Wisconsin Administrative Code
Department of Natural Resources
NR 600-699 - Environmental Protection - Hazardous Waste Management
Chapter NR 679 - Used Oil Management Standards
Subchapter G - Standards for Used Oil Burners Who Burn Off-Specification Used Oil for Energy Recovery
Section NR 679.63 - Rebuttable presumption for used oil

Universal Citation: WI Admin Code ยง NR 679.63

Current through August 26, 2024

(1) To ensure that used oil managed at a used oil burner facility is not hazardous waste under the rebuttable presumption of s. NR 679.10(2) (a) 2., a used oil burner shall determine whether the total halogen content of used oil managed at the facility is above or below 1,000 ppm.

(2) The used oil burner shall determine if the used oil contains above or below 1,000 ppm total halogens by doing any of the following:

(a) Testing the used oil.

(b) Applying knowledge of the halogen content of the used oil in light of the materials or processes used.

(c) If the used oil has been received from a processor or re-refiner regulated under subch. F, using information provided by the processor or re-refiner.

(3) Used oil containing greater than 1,000 ppm total halogens is presumed to be a hazardous waste because it has been mixed with halogenated hazardous waste listed in subch. D of ch. NR 661. The owner or operator may rebut this presumption by demonstrating that the used oil does not contain hazardous waste (for example, by showing that the used oil does not contain significant concentrations of halogenated hazardous constituents listed in ch. NR 661 Appendix VIII).

(a) The rebuttable presumption does not apply to metalworking oils or fluids containing chlorinated paraffins, if they are processed, through a tolling arrangement as described in s. NR 679.24(3), to reclaim metalworking oils or fluids. The presumption does apply to metalworking oils or fluids if the oils or fluids are recycled in any other manner, or are disposed.

(b) The rebuttable presumption does not apply to used oils contaminated with chlorofluorocarbons (CFCs) removed from refrigeration units where the CFCs are destined for reclamation. The rebuttable presumption does apply to used oils contaminated with CFCs that have been mixed with used oil from sources other than refrigeration units.

(4) Records of analyses conducted or information used to comply with subs. (1) to (3) shall be maintained by the burner for at least 3 years.

Disclaimer: These regulations may not be the most recent version. Wisconsin may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.