTANTS. Water supplier for public water systems
monitored for disinfectants shall report the information specified in the
following:
(a) Water supplier for public
water systems monitored for chlorine or chloramines under the requirements of
s.
NR 809.565(4) (a) shall report all of
the following:
1. The number of samples taken
during each month of the last quarter.
2. The monthly arithmetic average of all
samples taken in each month for the last 12 months.
3. The arithmetic average of all monthly
averages for the last 12 months.
4.
Whether the MRDL was exceeded, as determined according to s.
NR 809.566(3) (a).
(b) Water supplier for public water systems
monitored for chlorine dioxide under the requirements of s.
NR 809.565(4) (b) shall report all of
the following information:
1. The dates,
results and locations of samples taken during the last quarter.
2. Whether the MRDL was exceeded, as
determined according to s.
NR 809.566(3) (b).
3. Whether the MRDL was exceeded in any 2
consecutive daily samples and whether the resulting violation was acute or
nonacute as determined according to s.
NR 809.566(3) (b).
(4) DISINFECTION BYPRODUCT
PRECURSORS, ENHANCED COAGULATION OR ENHANCED SOFTENING TREATMENT SYSTEMS. Water
supplier for public water systems containing disinfection byproduct precursors
or using enhanced coagulation or enhanced softening, shall report the
information specified in the following:
(a)
Water supplier for public water systems monitored monthly or quarterly for TOC
under the requirements of s.
NR 809.565(5) and required to meet the
enhanced coagulation or enhanced softening requirements in s.
NR 809.569(1) (b) or (c) shall report
all of the following:
1. The number of paired
samples of source water and treated water, both prior to continuous
disinfection, taken during the last quarter.
2. The location, date and result of each
paired sample and associated alkalinity taken during the last
quarter.
3. For each month in the
reporting period that paired samples were taken, the arithmetic average of the
percent reduction of TOC for each paired sample and the required TOC percent
removal.
4. Calculations for
determining compliance with the TOC percent removal requirements, as provided
in s.
NR 809.569(3).
5. Whether the public water system is in
compliance with the enhanced coagulation or enhanced softening percent removal
requirements in s.
NR 809.569(1) for the last 4
quarters.
(b) Water
supplier for public water systems monitored monthly or quarterly for TOC under
the requirements of s.
NR 809.565(5) and meeting one or more of
the alternative compliance criteria in s.
NR 809.569(2) (b) or (c) shall report
all of the following:
1. The alternative
compliance criterion that the water supplier for the public water system is
using.
2. The number of paired
samples taken during the last quarter.
3. The location, date and result of each
paired sample and associated alkalinity taken during the last
quarter.
4. The running annual
arithmetic average based on monthly averages or quarterly samples of source
water TOC for public water systems meeting a criterion in s.
NR 809.569(2) (b) 1. and 3. or of
treated water TOC for public water systems meeting the criterion in s.
NR 809.569(2) (b) 2.
5. The running annual arithmetic average
based on monthly averages or quarterly samples of source water SUVA for public
water systems meeting the criterion in s.
NR 809.569(2) (b) 6. or of treated water
SUVA for public water systems meeting the criterion in s.
NR 809.569(2) (b) 7.
6. The running annual average of source water
alkalinity for public water systems meeting the criterion in s.
NR 809.569(2) (b) 3. and 4. and of
treated water alkalinity for public water systems meeting the criterion in s.
NR 809.569(2) (c) 1.
7. The running annual average for both TTHM
and HAA5 for public water systems meeting the criterion in s.
NR 809.569(2) (b) 3., 4., and
5.
8. The running annual average of
the amount of magnesium hardness removal (as CaCO3 mg/L) for public water
systems meeting the criterion in s. NR 809.567(2) (c) 2.
9. Whether the public water system is in
compliance with the particular alternative compliance criterion in s.
NR 809.569(2) (b) and (c).