(1) WHAT ARE MY
MONITORING REQUIREMENTS?
(a) For each capture
system subject to an operating limit in s.
NR 463.23(1) (b) 1., you shall install,
operate and maintain a CPMS according to the requirements in sub. (2) (a) and
both of the following requirements, as applicable:
1. If you use a flow measurement device to
monitor the operating limit parameter, you shall at all times monitor the
hourly average rate.
Note: For example, the hourly average actual volumetric
flow rate through each separately ducted hood or the average hourly total
volumetric flow rate at the inlet to the control device.
2. For dampers that are not manually set and
remain in the same position, you shall make a visual check at least once every
24 hours to verify that each damper for the capture system is in the same
position as during the initial performance test. Dampers that are manually set
and remain in the same position are exempt from the requirement to install and
operate a CPMS.
(b) For
each negative pressure baghouse or positive pressure baghouse equipped with a
stack that is applied to meet any PM or total metal HAP emissions limitation in
this subchapter, you shall at all times monitor the relative change in PM
loadings using a bag leak detection system according to the requirements in
sub. (2) (b) and do all of the following:
1.
Monitor the pressure drop across each baghouse cell each day to ensure pressure
drop is within the normal operating range identified in the manual.
2. Confirm that dust is being removed from
hoppers through weekly visual inspections or other means of ensuring the proper
functioning of removal mechanisms.
3. Check the compressed air supply for
pulse-jet baghouses each day.
4.
Monitor cleaning cycles to ensure proper operation using an appropriate
methodology.
5. Check bag cleaning
mechanisms for proper functioning through monthly visual inspection or
equivalent means.
6. Make monthly
visual checks of bag tension on reverse air and shaker-type baghouses to ensure
that bags are not kinked, kneed or bent, or lying on their sides. You do not
have to make this check for shaker-type baghouses using self-tensioning,
spring-loaded, devices.
7. Confirm
the physical integrity of the baghouse through quarterly visual inspections of
the baghouse interior for air leaks.
8. Inspect fans for wear, material buildup
and corrosion through quarterly visual inspections, vibration detectors or
equivalent means.
(c)
For each wet scrubber subject to the operating limits in s.
NR 463.23(1) (b) 2., you shall at all
times monitor the 3-hour average pressure drop and scrubber water flow rate
using CPMS according to the requirements in sub. (2) (c).
(d) For each combustion device subject to the
operating limit in s.
NR 463.23(1) (b) 3., you shall at all
times monitor the 15-minute average combustion zone temperature using a CPMS
according to the requirements of sub. (2) (d).
(e) For each combustion device subject to the
operating limit in s.
NR 463.23(1) (b) 4., you shall at all
times monitor the 3-hour average combustion zone temperature using CPMS
according to the requirements in sub. (2) (d).
(f) For each wet acid scrubber subject to the
operating limits in s.
NR 463.23(1) (b) 5., you shall do both
of the following at all times:
1. Monitor the
3-hour average scrubbing liquid flow rate using CPMS according to the
requirements of sub. (2) (e) 1.
2.
Monitor the 3-hour average pH of the scrubber blowdown using CPMS according to
the requirements in sub. (2) (e) 1., or measure and record the pH of the
scrubber blowdown once per production cycle using a pH probe and meter
according to the requirements in sub. (2) (e) 2.
(g) For one or more automated conveyor and
pallet cooling lines and automated shakeout lines at a new iron and steel
foundry subject to the VOHAP emissions limit in s.
NR 463.23(1) (a) 10., you shall at all
times monitor the 3-hour average VOHAP concentration using a CEMS according to
the requirements of sub. (2) (g).
(2) WHAT ARE THE INSTALLATION, OPERATION AND
MAINTENANCE REQUIREMENTS FOR MY MONITORS?
(a)
For each capture system subject to an operating limit in s.
NR 463.23(1) (b) 1., you shall install,
operate and maintain each CPMS according to the following requirements, as
applicable:
1. If you use a flow measurement
device to monitor an operating limit parameter for a capture system, you shall
do all of the following:
a. Locate the flow
sensor and other necessary equipment, such as straightening vanes, in a
position that provides a representative flow and that reduces swirling flow or
abnormal velocity distributions due to upstream and downstream
disturbances.
b. Use a flow sensor
with a minimum measurement sensitivity of 2% of the flow rate.
c. Conduct a flow sensor calibration check at
least semiannually.
d. At least
monthly, inspect all components for integrity, all electrical connections for
continuity and all mechanical connections for leakage.
e. Record the results of each inspection,
calibration and validation check required under this subdivision.
2. If you use a pressure
measurement device to monitor the operating limit parameter for a capture
system, you shall do all of the following:
a.
Locate the pressure sensors in, or as close as possible, to a position that
provides a representative measurement of the pressure and that minimizes or
eliminates pulsating pressure, vibration, and internal and external
corrosion.
b. Use a gauge with a
minimum measurement sensitivity of 0.5 inch of water or a transducer with a
minimum measurement sensitivity of one percent of the pressure range.
c. Check the pressure tap for blockage or
plugging daily.
d. Using a
manometer, check gauge calibration quarterly and transducer calibration
monthly.
e. Conduct calibration
checks any time the sensor exceeds the manufacturer's specified maximum
operating pressure range or install a new pressure sensor.
f. At least monthly, inspect all components
for integrity, all electrical connections for continuity and all mechanical
connections for leakage.
g. Record
the results of each inspection, calibration and validation check required under
this subdivision.
(b) You shall install, operate and maintain a
bag leak detection system according to all of the following requirements:
1. The system shall be certified by the
manufacturer to be capable of detecting emissions of particulate matter at
concentrations of 10 milligrams per actual cubic meter (0.0044 grains per
actual cubic foot) or less.
2. The
bag leak detection system sensor shall provide output of relative particulate
matter loadings, and the owner or operator shall continuously record the output
from the bag leak detection system using electronic or other means such as a
strip chart recorder or a data logger.
3. The system shall be equipped with an alarm
that will sound when an increase in relative particulate loadings is detected
over the alarm set point established in the operation and maintenance plan. The
alarm shall be located such that it can be heard by the appropriate plant
personnel.
4. The initial
adjustment of the system shall, at a minimum, consist of establishing the
baseline output by adjusting the sensitivity or range and the averaging period
of the device and establishing the alarm set points and the alarm delay time,
if applicable.
5. Following the
initial adjustment, the sensitivity or range, averaging period, alarm set point
or alarm delay time may not be adjusted without approval from the department.
Except, once per quarter, you may adjust the sensitivity of the bag leak
detection system to account for seasonal effects, including temperature and
humidity, according to the procedures in the operation and maintenance plan
required by s.
NR 463.23(3) (b).
6. For negative pressure induced air
baghouses and positive pressure baghouses that are discharged to the atmosphere
through a stack, the bag leak detector sensor shall be installed downstream of
the baghouse and upstream of any wet scrubber.
7. Where multiple detectors are required, the
system's instrumentation and alarm may be shared among detectors.
(c) For each wet scrubber subject
to the operating limits in s.
NR 463.23(1) (b) 2., you shall install
and maintain CPMS to measure and record the pressure drop and scrubber water
flow rate according to the requirements in subds. 1. and 2.:
1. For each CPMS for pressure drop, you shall
do all of the following:
a. Locate the
pressure sensor in, or as close as possible to, a position that provides a
representative measurement of the pressure drop and that minimizes or
eliminates pulsating pressure, vibration and internal and external
corrosion.
b. Use a gauge with a
minimum measurement sensitivity of 0.5 inch of water or a transducer with a
minimum measurement sensitivity of one percent of the pressure range.
c. Check the pressure tap for blockage or
plugging daily.
d. Using a
manometer, check gauge calibration quarterly and transducer calibration
monthly.
e. Conduct calibration
checks any time the sensor exceeds the manufacturer's specified maximum
operating pressure range or install a new pressure sensor.
f. At least monthly, inspect all components
for integrity, all electrical connections for continuity and all mechanical
connections for leakage.
2. For each CPMS for scrubber liquid flow
rate, you shall do all of the following:
a.
Locate the flow sensor and other necessary equipment in a position that
provides a representative flow and that reduces swirling flow or abnormal
velocity distributions due to upstream and downstream disturbances.
b. Use a flow sensor with a minimum
measurement sensitivity of 2% of the flow rate.
c. Conduct a flow sensor calibration check at
least semiannually according to the manufacturer's instructions.
d. At least monthly, inspect all components
for integrity, all electrical connections for continuity and all mechanical
connections for leakage.
(d) For each combustion device subject to the
operating limit in s.
NR 463.23(1) (b) 3. or 4., you shall
install and maintain a CPMS to measure and record the combustion zone
temperature according to the following requirements, as applicable:
1. Locate the temperature sensor in a
position that provides a representative temperature.
2. For a non-cryogenic temperature range, use
a temperature sensor with a minimum tolerance of 2.2°C or 0.75% of the
temperature value, whichever is larger.
3. For a cryogenic temperature range, use a
temperature sensor with a minimum tolerance of 2.2°C or 2% of the
temperature value, whichever is larger.
4. Shield the temperature sensor system from
electromagnetic interference and chemical contaminants.
5. If you use a chart recorder, it shall have
a sensitivity in the minor division of at least 20°F.
6. Perform an electronic calibration at least
semiannually according to the procedures in the manufacturer's owners manual.
Following the electronic calibration, conduct a temperature sensor validation
check, in which a second or redundant temperature sensor placed nearby the
process temperature sensor shall yield a reading within 16.7°C of the
process temperature sensor's reading.
7. Conduct calibration and validation checks
any time the sensor indicates a temperature that exceeds the manufacturer's
specified maximum operating temperature range, or install a new temperature
sensor.
8. At least monthly,
inspect all components for integrity and all electrical connections for
continuity, oxidation and galvanic corrosion.
(e) For each wet acid scrubber subject to the
operating limits in s.
NR 463.23(1) (b) 5., you shall install
and maintain CPMS to measure and record the scrubbing liquid flow rate
according to the requirements in par. (c) 2. and do either of the following:
1. Install and maintain CPMS to measure and
record the pH of the scrubber blowdown according to all of the following
requirements:
a. Locate the pH sensor in a
position that provides a representative measurement of the pH and that
minimizes or eliminates internal and external corrosion.
b. Use a gauge with a minimum measurement
sensitivity of 0.1 pH unit or a transducer with a minimum measurement
sensitivity of 5% of the pH range.
c. Check gauge calibration quarterly or
transducer calibration monthly using a manual pH gauge.
d. At least monthly, inspect all components
for integrity, all electrical connections for continuity and all mechanical
connections for leakage.
2. Extract a sample for analysis by a pH
meter that has all of the following:
a. A
range of at least 1 to 5 pH units or more.
b. An accuracy of 0.1 pH unit.
c. A resolution of at least 0.1 pH
unit.
(f) You
shall operate each CPMS used to meet the requirements of this subchapter
according to all of the following requirements:
1. Each CPMS shall complete a minimum of one
cycle of operation for each successive 15-minute period. You shall have a
minimum of 3 of the required 4 data points to constitute a valid hour of
data.
2. Each CPMS shall have valid
hourly data for 100% of every averaging period.
3. Each CPMS shall calculate and record the
hourly average of all recorded readings and the 3-hour average of all recorded
readings.
(g) For each
automated conveyor and pallet cooling line and automated shakeout line at a new
iron and steel foundry subject to the VOHAP emission limit in s.
NR 463.23(1) (a) 10., you shall install,
operate and maintain a CEMS to measure and record the concentration of VOHAP
emissions according to all of the following requirements:
1. You shall install, operate and maintain
each CEMS according to performance specification 8 in 40 CFR part 60, Appendix
B, incorporated by reference in s.
NR 484.04(21).
2. You shall conduct a performance evaluation
of each CEMS according to the requirements of s.
NR 460.07
and performance specification 8 in 40 CFR part 60, Appendix B.
3. As specified in s.
NR 460.07(3) (d)
2., each CEMS shall complete a minimum of one
cycle of operation, which includes sampling, analyzing and data recording, for
each successive 15-minute period.
4. You shall reduce CEMS data as specified in
s.
NR 460.07(7)
(b).
5. Each CEMS shall calculate and record the
3-hour average emissions using all the hourly averages collected for periods
during which the CEMS is not out-of-control.
6. You shall record the results of each
inspection, calibration and validation check required under this
paragraph.
(3) HOW DO I MONITOR AND COLLECT DATA TO
DEMONSTRATE CONTINUOUS COMPLIANCE?
(a) Except
for monitoring malfunctions, associated repairs and required quality assurance
or control activities, including, as applicable, calibration checks and
required zero and span adjustments, you shall monitor continuously or collect
data at all required intervals any time a source of emissions is
operating.
(b) You may not use data
recorded during monitoring malfunctions, associated repairs and required
quality assurance or control activities in data averages and calculations used
to report emissions or operating levels or to fulfill a minimum data
availability requirement, if applicable. You shall use all the data collected
during all other periods in assessing compliance.
(4) HOW DO I DEMONSTRATE CONTINUOUS
COMPLIANCE WITH THE EMISSION LIMITATIONS THAT APPLY TO ME?
(a) You shall demonstrate continuous
compliance by meeting the following requirements, as applicable:
1. For each electric arc metal melting
furnace, electric induction metal melting furnace or scrap preheater at an
existing iron and steel foundry, you shall do one of the following:
a. Maintain the average PM concentration in
the exhaust stream at or below 0.005 gr/dscf.
b. Maintain the average total metal HAP
concentration in the exhaust stream at or below 0.0004 gr/dscf.
2. For each cupola metal melting
furnace at an existing iron and steel foundry, you shall do one of the
following:
a. Maintain the average PM
concentration in the exhaust stream at or below 0.006 gr/dscf.
b. Maintain the average total metal HAP
concentration in the exhaust stream at or below 0.0005 gr/dscf.
3. For each cupola metal melting
furnace or electric arc metal melting furnace at new iron and steel foundry,
you shall do one of the following:
a. Maintain
the average PM concentration in the exhaust stream at or below 0.002
gr/dscf.
b. Maintain the average
total metal HAP concentration in the exhaust stream at or below 0.0002
gr/dscf.
4. For each
electric induction metal melting furnace or scrap preheater at a new iron and
steel foundry, you shall do one of the following:
a. Maintain the average PM concentration in
the exhaust stream at or below 0.001 gr/dscf.
b. Maintain the average total metal HAP
concentration in the exhaust stream at or below 0.00008 gr/dscf.
5. For each pouring station at an
existing iron and steel foundry, you shall do one of the following:
a. Maintain the average PM concentration in
the exhaust stream at or below 0.010 gr/dscf.
b. Maintain the average total metal HAP
concentration in the exhaust stream at or below 0.0008 gr/dscf.
6. For each pouring area or
pouring station at a new iron and steel foundry, you shall do one of the
following:
a. Maintain the average PM
concentration in the exhaust stream at or below 0.002 gr/dscf.
b. Maintain the average total metal HAP
concentration in the exhaust stream at or below 0.0002 gr/dscf.
7. For each building or structure
housing any emission source at the iron and steel foundry, you shall maintain
the opacity of any fugitive emissions discharged to the atmosphere at or below
20% opacity (6-minute average), except for one 6-minute average per hour that
does not exceed 27% opacity.
8. For
each cupola metal melting furnace at a new or existing iron and steel foundry,
you shall maintain the average VOHAP concentration in the exhaust stream at or
below 20 ppmv corrected to 10% oxygen.
9. For each scrap preheater at an existing
iron and steel foundry that does not comply with the work practice standard in
s.
NR 463.23(2) (e) 1. or 2. and for each
scrap preheater at a new iron and steel foundry that does not comply with the
work practice standard in s.
NR 463.23(2) (f), you shall maintain the
average VOHAP concentration in the exhaust stream at or below 20
ppmv.
10. For one or more automated
conveyor and pallet cooling lines or automated shakeout lines that use a sand
mold system at a new iron and steel foundry, you shall do all of the following:
a. Maintain the 3-hour flow-weighted average
VOHAP concentration in the exhaust stream at or below 20 ppmv.
b. Inspect and maintain each CEMS according
to the requirements of sub. (2) (g) and record all information needed to
document conformance with these requirements.
c. Collect and reduce monitoring data
according to the requirements of sub. (2) (g) and record all information needed
to document conformance with these requirements.
11. For each TEA cold box mold or core making
line at a new or existing iron and steel foundry, you shall maintain a 99%
reduction in the VOHAP concentration in the exhaust stream or maintain the
average VOHAP concentration in the exhaust stream at or below 1 ppmv.
12. You shall conduct subsequent performance
tests at least every 5 years for each emission source subject to an emission
limit for PM, total metal HAP, VOHAP or TEA in s.
NR 463.23(1) (a) and subsequent
performance tests at least every 6 months for each building or structure
subject to the opacity limit in s.
NR 463.23(1) (a) 7.
(b) You shall demonstrate
continuous compliance for each capture system subject to an operating limit in
s.
NR 463.23(1) (b) 1. by doing both of the
following:
1. Operate the capture system at
or above the lowest values or settings established for the operating limits in
your operation and maintenance plan.
2. Monitor the capture system according to
the requirements in sub. (1) (a) and collect, reduce and record the monitoring
data for each of the operating limit parameters according to the applicable
requirements in this subchapter.
(c) You shall demonstrate continuous
compliance for each baghouse equipped with a bag leak detection system doing
both of the following:
1. Maintain records of
the times the bag leak detection system alarm sounded, and for each valid
alarm, the time you initiated corrective action, the corrective action taken
and the date on which corrective action was completed.
2. Inspect and maintain each baghouse
according to the requirements of sub. (1) (b) 1. to 8., and record all
information needed to document conformance with these requirements.
(d) You shall demonstrate
continuous compliance for each wet scrubber that is subject to the operating
limits in s.
NR 463.23(1) (b) 2., by doing all of the
following:
1. Maintaining the 3-hour average
pressure drop and 3-hour average scrubber water flow rate at levels no lower
than those established during the initial or subsequent performance
test.
2. Inspecting and maintaining
each CPMS according to the requirements of sub. (2) (c) and recording all
information needed to document conformance with the requirements.
3. Collecting and reducing monitoring data
for pressure drop and scrubber water flow rate according to the requirements of
sub. (2) (f) and recording all information needed to document conformance with
the requirements.
(e)
You shall demonstrate continuous compliance for each combustion device that is
subject to the operating limit in s.
NR 463.23(1) (b) 3., by doing all of the
following:
1. Maintaining the 15-minute
average combustion zone temperature at a level no lower than
1,300°F.
2. Inspecting and
maintaining each CPMS according to the requirements of sub. (2) (d) and
recording all information needed to document conformance with the
requirements.
3. Collecting and
reducing monitoring data for combustion zone temperature according to the
requirements of sub. (2) (f) and recording all information needed to document
conformance with the requirements.
(f) You shall demonstrate continuous
compliance for each combustion device that is subject to the operating limit in
s.
NR 463.23(1) (b) 4., by doing all of the
following:
1. Maintaining the 3-hour average
combustion zone temperature at a level no lower than that established during
the initial or subsequent performance test.
2. Inspecting and maintaining each CPMS
according to the requirements of sub. (2) (d) and recording all information
needed to document conformance with these requirements.
3. Collecting and reducing monitoring data
for combustion zone temperature according to the requirements of sub. (2) (f)
and recording all information needed to document conformance with these
requirements.
(g) You
shall demonstrate continuous compliance for each acid wet scrubber subject to
the operating limits in s.
NR 463.23(1) (b) 5., by doing all of the
following:
1. Maintaining the 3-hour average
scrubbing liquid flow rate at a level no lower than the level established
during the initial or subsequent performance test.
2. Maintaining the 3-hour average pH of the
scrubber blowdown at a level no higher than 4.5, if measured by a CPMS, or
maintaining the pH level of the scrubber blowdown during each production shift
no higher than 4.5.
3. Inspecting
and maintaining each CPMS according to the requirements of sub. (2) (e) and
recording all information needed to document conformance with the
requirements.
4. Collecting and
reducing monitoring data for scrubbing liquid flow rate and scrubber blowdown
pH according to the requirements of sub. (2) (f) and recording all information
needed to document conformance with the requirements. If the pH level of the
scrubber blowdown is measured by a probe and meter, you shall demonstrate
continuous compliance by maintaining records that document the date, time and
results of each sample taken for each production shift.
(5) HOW DO I DEMONSTRATE
CONTINUOUS COMPLIANCE WITH THE WORK PRACTICE STANDARDS THAT APPLY TO ME?
(a) You shall maintain records that document
continuous compliance with the certification requirements in s.
NR 463.23(2) (b) or with the procedures
in your scrap selection and inspection plan required in s.
NR 463.23(2) (c). Your records
documenting compliance with the scrap selection and inspection plan shall
include a copy kept onsite of the procedures used by the scrap supplier for
either removing accessible mercury switches or for purchasing automobile bodies
that have had mercury switches removed, as applicable.
(b) You shall keep records of the chemical
composition of all catalyst binder formulations applied in each furan warm box
mold or core making line at a new or existing iron and steel foundry to
demonstrate continuous compliance with the requirements in s.
NR 463.23(2) (d).
(c) For a scrap preheater at an existing iron
and steel foundry, you shall operate and maintain each gas-fired preheater so
that the flame directly contacts the scrap charged to demonstrate continuous
compliance with the requirement s.
NR 463.23(2) (e) 1. If you choose to
meet the work practice standard in s.
NR 463.23(2) (e) 2., you shall keep
records to document that the scrap preheater charges only material that is
subject to and in compliance with the scrap certification requirements in s.
NR 463.23(2) (b).
(d) For a scrap preheater at a new iron and
steel foundry, you shall keep records to document that each scrap preheater
charges only material that is subject to and in compliance with the scrap
certification requirements in s.
NR 463.23(2) (b) to demonstrate
continuous compliance with the requirement in s.
NR 463.23(2) (f).
(6) HOW DO I DEMONSTRATE CONTINUOUS
COMPLIANCE WITH THE OPERATION AND MAINTENANCE REQUIREMENTS THAT APPLY TO ME?
(a) For each capture system and control
device for an emission source subject to an emission limit in s.
NR 463.23(1) (a), you shall demonstrate
continuous compliance with the operation and maintenance requirements of s.
NR 463.23(3) by doing all of the
following:
1. Making monthly inspections of
capture systems and initiating corrective action according to s.
NR 463.23(3) (b) 1., and recording all
information needed to document conformance with the requirements.
2. Performing preventive maintenance for each
control device according to the preventive maintenance plan required by s.
NR 463.23(3) (b) 3., and recording all
information needed to document conformance with the requirements.
3. Operating and maintaining each bag leak
detection system according to the site-specific monitoring plan required by s.
NR 463.23(3) (b) 4., and recording all
information needed to demonstrate conformance with the requirements.
4. Initiating and completing corrective
action for a bag leak detection system alarm according to the corrective action
plan required by s.
NR 463.23(3) (b) 5., and recording all
information needed to document conformance with the requirements.
5. Igniting gases from mold vents according
to the procedures in the plan required by s.
NR 463.23(3) (b) 6.
(b) Any instance where you fail to
follow the procedures in par. (a) is a deviation that shall be included in your
semiannual compliance report.
(c)
You shall maintain a current copy of the operation and maintenance plans
required by s.
NR 463.23(3) (b) onsite and available
for inspection upon request. You shall keep the plans for the life of the iron
and steel foundry or until the iron and steel foundry is no longer subject to
the requirements of this subchapter.
(7) WHAT OTHER REQUIREMENTS MUST I MEET TO
DEMONSTRATE CONTINUOUS COMPLIANCE?
(a)
Deviations. You shall report each instance in which you did not meet each
emission limitation in s.
NR 463.23(1), including each operating
limit, that applies to you. This requirement includes periods of startup,
shutdown and malfunction. You also shall report each instance in which you did
not meet each work practice standard in s.
NR 463.23(2) and each operation and
maintenance requirement of s.
NR 463.23(3) that applies to you.
Failure to meet the requirements described in this paragraph are deviations
from the emission limitations, work practice standards and operation and
maintenance requirements in this subchapter and shall be reported according to
the requirements of s.
NR 463.27(2).
(b) Startups, shutdowns and malfunctions.
1. Consistent with the requirements of ss.
NR 460.05(4) and 460.06(4) (a),
deviations that occur during a period of startup, shutdown or malfunction are
not violations if you demonstrate to the department's satisfaction that you
were operating in accordance with s.
NR 460.05(4) (a).
2. The department shall determine whether
deviations that occur during a period of startup, shutdown or malfunction are
violations according to the provisions in s.
NR 460.05(4).
(8) HOW DO I APPLY FOR ALTERNATIVE
MONITORING REQUIREMENTS FOR A CONTINUOUS EMISSIONS MONITORING SYSTEM?
(a) You may submit a request to the
administrator for an alternative monitoring method to demonstrate compliance
with the VOHAP emission limits in s.
NR 463.23(1) (a) 10. for automated
pallet cooling lines or automated shakeout lines at a new iron and steel
foundry according to the procedures in this section.
(b) You may request approval to use an
alternative monitoring method in the notification of construction or for new
sources, or at any time.
(c) You
shall submit a monitoring plan to the administrator that includes a description
of the control technique or pollution prevention technique, a description of
the continuous monitoring system or method, including appropriate operating
parameters that will be monitored, test results demonstrating compliance with
the emission limit, operating limits, if applicable, determined according to
the test results, and the frequency of measuring and recording to establish
continuous compliance. If applicable, you shall also include operation and
maintenance requirements for the monitors.
(d) The monitoring plan is subject to
approval by the administrator. Use of the alternative monitoring method may not
begin until approval is granted by the administrator.
The Administrator of the US Environmental Protection
Agency retains the authority to approve major alternatives to monitoring
according to
40 CFR
63.7761(c) (3).