(1)
ROUTINE AND REDUCED MONITORING.
(a)
Monitoring site plans. Water suppliers for all public water
systems shall collect total coliform samples at sites which are representative
of water throughout the distribution system according to a written sample
siting plan. These plans are subject to department review and revision.
Monitoring required by this section and s. NR 809.32 may take place at a
customer's premise, dedicated sampling station, or other designated compliance
sampling location. Routine and repeat sample sites and any sampling points
necessary to meet the requirements of s. NR 809.325 shall be identified in the
sampling plan.
(ag)
Action
after total coliform positive sample. Following any total
coliform-positive sample taken under the provisions of this section, water
suppliers shall comply with the repeat monitoring requirements and E.
coli analytical requirements in subs. (2) and (4).
(ar)
Transition from total coliform
rule to revised total coliform rule.
1. Water suppliers of public water systems,
including seasonal systems, shall continue to monitor according to the total
coliform monitoring schedules that were in effect on March 31, 2016, unless any
of the conditions for increased monitoring in sub. (2m) are triggered on or
after April 1, 2016, or unless otherwise directed by the department.
2. Beginning April 1, 2016, the department
shall perform a special monitoring evaluation during each sanitary survey to
review the status of each public water system, including the distribution
system, to determine whether the public water system is on an appropriate
monitoring schedule. After the department has performed the special monitoring
evaluation during each sanitary survey, the department may modify the public
water system's monitoring schedule, as necessary, or it may allow the public
water system to stay on its existing monitoring schedule, consistent with the
provisions of this section. The department may not allow public water systems
to begin less frequent monitoring under the special monitoring evaluation
unless the public water system has already met the applicable criteria for less
frequent monitoring in this section. For seasonal systems on quarterly or
annual monitoring, this evaluation shall include review of the approved sample
siting plan, which shall designate the time period(s) for monitoring based on
site-specific considerations (e.g., during periods of highest demand or highest
vulnerability to contamination). The water supplier of the seasonal system
shall collect compliance samples during these time periods.
(b)
Monitoring frequency
at community water systems. Water suppliers for community water
systems shall take water samples for coliform determination at regular
intervals, and in a number proportionate to the population served by the
community water system. Water suppliers required to collect multiple samples
each month shall sample at geographically representative locations and on dates
evenly spaced during the month. The minimum sampling frequency shall be as set
forth in the following table:
Population served:
|
Minimum number of samples per
month
|
25 to 1,000 (Not serving a municipality)
|
1
|
25 to 1,000 (Serving a municipality)
|
2
|
1,001 to 2,500
|
2
|
2,501 to 3,300
|
3
|
3,301 to 4,100
|
4
|
4,101 to 4,900
|
5
|
4,901 to 5,800
|
6
|
5,801 to 6,700
|
7
|
6,701 to 7,600
|
8
|
7,601 to 8,500
|
9
|
8,501 to 12,900
|
10
|
12,901 to 17,200
|
15
|
17,201 to 21,500
|
20
|
21,501 to 25,000
|
25
|
25,001 to 33,000
|
30
|
33,001 to 41,000
|
40
|
41,001 to 50,000
|
50
|
50,001 to 59,000
|
60
|
59,001 to 70,000
|
70
|
70,001 to 83,000
|
80
|
83,001 to 96,000
|
90
|
96,001 to 130,000
|
100
|
130,001 to 220,000
|
120
|
220,001 to 320,000
|
150
|
320,001 to 450,000
|
180
|
450,001 to 600,000
|
210
|
600,001 to 780,000
|
240
|
780,001 to 970,000
|
270
|
970,001 to 1,230,000
|
300
|
1,230,001 to 1,520,000
|
330
|
1,520,001 to 1,850,000
|
360
|
1,850,001 to 2,270,000
|
390
|
2,270,001 to 3,020,000
|
420
|
3,020,001 to 3,960,000
|
450
|
3,960,001 or more
|
480
|
(c)
Monitoring frequency for coliforms at non-community water
systems. The monitoring frequency for total coliforms for
non-community water systems, notwithstanding pars. (dg) and (dr), is as
follows:
1. A water supplier for a
non-community water system using only groundwater and serving 1,000 persons per
day or fewer shall monitor each calendar quarter that the non-community water
system provides water to the public.
2. A water supplier for a non-community water
system using only groundwater and serving on average more than 1,000 persons
per day for any month shall monitor at the same frequency as a like-sized
community water system, as specified in par. (b), except that the department
may reduce the monitoring frequency, in writing, for any month the average
daily population served is 1,000 persons or fewer per day.
3. A water supplier for a non-community water
system using surface water, or groundwater under the direct influence of
surface water as defined in s. NR 809.04 (40), in total or in part, shall
monitor at the same frequency as a like-sized municipal community water system,
as specified in par. (b). GWUDI public water systems shall begin monitoring at
this frequency beginning 6 months after the department determines that the
groundwater source is under the direct influence of surface water.
4. The water supplier for a transient
non-community water system serving a school shall sample for coliform bacteria
in each calendar quarter during which the public water system provides water to
the public, unless the department, on the basis of sub. (2m), determines that
more frequent monitoring is appropriate. Transient non-community systems
serving schools are not eligible for reduced monitoring under par. (dg) of this
section.
(de)
Annual site visits. Beginning no later than calendar year
2017, transient non-community systems on annual monitoring, including seasonal
systems, shall have an initial and recurring annual site visit by the
department that is equivalent to a Level 2 assessment or an annual voluntary
Level 2 assessment that meets the criteria in s. NR 809.313 (2) to remain on
annual monitoring. The periodic required sanitary survey may be used to meet
the requirement for an annual site visit for the year in which the sanitary
survey was completed. Transient non-community systems with little-to-no
distribution system may, at the discretion of the department, be exempt from
the annual site visit requirements in this section, and still remain on annual
monitoring.
(dg)
Criteria
for annual monitoring at transient non-community systems. Beginning
April 1, 2016, the department may reduce the monitoring frequency for a
well-operated transient non-community ground water system serving 1,000 persons
per day or fewer from quarterly routine monitoring to no less than annual
monitoring, if the transient non-community system demonstrates that it meets
the criteria for reduced monitoring in subds.
1. to 4., except for a transient
non-community system that has been on increased monitoring under the provisions
of sub. (2m). A transient non-community system on increased monitoring under
sub. (2m) shall meet the provisions of sub. (2m) (b) to go to quarterly
monitoring and shall meet the provisions of sub. (2m) (c) to go to annual
monitoring.
1. The transient
non-community system has a clean compliance history for a minimum of 12
months.
2. The most recent sanitary
survey shows that the transient non-community system is free of sanitary
defects or has corrected all identified sanitary defects, has a protected water
source, and meets approved construction standards.
3. The department has conducted an annual
site visit within the last 12 months and the water supplier has corrected all
identified sanitary defects. A Level 2 assessment that meets the criteria in s.
NR 809.313 (2) may be substituted for the department annual site
visit.
4. The public water system
is not a school.
(dr)
Seasonal system requirements.
1. Beginning April 1, 2016, all water
suppliers of seasonal systems shall demonstrate completion of a
department-approved start-up procedure, which may include a requirement for
start-up sampling prior to serving water to the public.
2. Seasonal systems shall be monitored every
month that they are in operation unless they meet the criteria in subd. 2. a.
to c. to be eligible for monitoring less frequently than monthly beginning
April 1, 2016, except as provided under par. (ar).
a. Seasonal systems that are monitored less
frequently than monthly shall have an approved sample siting plan that
designates the time period for monitoring based on site-specific considerations
(e.g., during periods of highest demand or highest vulnerability to
contamination). Water suppliers of seasonal systems shall collect compliance
samples during this time period.
b.
To be eligible for quarterly monitoring, seasonal systems shall meet the
criteria in sub. (2m) (b).
c. To be
eligible for annual monitoring, seasonal systems shall meet the criteria under
sub. (2m) (c).
3. The
department may exempt any seasonal system from some or all of the requirements
for seasonal systems if the entire distribution system remains pressurized
during the entire period that the seasonal system is not operating, except that
seasonal systems that are monitored less frequently than monthly shall be
monitored during the vulnerable period as designated by the
department.
(e)
Sample collection time intervals. Water suppliers for public
water systems shall collect samples at regular time intervals throughout the
month, except that for public water systems which use only groundwater and
serve 4,900 persons or fewer, may collect all required samples on a single day
if the samples are taken from different sites.
(eg)
Minimum required number of
samples after MCL violation or treatment technique trigger. Water
suppliers shall take at least the minimum number of required samples even if
the public water system has had an E. coli MCL violation or
has exceeded the coliform treatment technique triggers in s. NR 809.313.
(er)
Sampling in excess of
requirements. Water suppliers may conduct more compliance monitoring
than is required by this section to investigate potential problems in the
distribution system and use monitoring as a tool to assist in uncovering
problems. Water suppliers may take more than the minimum number of required
routine samples and shall include the results in calculating whether the
coliform treatment technique trigger in s. NR 809.313 has been exceeded only if
the samples are taken in accordance with the existing sample siting plan and
are representative of water throughout the distribution system.
(f)
Special purpose samples.
Special purpose samples such as those taken to determine whether disinfection
practices are sufficient following pipe placement, replacement or repair, may
not be used to determine whether the coliform treatment technique trigger has
been exceeded. Repeat samples taken pursuant to sub. (2) are not considered
special purpose samples, and shall be used to determine whether the coliform
treatment technique trigger has been exceeded.
(g)
Analyses required after turbidity
exceedances at selected systems. A water supplier for a public water
system that uses surface water or groundwater under the direct influence of
surface water as defined in s. NR 809.04 (40), and does not provide filtration
in compliance with s. NR 810.29, shall collect at least one sample in the
distribution system near the first service connection each day one or more
turbidity measurements of the source water obtained as specified in s. NR 810.38 (1) (c), exceeds 1 NTU. This sample shall be analyzed for the presence
of total coliforms. The water supplier shall collect this coliform sample
within 24 hours of the first exceedance unless the department determines that
the water supplier, for logistical reasons beyond their control, cannot have
the sample analyzed within 30 hours of collection. Results from this coliform
monitoring shall be used to determine whether the coliform treatment technique
trigger has been exceeded in s. NR 809.313.
(2) REPEAT MONITORING.
(a) If a routine sample is total
coliform-positive, the water supplier for a public water system shall collect a
set of repeat samples within 24 hours of being notified of the positive result.
The water supplier shall collect no fewer than 3 repeat samples for each total
coliform-positive sample found. The department may extend the 24-hour limit on
a case-by-case basis if the water supplier has a logistical problem that is
beyond its control in collecting the repeat samples within 24 hours. In the
case of an extension, the department shall specify how much time the water
supplier has to collect repeat samples. The department may not waive the
requirement for a water supplier to collect repeat samples in this paragraph or
pars. (b) to (c).
(b) Unless the
provisions of subds. 1. and 2. are met, the water supplier shall collect at
least one repeat sample from the sampling tap where the original total
coliform-positive sample was taken, and at least one repeat sample at a tap
within 5 service connections upstream and at least one repeat sample at a tap
within five service connections downstream of the original sampling site. If a
total coliform-positive sample is at the end of the distribution system, or one
service connection away from the end of the distribution system, the water
supplier shall take all required repeat samples. However, the department may
allow an alternative sampling location in lieu of the requirement to collect at
least one repeat sample upstream or downstream of the original sampling site.
Except as provided in subd. 2., public water systems required to conduct
triggered source water monitoring under s. NR 809.325 shall take ground water
source samples in addition to repeat samples required under this paragraph.
1. A water supplier may propose repeat
monitoring locations to the department that the water supplier believes to be
representative of a pathway for contamination of the distribution system. A
water supplier may elect to specify either alternative fixed locations or
criteria for selecting repeat sampling sites on a situational basis in a
standard operating procedure (SOP) in its sample siting plan. The water
supplier shall design its SOP to focus the repeat samples at locations that
best verify and determine the extent of potential contamination of the
distribution system area based on specific situations. The department may
modify the SOP or require alternative monitoring locations as needed.
2. A water supplier of a ground water system
serving 1,000 or fewer people may propose repeat sampling locations to the
department that differentiate potential source water and distribution system
contamination (e.g., by sampling at entry points to the distribution system). A
water supplier of a ground water system with a single well required to conduct
triggered source water monitoring may, with written department approval, take
one of the repeat samples at the monitoring location required for triggered
source water monitoring under s. NR 809.325 if the water supplier demonstrates
to the department's satisfaction that the sample siting plan remains
representative of water quality in the distribution system. If approved by the
department, the water supplier may use that dual purpose sample result to meet
the monitoring requirements in both s. NR 809.325 and this section.
a. If a dual purpose repeat sample taken at
the monitoring location required for triggered source water monitoring is
E. coli-positive, the public water system has violated the
E. coli MCL and shall also comply with s. NR 809.325 (2) (e).
If a water supplier takes more than one repeat sample at the monitoring
location required for triggered source water monitoring, the water supplier may
reduce the number of additional source water samples required under s. NR 809.325 (2) (e) by the number of repeat samples taken at that location that
were not E. coli-positive.
b. If a water supplier takes more than one
repeat sample at the monitoring location required for triggered source water
monitoring under s. NR 809.325 (2). and more than one repeat sample is
E. coli-positive, the public water system has violated the
E. coli MCL and shall comply with s. NR 809.327.
c. If all repeat samples taken at the
monitoring location required for triggered source water monitoring are
E. coli-negative and a repeat sample taken at a monitoring
location other than the one required for triggered source water monitoring is
E. coli-positive, the public water system has violated the
E. coli MCL, but is not required to comply with s. NR 809.325 (2) (e).
3. The
department may review, revise, and approve, as appropriate, repeat sampling
proposed by water suppliers under subds. 1. and 2. The water supplier shall
demonstrate that the sample siting plan remains representative of the water
quality in the distribution system. The department may determine that
monitoring at the entry point to the distribution system, especially at ground
water systems without disinfection is effective to differentiate between
potential source water and distribution system problems.
(c) Water suppliers at ground water systems
may use a repeat sample, taken at the source or all of the sources serving the
location of each routine positive sample, to meet the requirements of both this
paragraph and s. NR 809.325 (2) (d). In cases where more than one source serves
the location of the routine positive sample or samples, repeat samples shall be
taken from each of the sources to satisfy the requirements of this paragraph
and s. NR 809.325 (2) (d).
(d) The
water supplier shall collect all repeat samples on the same day, except that
the department may allow a water supplier for a public water system with a
single service connection to collect the required set of repeat samples over a
3-day period or to collect a larger volume repeat sample in one or more sample
containers of any size, as long as the total volume collected is at least 300
mL.
(e) If one or more repeat
samples in the set is total coliform-positive, the water supplier shall collect
an additional set of repeat samples in the manner specified in pars. (a) to
(d). The additional set of samples shall be collected within 24 hours after the
water supplier is notified of the positive result, unless the department
extends the limit as provided in par. (a). The water supplier shall repeat this
process until either total coliforms are not detected in one complete set of
repeat samples or the water supplier determines that the coliform treatment
technique trigger specified in s. NR 809.313 has been exceeded and the water
supplier notifies the department as specified in s. NR 809.80 (2). If a trigger
identified in s. NR 809.313 is exceeded as a result of a routine sample being
total coliform-positive, water suppliers are required to conduct only one round
of repeat monitoring for each total coliform-positive routine sample.
(f) Water suppliers collecting
samples on a quarterly or annual frequency shall conduct additional routine
monitoring the month following one or more total coliform-positive samples
regardless of whether the positive samples resulted in a Level 1 treatment
technique trigger. Water suppliers shall collect at least three routine samples
during the next month, after consultation with the department, except that the
department may waive this requirement if the conditions of subd. 1., 2., or 3.
are met. Water suppliers may either collect samples at regular time intervals
throughout the month or may collect all required routine samples on a single
day if samples are taken from different sites. Water suppliers shall use the
results of additional routine samples in coliform treatment technique trigger
calculations under s. NR 809.313 (1).
1. The
department may waive the requirement to collect 3 routine samples during the
next month the public water system provides water to the public if the
department performs a site visit before the end of the next month the public
water system provides water to the public. Although a sanitary survey need not
be performed, the site visit shall be sufficiently detailed to allow the
department to determine whether additional monitoring or any corrective action
is needed. The department may not approve an employee of the public water
system to perform this site visit, even if the employee is an agent approved by
the department to perform sanitary surveys.
2. The department may waive the requirement
to collect 3 routine samples during the next month the public water system
provides water to the public if the department has determined why the sample
was total coliform positive and establishes that the water supplier has
corrected the problem or will correct the problem before the end of the next
month the public water system serves water to the public. In this case, the
decision to waive the following month's additional monitoring requirement will
be documented in writing, signed by a qualified department official, and made
available to the public. The written documentation shall describe the specific
cause of the total coliform positive sample and what action the water supplier
has taken or will take to correct this problem.
3. The requirement to collect 3 routine
samples during the next month the public water system provides water to the
public shall not be waived solely on the grounds that all repeat samples are
total coliform-negative. The water supplier shall collect at least one routine
sample before the end of the next month the public water system serves water to
the public and use it to determine compliance with the treatment technique
trigger for total coliforms in s. NR 809.31, unless the department has
determined that the water supplier corrected the contamination problem before
the water supplier collected the set of repeat samples required in pars. (a) to
(e) and all repeat samples were total coliform negative.
(g) After a water supplier collects a routine
sample and before learning the results of the analysis of that sample, if the
water supplier collects another routine sample from within 5 adjacent service
connections of the initial sample, and the initial sample after analysis is
found to contain total coliforms, then the water supplier may count the
subsequent sample as a repeat sample instead of as a routine sample.
(h) Results of all routine and repeat samples
not invalidated by the department shall be included in determining whether any
coliform treatment technique triggers specified in s. NR 809.313 have been
exceeded. If any trigger has been exceeded, water suppliers shall complete
assessments as required in s. NR 809.313.
(2m) INCREASED MONITORING.
(a)
Increased monitoring requirements
for public water systems on quarterly or annual monitoring. Except as
specified in pars. (d) and (e), water suppliers at public water systems on
quarterly or annual monitoring that experience any of the events identified in
subds. 1. to 4. shall begin monthly monitoring the month following the event. A
water supplier at a public water system on annual monitoring that experiences
the event identified in subd. 5. shall begin quarterly monitoring the quarter
following the event. The water supplier shall continue monthly or quarterly
monitoring until the requirements in par. (b) for quarterly monitoring or par.
(c) for annual monitoring are met. A public water system on monthly monitoring
for reasons other than those identified in subds. 1. to 4. is not considered to
be on increased monitoring for the purposes of pars. (b) and (c).
1. The public water system triggers a Level 2
assessment or two Level 1 assessments under the provisions of s. NR 809.313 in
a rolling 12-month period.
2. The
public water system has an E. coli MCL violation.
3. The public water system has a coliform
treatment technique violation.
4.
The public water system has two coliform monitoring violations in a rolling
12-month period, or is a non-community public water system and has one coliform
monitoring violation and one Level 1 assessment under the provisions of s. NR 809.313 in a rolling 12-month period for a public water system on quarterly
monitoring.
5. The public water
system has one coliform monitoring violation for a public water system on
annual monitoring. For transient non-community public water systems, the
department may elect to not count monitoring violations under sub. (9) if the
missed sample is collected no later than the end of the monitoring period
following the monitoring period in which the sample was missed. The water
supplier shall collect the make-up sample in a different week than the routine
sample for that monitoring period and shall collect the sample as soon as
possible during the monitoring period, except that this is not allowed under
par. (c). This authority does not affect the provisions of sub. (9) and s. NR 809.312 (2).
(b)
Requirements for public water systems on increased monitoring to return
to quarterly monitoring. The department may reduce the monitoring
frequency for a public water system on monthly monitoring triggered under par.
(a) to quarterly monitoring if the public water system meets the criteria in
subds. 1. and 2.
1. Within the last 12
months, the public water system shall have a completed sanitary survey or a
site visit by the department or a voluntary Level 2 assessment by a party
approved by the department, be free of sanitary defects, and have a protected
water source.
2. The public water
system shall have a clean compliance history for a minimum of 12 months. For
transient non-community public water systems, the department may elect to not
count monitoring violations, as allowed under sub. (9), if the missed sample is
collected no later than the end of the monitoring period following the
monitoring period in which the sample was missed. The water supplier shall
collect the make-up sample in a different week than the routine sample for that
monitoring period and should collect the sample as soon as possible during the
monitoring period, except that this is not allowed under par. (c). This
authority does not affect the provisions of sub. (9) and s. NR 809.312 (2).
(c)
Requirements for systems on increased monitoring to qualify for annual
monitoring. The department may reduce the monitoring frequency for a
transient non-community public water system on increased monitoring under par.
(a) if the transient non-community public water system meets the criteria in
par. (d) and the criteria in subds. 1. and 2.
1. The department shall conduct an annual
site visit and the water supplier shall correct all identified sanitary
defects. The water supplier may substitute a voluntary Level 2 assessment
conducted by a party approved by the department in place of the department's
annual site visit in any given year.
2. The water supplier shall have in place or
adopt one or more additional enhancements to the water system barriers to
contamination in subds. 2. a. to 2. e.
a.
Cross connection control, as approved by the department.
b. Regular visits by a circuit rider approved
by the department.
c. Continuous
disinfection entering the distribution system and a residual in the
distribution system in accordance with criteria specified by the
department.
d. Demonstration of
maintenance of at least a 4-log removal or inactivation of viruses as provided
for under s. NR 809.327 (4).
e.
Other equivalent enhancements to public water system barriers to contamination
as approved by the department.
(d)
Allowance for transient
non-community water systems to monitor annually.The department may
allow water suppliers at transient non-community water systems to monitor
annually for total coliform and
E. coli following conditions
that would require increased monitoring under par. (a), provided the water
supplier meets the requirements of subd. 1. or 2.
1. For water systems that began operation and
conducted coliform monitoring prior to April 1, 2016, the water supplier shall
have done all of the following:
a. Completed
all required total coliform monitoring in the previous calendar year.
b. Received a sanitary survey within the
previous 5 years.
c. Corrected all
significant deficiencies or is following a department agreed upon schedule for
correcting all significant deficiencies.
d. Received a level 2 assessment within 30
days of any level 1 assessment trigger identified after April 1, 2016, and
corrected all sanitary defects or is following a department agreed upon
schedule for correcting all sanitary defects.
e. Completed all repeat sampling requirements
associated with any total coliform positive identified after April 1,
2016.
f. Had no E.
coli MCL exceedances in the previous 2 years.
2. For public water systems that began
operation or began coliform monitoring on or after April 1, 2016, the water
supplier shall meet all of the requirements of subd. 1 and shall have completed
at least one year of coliform monitoring at a frequency of no less than
quarterly.
(e)
Allowance for non-transient non-community water systems to monitor
quarterly.The department may allow a water supplier of a non-transient
non-community water system to monitor quarterly for total coliform and
E. coli following conditions that would require increased
monitoring under par. (a), provided the water supplier meets the same
requirements specified for transient non-community water systems in par. (d) 1.
a. to f.
(3)
INVALIDATION OF TOTAL COLIFORM SAMPLES.
(a) A
total coliform-positive sample invalidated under this subsection does not count
towards meeting the minimum monitoring requirements of this section.
(b) The department may invalidate a total
coliform-positive sample only if the conditions of subd. 1., 2. or 3. are met.
1. A certified laboratory establishes that
improper sample analysis caused the total coliform-positive result.
2. The department, on the basis of the
results of repeat samples collected as required by sub. (2) (a) to (e),
determines that the total coliform-positive sample resulted from a domestic or
other non-distribution system plumbing problem. A sample may not be invalidated
by the department on the basis of repeat sample results alone, unless all
repeat samples collected at the same tap as the original total
coliform-positive sample are also total coliform-positive, and all repeat
samples collected at a location other than the original tap are total
coliform-negative. The department will not invalidate a total coliform-positive
sample on the basis of repeat samples if all the repeat samples are total
coliform-negative, or if the public water system has only one service
connection.
3. The department has
substantial grounds to believe that a total coliform-positive result is due to
a circumstance or condition which does not reflect water quality in the
distribution system. In this case, the water supplier shall still collect all
repeat samples required, and shall use them to determine whether a coliform
treatment technique trigger in s. NR 809.313 has been exceeded. To invalidate a
total coliform-positive sample under this paragraph, the decision with the
rationale for the decision shall be documented in writing, approved by a
qualified department official and available to the public for inspection. The
document shall state the specific cause of the total coliform-positive sample,
and what action the water supplier has taken or will take, to correct this
problem. The department may not invalidate a total coliform-positive sample
solely on the grounds that all repeat samples are total
coliform-negative.
(c) A
laboratory shall invalidate a total coliform sample if the sample produces a
turbid culture in the absence of gas production using an analytical method
where gas formation is examined for, example, the Multiple Tube Fermentation
Technique, produces a turbid culture in the absence of an acid reaction in the
Presence-Absence Coliform Test, or exhibits confluent growth or produces
colonies too numerous to count with an analytical method using a membrane
filter, for example, Membrane Filter Technique, except that a laboratory shall
not invalidate a total coliform sample if total coliforms are detected. If a
laboratory invalidates a sample because of such interference, the water
supplier shall collect another sample from the same location as the original
sample within 24 hours of being notified of the interference problem, and have
it analyzed for the presence of total coliforms. The water supplier shall
continue to re-sample every 24 hours and have the samples analyzed until a
valid result is obtained. The department may waive the 24 hour time limit on a
case-by-case basis. Alternatively, the department may implement criteria for
waiving the 24-hour sampling time limit to use in lieu of case-by-case
extensions.
(4)
E. COLI testing.
(a) If any
routine or repeat sample is total coliform-positive, the water supplier shall
analyze that total coliform-positive culture medium to determine if E.
coli are present. If E. coli are present, the water
supplier shall notify the department by the end of the day when the water
supplier is notified of the test result, unless the water supplier is notified
of the result after normal department business hours, in which case the water
supplier shall notify the department before the end of the next business
day.
(b) The department may allow a
water supplier for a public water system, on a case-by-case basis, to forgo
E. coli testing on a total coliform-positive sample if that
water supplier assumes that the total coliform-positive sample is E.
coli positive. Accordingly, the water supplier shall notify the
department as specified in par. (a) and the provisions of s. NR 809.30 (2)
apply.
(5) GROUNDWATER
SYSTEM RAW WATER SAMPLING. In addition to sampling from the distribution
system, each water supplier for a public water system providing disinfection
shall obtain at least one sample every 3 months from each well prior to the
point of treatment. For public water systems which have more than one well in
the same location and utilizing the same aquifer, the supplier of water may
sample only one of the wells each time on an alternating basis. If a well has a
high potential for contamination, the department may, in individual cases,
require more frequent sampling.
(6)
SURFACE WATER SYSTEM RAW WATER SAMPLING. At surface water facilities, the
microbiological quality of the source water shall be monitored sufficiently to
maintain quality control of the treatment process. Water suppliers shall
establish a schedule for each plant, subject to review and modification by the
department.
Note: Generally, enumeration methods such as
membrane filter, numeric enzyme substrate, or 5 tube fermentation tests and
heterotrophic plate counts of the raw, settled and finished water on an
established schedule will be necessary to meet this requirement.
(7) HETEROTROPHIC PLATE COUNTS. At
all waterworks which have a potential for high total bacteria levels because of
the water quality, the method of treatment, chemical addition or other cause,
the department may require heterotrophic plate counts pursuant to an
established schedule. Analyses shall be conducted in accordance with the
analytical requirements in s. NR 809.311 (1), Table F.
(9) MONITORING VIOLATION.
(a) Failure to take every required routine or
additional routine sample in a compliance period is a monitoring
violation.
(b) Failure to analyze
for E. coli following a total coliform-positive routine sample
is a monitoring violation.
(10) REPORTING VIOLATION.
(a) Failure to submit a monitoring report or
completed assessment form after a water supplier properly conducts monitoring
or assessment in a timely manner is a reporting violation.
(b) Failure to notify the department
following an E. coli-positive sample as required by sub. (4)
in a timely manner is a reporting violation.
(c) Failure to submit certification of
completion of department-approved start-up procedure by a seasonal system is a
reporting violation.