Current through August 26, 2024
(1) This section applies to the control of
air pollutant emissions from tanks for which s.
NR 665.1083(2) references the use of
this section for the air emission control.
(2) The owner or operator shall control air
pollutant emissions from each tank subject to this section according to one of
the following requirements, as applicable:
(a)
For a tank that manages hazardous waste that meets all of the following
conditions, control air pollutant emissions from the tank according to the Tank
Level 1 controls specified in sub. (3) or the Tank Level 2 controls specified
in sub. (4):
1. The hazardous waste in the
tank has a maximum organic vapor pressure which is less than the maximum
organic vapor pressure limit for the tank's design capacity category as
follows:
a. For a tank design capacity equal
to or greater than 151 m3, the maximum organic vapor
pressure limit for the tank is 5.2 kPa.
b. For a tank design capacity equal to or
greater than 75 m3 but less than 151
m3, the maximum organic vapor pressure limit for the
tank is 27.6 kPa.
c. For a tank
design capacity less than 75 m3, the maximum organic
vapor pressure limit for the tank is 76.6 kPa.
2. The hazardous waste in the tank is not
heated to a temperature that is greater than the temperature at which the
maximum organic vapor pressure of the hazardous waste is determined for the
purpose of complying with subd. 1.
3. The hazardous waste in the tank is not
treated using a waste stabilization process, as defined in s.
NR 665.1081.
(b) For a tank that manages hazardous waste
that does not meet all of the conditions in par. (a) 1. to 3., control air
pollutant emissions from the tank using Tank Level 2 controls according to sub.
(4). Examples of tanks required to use Tank Level 2 controls include a tank
used for a waste stabilization process, and a tank for which the hazardous
waste in the tank has a maximum organic vapor pressure that is equal to or
greater than the maximum organic vapor pressure limit for the tank's design
capacity category as specified in par. (a) 1.
(3) Owners and operators controlling air
pollutant emissions from a tank using Tank Level 1 controls shall meet all of
the following requirements:
(a) Determine the
maximum organic vapor pressure for a hazardous waste to be managed in the tank
using Tank Level 1 controls before the first time the hazardous waste is placed
in the tank. Determine the maximum organic vapor pressure using the procedures
in s.
NR 665.1084(3). Thereafter, perform a
new determination whenever changes to the hazardous waste managed in the tank
could potentially cause the maximum organic vapor pressure to increase to a
level that is equal to or greater than the maximum organic vapor pressure limit
for the tank design capacity category specified in sub. (2) (a) 1., as
applicable to the tank.
(b) Equip
the tank with a fixed roof designed to meet all of the following
specifications:
1. Design the fixed roof and
its closure devices to form a continuous barrier over the entire surface area
of the hazardous waste in the tank. The fixed roof may be a separate cover
installed on the tank (e.g., a removable cover mounted on an open-top tank) or
may be an integral part of the tank structural design (e.g., a horizontal
cylindrical tank equipped with a hatch).
2. Install the fixed roof in a manner such
that there are no visible cracks, holes, gaps or other open spaces between roof
section joints or between the interface of the roof edge and the tank
wall.
3. Each opening in the fixed
roof, and any manifold system associated with the fixed roof, shall be any of
the following:
a. Equipped with a closure
device designed to operate such that when the closure device is secured in the
closed position there are no visible cracks, holes, gaps or other open spaces
in the closure device or between the perimeter of the opening and the closure
device.
b. Connected by a
closed-vent system that is vented to a control device. The control device shall
remove or destroy organics in the vent stream, and shall be operating whenever
hazardous waste is managed in the tank, except as follows:
1) During periods it is necessary to provide
access to the tank for performing the activities of subd. 3. b. 2), venting of
the vapor headspace underneath the fixed roof to the control device is not
required, opening of closure devices is allowed and removal of the fixed roof
is allowed. After completing the activity, promptly secure the closure device
in the closed position or reinstall the cover, as applicable, and resume
operation of the control device.
2)
During periods of routine inspection, maintenance or other activities needed
for normal operations, and for the removal of accumulated sludge or other
residues from the bottom of the tank.
4. Make the fixed roof and its closure
devices of suitable materials that will minimize exposure of the hazardous
waste to the atmosphere, to the extent practical, and will maintain the
integrity of the fixed roof and closure devices throughout their intended
service life. Factors to consider when selecting the materials for and
designing the fixed roof and closure devices shall include organic vapor
permeability, the effects of any contact with the hazardous waste or its vapors
managed in the tank, the effects of outdoor exposure to wind, moisture and
sunlight and the operating practices used for the tank on which the fixed roof
is installed.
(c)
Whenever a hazardous waste is in the tank, install the fixed roof with each
closure device secured in the closed position except as follows:
1. Opening of closure devices or removal of
the fixed roof is allowed at the following times:
a. To provide access to the tank for
performing routine inspection, maintenance or other activities needed for
normal operations. Examples of those activities include those times when a
worker needs to open a port to sample the liquid in the tank, or when a worker
needs to open a hatch to maintain or repair equipment. After completing the
activity, promptly secure the closure device in the closed position or
reinstall the cover, as applicable, to the tank.
b. To remove accumulated sludge or other
residues from the bottom of the tank.
2. Opening of a spring-loaded pressure-vacuum
relief valve, conservation vent or similar type of pressure relief device which
vents to the atmosphere is allowed during normal operations for the purpose of
maintaining the tank internal pressure according to the tank design
specifications. Design the device to operate with no detectable organic
emissions when the device is secured in the closed position. Establish the
settings at which the device opens such that the device remains in the closed
position whenever the tank internal pressure is within the internal pressure
operating range determined by the owner or operator based on the tank
manufacturer recommendations, applicable rules, fire protection and prevention
codes, standard engineering codes and practices or other requirements for the
safe handling of flammable, ignitable, explosive, reactive or hazardous
materials. Examples of normal operating conditions that may require these
devices to open are during those times when the tank internal pressure exceeds
the internal pressure operating range for the tank as a result of loading
operations or diurnal ambient temperature fluctuations.
3. Opening of a safety device, as defined in
s.
NR 665.1081, is allowed at any time conditions require
doing so to avoid an unsafe condition.
(d) Inspect the air emission control
equipment according to all of the following requirements:
1. Visually inspect the fixed roof and its
closure devices to check for defects that could result in air pollutant
emissions. Defects include, but are not limited to, visible cracks, holes or
gaps in the roof sections or between the roof and the tank wall, broken,
cracked or otherwise damaged seals or gaskets on closure devices and broken or
missing hatches, access covers, caps or other closure devices.
2. Perform an initial inspection of the fixed
roof and its closure devices on or before the date that the tank becomes
subject to this section. Thereafter, perform the inspections at least once
every year except under the special conditions provided for in sub.
(12).
3. In the event that a defect
is detected, repair the defect according to sub. (11).
4. Maintain a record of the inspection
according to s.
NR 665.1090(2).
(4) Owners and operators
controlling air pollutant emissions from a tank using Tank Level 2 controls
shall use one of the following tanks:
(a) A
fixed-roof tank equipped with an internal floating roof according to sub.
(5).
(b) A tank equipped with an
external floating roof according to sub. (6).
(c) A tank vented through a closed-vent
system to a control device according to sub. (7).
(d) A pressure tank designed and operated
according to sub. (8).
(e) A tank
located inside an enclosure that is vented through a closed-vent system to an
enclosed combustion control device according to sub. (9).
(5) The owner or operator who controls air
pollutant emissions from a tank using a fixed-roof with an internal floating
roof shall meet pars. (a) to (c).
(a) Equip
the tank with a fixed roof and an internal floating roof according to all of
the following requirements:
1. Design the
internal floating roof to float on the liquid surface except when the floating
roof must be supported by the leg supports.
2. Equip the internal floating roof with a
continuous seal between the wall of the tank and the floating roof edge that
meets any of the following requirements:
a. A
single continuous seal that is either a liquid-mounted seal or a metallic shoe
seal, as defined in s.
NR 665.1081.
b. Two continuous seals mounted one above the
other. The lower seal may be a vapor-mounted seal.
3. The internal floating roof shall meet all
of the following specifications:
a. Each
opening in a non-contact internal floating roof, except for automatic bleeder
vents (vacuum breaker vents) and the rim space vents, provides a projection
below the liquid surface.
b. Each
opening in the internal floating roof is equipped with a gasketed cover or a
gasketed lid except for leg sleeves, automatic bleeder vents, rim space vents,
column wells, ladder wells, sample wells and stub drains.
c. Each penetration of the internal floating
roof for the purpose of sampling has a slit fabric cover that covers at least
90 percent of the opening.
d. Each
automatic bleeder vent and rim space vent is gasketed.
e. Each penetration of the internal floating
roof that allows for passage of a ladder has a gasketed sliding
cover.
f. Each penetration of the
internal floating roof that allows for passage of a column supporting the fixed
roof has a flexible fabric sleeve seal or a gasketed sliding cover.
(b) Operate the tank
according to all of the following requirements:
1. When the floating roof is resting on the
leg supports, the process of filling, emptying or refilling shall be continuous
and shall be completed as soon as practical.
2. Set automatic bleeder vents to closed at
all times when the roof is floating, except when the roof is being floated off
or is being landed on the leg supports.
3. Prior to filling the tank, bolt or fasten
closed (i.e., no visible gaps) each cover, access hatch, gauge float well or
lid on any opening in the internal floating roof. Set rim space vents to open
only when the internal floating roof is not floating or when the pressure
beneath the rim exceeds the manufacturer's recommended setting.
(c) Inspect the internal floating
roof according to all of the following requirements:
1. Visually inspect the floating roof and its
closure devices to check for defects that could result in air pollutant
emissions. Defects include, but are not limited to, the internal floating roof
is not floating on the surface of the liquid inside the tank, liquid has
accumulated on top of the internal floating roof, any portion of the roof seals
have detached from the roof rim, holes, tears or other openings are visible in
the seal fabric, the gaskets no longer close off the hazardous waste surface
from the atmosphere or the slotted membrane has more than 10 percent open
area.
2. Inspect the internal
floating roof components as follows, except as provided in subd. 3.:
a. Visually inspect the internal floating
roof components through openings on the fixed-roof (e.g., manholes and roof
hatches) at least once every 12 months after initial fill.
b. Visually inspect the internal floating
roof, primary seal, secondary seal (if one is in service), gaskets, slotted
membranes and sleeve seals (if any) each time the tank is emptied and degassed
and at least every 10 years.
3. As an alternative to performing the
inspections in subd. 2. for an internal floating roof equipped with 2
continuous seals mounted one above the other, visually inspect the internal
floating roof, primary and secondary seals, gaskets, slotted membranes and
sleeve seals (if any) each time the tank is emptied and degassed and at least
every 5 years.
4. Prior to each
inspection required by subd. 2. or 3., notify the department in advance of each
inspection to provide the department with the opportunity to have an observer
present during the inspection. Notify the department of the date and location
of the inspection as follows:
a. Prior to each
visual inspection of an internal floating roof in a tank that has been emptied
and degassed, prepare and send written notification so that the department
receives it at least 30 calendar days before refilling the tank, except when an
inspection is not planned as provided for in subd. 4. b.
b. When a visual inspection is not planned
and the owner or operator could not have known about the inspection 30 calendar
days before refilling the tank, notify the department as soon as possible, but
no later than 7 calendar days before refilling the tank. Make this notification
by telephone and immediately follow with a written explanation for why the
inspection is unplanned. Alternatively, send written notification, including
the explanation for the unplanned inspection, so that the department receives
it at least 7 calendar days before refilling the tank.
5. In the event that a defect is detected,
repair the defect according to sub. (11).
6. Maintain a record of the inspection
according to the requirements in s.
NR 665.1090(2).
(d) Safety devices, as defined in s.
NR 665.1081, may be installed and operated as necessary
on any tank complying with this subsection.
(6) The owner or operator who controls air
pollutant emissions from a tank using an external floating roof shall meet
pars. (a) to (c).
(a) Design the external
floating roof according to all of the following requirements:
1. Design the external floating roof to float
on the liquid surface except when the floating roof must be supported by the
leg supports.
2. Equip the floating
roof with 2 continuous seals, one above the other, between the wall of the tank
and the roof edge. The lower seal is referred to as the primary seal, and the
upper seal is referred to as the secondary seal.
a. The primary seal shall be a liquid-mounted
seal or a metallic shoe seal, as defined in s.
NR 665.1081. The total area of the gaps between the tank
wall and the primary seal may not exceed 212 square centimeters
(cm2) per meter of tank diameter, and the width of
any portion of these gaps may not exceed 3.8 centimeters (cm). If a metallic
shoe seal is used for the primary seal, design the metallic shoe seal so that
one end extends into the liquid in the tank and the other end extends a
vertical distance of at least 61 centimeters above the liquid
surface.
b. Mount the secondary
seal above the primary seal and cover the annular space between the floating
roof and the wall of the tank. The total area of the gaps between the tank wall
and the secondary seal may not exceed 21.2 square centimeters
(cm2) per meter of tank diameter, and the width of
any portion of these gaps may not exceed 1.3 centimeters (cm).
3. The external floating roof
shall meet all of the following specifications:
a. Except for automatic bleeder vents (vacuum
breaker vents) and rim space vents, each opening in a non-contact external
floating roof shall project below the liquid surface.
b. Except for automatic bleeder vents, rim
space vents, roof drains and leg sleeves, equip each opening in the roof with a
gasketed cover, seal or lid.
c.
Equip each access hatch and each gauge float well with a cover designed to be
bolted or fastened when the cover is secured in the closed position.
d. Equip each automatic bleeder vent and each
rim space vent with a gasket.
e.
Equip each roof drain that empties into the liquid managed in the tank with a
slotted membrane fabric cover that covers at least 90 percent of the area of
the opening.
f. Equip each
unslotted and slotted guide pole well with a gasketed sliding cover or a
flexible fabric sleeve seal.
g.
Equip each unslotted guide pole with a gasketed cap on the end of the
pole.
h. Equip each slotted guide
pole with a gasketed float or other device which closes off the liquid surface
from the atmosphere.
i. Equip each
gauge hatch and each sample well with a gasketed cover.
(b) Operate the tank according to
all of the following requirements:
1. When the
floating roof is resting on the leg supports, the process of filling, emptying
or refilling shall be continuous and shall be completed as soon as
practical.
2. Except for automatic
bleeder vents, rim space vents, roof drains and leg sleeves, secure and
maintain each opening in the roof in a closed position at all times except when
the closure device must be open for access.
3. Bolt or fasten covers on each access hatch
and each gauge float well when secured in the closed position.
4. Set closed automatic bleeder vents at all
times when the roof is floating, except when the roof is being floated off or
is being landed on the leg supports.
5. Set to open rim space vents only at those
times that the roof is being floated off the roof leg supports or when the
pressure beneath the rim seal exceeds the manufacturer's recommended
setting.
6. Secure the cap on the
end of each unslotted guide pole in the closed position at all times except
when measuring the level of the liquid in the tank or collecting samples of the
liquid.
7. Secure the cover on each
gauge hatch or sample well in the closed position at all times except when the
hatch or well must be opened for access.
8. Both the primary seal and the secondary
seal shall completely cover the annular space between the external floating
roof and the wall of the tank in a continuous fashion except during
inspections.
(c) Inspect
the external floating roof according to all of the following procedures:
1. Measure the external floating roof seal
gaps according to all of the following requirements:
a. Perform measurements of gaps between the
tank wall and the primary seal within 60 calendar days after initial operation
of the tank following installation of the floating roof and, thereafter, at
least once every 5 years.
b.
Perform measurements of gaps between the tank wall and the secondary seal
within 60 calendar days after initial operation of the tank following
installation of the floating roof and, thereafter, at least once every
year.
c. If a tank ceases to hold
hazardous waste for a period of one year or more, subsequent introduction of
hazardous waste into the tank is an initial operation for the purposes of subd.
1. a. and b.
d. Determine the
total surface area of gaps in the primary seal and in the secondary seal
individually using the following procedure:
1)
Perform the seal gap measurements at one or more floating roof levels when the
roof is floating off the roof supports.
2) Measure seal gaps, if any, around the
entire perimeter of the floating roof in each place where a 0.32-centimeter
(cm) diameter uniform probe passes freely (without forcing or binding against
the seal) between the seal and the wall of the tank and measure the
circumferential distance of each location.
3) For a seal gap measured under this
paragraph, determine the gap surface area using probes of various widths to
measure accurately the actual distance from the tank wall to the seal and
multiplying each width by its respective circumferential distance.
4) Calculate the total gap area by adding the
gap surface areas determined for each identified gap location for the primary
seal and the secondary seal individually, and then dividing the sum for each
seal type by the nominal diameter of the tank. Then compare these total gap
areas per unit of tank diameter for the primary seal and secondary seal to the
respective standards for the seal type in par. (a) 2.
e. In the event that the seal gap
measurements do not conform to the specifications in par. (a) 2., repair the
defect according to sub. (11).
f.
Maintain a record of the inspection according to s.
NR 665.1090(2).
2. Visually inspect the external floating
roof according to all of the following requirements:
a. Visually inspect the floating roof and its
closure devices to check for defects that could result in air pollutant
emissions. Defects include, but are not limited to, holes, tears or other
openings in the rim seal or seal fabric of the floating roof, a rim seal
detached from the floating roof, all or a portion of the floating roof deck
being submerged below the surface of the liquid in the tank, broken, cracked or
otherwise damaged seals or gaskets on closure devices and broken or missing
hatches, access covers, caps or other closure devices.
b. Perform an initial inspection of the
external floating roof and its closure devices on or before the date that the
tank becomes subject to this section. Thereafter, perform the inspections at
least once every year except for the special conditions provided for in sub.
(12).
c. In the event that a defect
is detected, repair the defect according to sub. (11).
d. Maintain a record of the inspection
according to s.
NR 665.1090(2).
3. Prior to each inspection required by subd.
1. or 2., notify the department in advance of each inspection to provide the
department with the opportunity to have an observer present during the
inspection. Notify the department of the date and location of the inspection as
follows:
a. Prior to each inspection to
measure external floating roof seal gaps as required under subd. 1., prepare
and send written notification so that the department receives it at least 30
calendar days before the date the measurements are scheduled to be
performed.
b. Prior to each visual
inspection of an external floating roof in a tank that has been emptied and
degassed, prepare and send written notification so that the department receives
it at least 30 calendar days before refilling the tank except when an
inspection is not planned as provided for in subd. 3. c.
c. When a visual inspection is not planned
and the owner or operator could not have known about the inspection 30 calendar
days before refilling the tank, notify the department as soon as possible, but
no later than 7 calendar days before refilling the tank. This notification may
be made by telephone and immediately followed by a written explanation for why
the inspection is unplanned. Alternatively, written notification, including the
explanation for the unplanned inspection, may be sent so that the department
receives it at least 7 calendar days before refilling the tank.
(d) Safety devices, as
defined in s.
NR 665.1081, may be installed and operated as necessary
on any tank complying with this subsection.
(7) The owner or operator who controls air
pollutant emissions from a tank by venting the tank to a control device shall
meet all of the following requirements:
(a)
Cover the tank with a fixed roof and vent the tank directly through a
closed-vent system to a control device according to all of the following
requirements:
1. Design the fixed roof and its
closure devices to form a continuous barrier over the entire surface area of
the liquid in the tank.
2. Equip
each opening in the fixed roof not vented to the control device with a closure
device. If the pressure in the vapor headspace underneath the fixed roof is
less than atmospheric pressure when the control device is operating, design the
closure devices to operate such that when the closure device is secured in the
closed position there are no visible cracks, holes, gaps or other open spaces
in the closure device or between the perimeter of the cover opening and the
closure device. If the pressure in the vapor headspace underneath the fixed
roof is equal to or greater than atmospheric pressure when the control device
is operating, design the closure device to operate with no detectable organic
emissions.
3. Make the fixed roof
and its closure devices of suitable materials that will minimize exposure of
the hazardous waste to the atmosphere, to the extent practical, and will
maintain the integrity of the fixed roof and closure devices throughout their
intended service life. Factors to consider when selecting the materials for and
designing the fixed roof and closure devices shall include organic vapor
permeability, the effects of any contact with the liquid and its vapor managed
in the tank, the effects of outdoor exposure to wind, moisture and sunlight and
the operating practices used for the tank on which the fixed roof is
installed.
4. Design and operate
the closed-vent system and control device according to s.
NR 665.1088.
(b) Whenever a hazardous waste is in the
tank, install the fixed roof with each closure device secured in the closed
position and the vapor headspace underneath the fixed roof vented to the
control device except as follows:
1. Venting
to the control device is not required, and opening of closure devices or
removal of the fixed roof is allowed at the following times:
a. To provide access to the tank for
performing routine inspection, maintenance or other activities needed for
normal operations. Examples of those activities include those times when a
worker needs to open a port to sample liquid in the tank or when a worker needs
to open a hatch to maintain or repair equipment. After completing the activity,
promptly secure the closure device in the closed position or reinstall the
cover, as applicable, to the tank.
b. To remove accumulated sludge or other
residues from the bottom of the tank.
2. Opening of a safety device, as defined in
s.
NR 665.1081, is allowed at any time conditions require
doing so to avoid an unsafe condition.
(c) Inspect and monitor the air emission
control equipment according to all of the following procedures:
1. Visually inspect the fixed roof and its
closure devices to check for defects that could result in air pollutant
emissions. Defects include, but are not limited to, visible cracks, holes or
gaps in the roof sections or between the roof and the tank wall, broken,
cracked or otherwise damaged seals or gaskets on closure devices and broken or
missing hatches, access covers, caps or other closure devices.
2. Inspect and monitor the closed-vent system
and control device according to the procedures in s.
NR 665.1088.
3. Perform an initial inspection of the air
emission control equipment on or before the date that the tank becomes subject
to this section. Thereafter, perform the inspections at least once every year
except for the special conditions provided for in sub. (12).
4. In the event that a defect is detected,
repair the defect according to sub. (11).
5. Maintain a record of the inspection
according to s.
NR 665.1090(2).
(8) The owner or operator who
controls air pollutant emissions by using a pressure tank shall meet all of the
following requirements.
(a) Design the tank to
not vent to the atmosphere as a result of compression of the vapor headspace in
the tank during filling of the tank to its design capacity.
(b) Equip all tank openings with closure
devices designed to operate with no detectable organic emissions determined
using the procedure in s.
NR 665.1084(4).
(c) Whenever hazardous waste is in the tank,
operate the tank as a closed system that does not vent to the atmosphere except
under any of the following conditions:
1. At
those times when opening of a safety device, as defined in s.
NR 665.1081, is required to avoid an unsafe
condition.
2. At those times when
purging of inerts from the tank is required and the purge stream is routed to a
closed-vent system and control device designed and operated according to s.
NR 665.1088.
(9) The owner or operator who controls air
pollutant emissions by using an enclosure vented through a closed-vent system
to an enclosed combustion control device shall meet all of the following
requirements:
(a) Locate the tank inside an
enclosure. Design and operate the enclosure according to the criteria for a
permanent total enclosure in Method 204-"Criteria for and Verification of a
Permanent or Temporary Total Enclosure" of appendix M of 40 CFR part 51, incorporated by reference in s.
NR 660.11. The enclosure may have permanent or temporary
openings to allow worker access; passage of material into or out of the
enclosure by conveyor, vehicles or other mechanical means; entry of permanent
mechanical or electrical equipment or direct airflow into the enclosure.
Perform the verification procedure for the enclosure in Section 8 of Method 204
initially when the enclosure is first installed and, thereafter,
annually.
(b) Vent the enclosure
through a closed-vent system to an enclosed combustion control device that is
designed and operated according to the standards for a vapor incinerator,
boiler or process heater in s.
NR 665.1088.
(c) Safety devices, as defined in s.
NR 665.1081, may be installed and operated as necessary
on any enclosure, closed-vent system or control device used to comply with
pars. (a) and (b).
(d) Inspect and
monitor the closed-vent system and control device as specified in s.
NR 665.1088.
(10) The owner or operator shall transfer
hazardous waste to a tank subject to this section according to all of the
following requirements:
(a) Except as provided
in par. (b), transfer hazardous waste to the tank from another tank subject to
this section or from a surface impoundment subject to s.
NR 665.1086 using continuous hard-piping or another
closed system that does not allow exposure of the hazardous waste to the
atmosphere. For the purpose of complying with this paragraph, an individual
drain system is a closed system when it meets 40 CFR part 63, subpart
RR-National Emission Standards for Individual Drain Systems.
(b) Paragraph (a) does not apply when
transferring a hazardous waste to the tank under any of the following
conditions:
1. The hazardous waste meets the
average VO concentration conditions in s.
NR 665.1083(3)
(a) at the point of waste
origination.
2. The hazardous waste
has been treated by an organic destruction or removal process to meet s.
NR 665.1083(3)
(b).
3. The hazardous waste meets s.
NR 665.1083(3)
(d).
(11) The owner or operator shall repair each
defect detected during an inspection performed according to sub. (3) (d), (5)
(c), (6) (c) or (7) (c) as follows:
(a) Make
first efforts at repair of the defect no later than 5 calendar days after
detection, and complete the repair as soon as possible but no later than 45
calendar days after detection except as provided in par. (b).
(b) Repair of a defect may be delayed beyond
45 calendar days if the owner or operator determines that repair of the defect
requires emptying or temporary removal from service of the tank and no
alternative tank capacity is available at the site to accept the hazardous
waste normally managed in the tank. In this case, repair the defect the next
time the process or unit that is generating the hazardous waste managed in the
tank stops operation. Complete repair of the defect before the process or unit
resumes operation.
(12)
Following the initial inspection and monitoring of the cover as required by the
applicable provisions of this subchapter, subsequent inspection and monitoring
may be performed at intervals longer than one year under the following special
conditions:
(a) In the case when inspecting
or monitoring the cover would expose a worker to dangerous, hazardous or other
unsafe conditions, the owner or operator may designate a cover as an "unsafe to
inspect and monitor cover" and comply with all of the following requirements:
1. Prepare a written explanation for the
cover stating the reasons why the cover is unsafe to visually inspect or to
monitor, if required.
2. Develop
and implement a written plan and schedule to inspect and monitor the cover,
using the procedures specified in the applicable section of this subchapter, as
frequently as practicable during those times when a worker can safely access
the cover.
(b) In the
case when a tank is buried partially or entirely underground, inspect and
monitor, as required by the applicable provisions of this section, only those
portions of the tank cover and those connections to the tank (e.g., fill ports,
access hatches, gauge wells, etc.) that are located on or above the ground
surface.