Current through August 26, 2024
(1)
(a) Monitor each pump in light liquid service
monthly to detect leaks by the methods specified in s.
NR 664.1063(2), except as provided in
subs. (4) to (6).
(b) Check each
pump in light liquid service by visual inspection each calendar week for
indications of liquids dripping from the pump seal.
(2)
(a) If
an instrument reading of 10,000 ppm or greater is measured, a leak is
detected.
(b) If there are
indications of liquids dripping from the pump seal, a leak is
detected.
(3)
(a) When a leak is detected, repair it as
soon as practicable, but not later than 15 calendar days after it is detected,
except as provided in s.
NR 664.1059.
(b) Make a first attempt at repair (e.g.,
tightening the packing gland) no later than 5 calendar days after each leak is
detected.
(4) Each pump
equipped with a dual mechanical seal system that includes a barrier fluid
system is exempt from sub. (1), provided all of the following requirements are
met:
(a) Each dual mechanical seal system
shall be one of the following:
1. Operated
with the barrier fluid at a pressure that is at all times greater than the pump
stuffing box pressure.
2. Equipped
with a barrier fluid degassing reservoir that is connected by a closed-vent
system to a control device that complies with s.
NR 664.1060.
3. Equipped with a system that purges the
barrier fluid into a hazardous waste stream with no detectable emissions to the
atmosphere.
(b) The
barrier fluid system may not be a hazardous waste with organic concentrations
10% or greater by weight.
(c) Equip
each barrier fluid system with a sensor that will detect failure of the seal
system, the barrier fluid system or both.
(d) Check each pump by visual inspection,
each calendar week, for indications of liquids dripping from the pump
seals.
(e)
1. Check each sensor as described in par. (c)
daily, or equip it with an audible alarm and check the alarm monthly to ensure
that it is functioning properly.
2.
Determine, based on design considerations and operating experience, a criterion
that indicates failure of the seal system, the barrier fluid system or
both.
(f)
1. If there are indications of liquids
dripping from the pump seal or the sensor indicates failure of the seal system,
the barrier fluid system or both based on the criterion determined in par. (e)
2., a leak is detected.
2. When a
leak is detected, repair it as soon as practicable, but not later than 15
calendar days after it is detected, except as provided in s.
NR 664.1059.
3. Make a first attempt at repair (e.g.,
relapping the seal) no later than 5 calendar days after each leak is
detected.
(5)
Any pump that is designated, as described in s.
NR 664.1064(7)
(b), for no detectable emissions, as
indicated by an instrument reading of less than 500 ppm above background, is
exempt from subs. (1), (3) and (4) if the pump meets all of the following
requirements:
(a) It has no externally
actuated shaft penetrating the pump housing.
(b) It operates with no detectable emissions
as indicated by an instrument reading of less than 500 ppm above background
measured by the methods specified in s.
NR 664.1063(3).
(c) It is tested for compliance with par. (b)
initially upon designation, annually and at other times requested by the
department.
(6) If any
pump is equipped with a closed-vent system capable of capturing and
transporting any leakage from the seal or seals to a control device that
complies with s.
NR 664.1060, it is exempt from subs. (1) to (5).