Current through August 26, 2024
The owner or operator of an affected source subject to the
emission limitations of this subchapter shall conduct monitoring according to
the type of air pollution control technique that is used to comply with the
emission limitation. The monitoring required to demonstrate continuous
compliance with the emission limitations is identified in this section for the
air pollution control techniques expected to be used by the owners or operators
of affected sources.
(1) COMPOSITE
MESH-PAD SYSTEMS.
(a) During the initial
performance test, the owner or operator of an affected source, or a group of
affected sources under common control, complying with the emission limitations
in s.
NR 463.04 through the use of a composite mesh-pad system
shall determine the outlet chromium concentration using the test methods and
procedures in s.
NR 463.09(3), and shall establish as a
site-specific operating parameter the pressure drop across the system, setting
the value that corresponds to compliance with the applicable emission
limitation, using the procedures in s.
NR 463.09(4) (e). An owner or operator
may conduct multiple performance tests to establish a range of compliant
pressure drop values, or may set as the compliant value the average pressure
drop measured over the 3 test runs of one performance test and accept ±
2 inches of water column from this value as the compliant range. [DOUBLE
DAGGER]
(b) On and after the date
on which the initial performance test is required to be completed under s.
NR 460.06, the owner or operator of an affected source,
or group of affected sources under common control, shall monitor and record the
pressure drop across the composite mesh-pad system once each day that any
affected source is operating. To be in compliance with the standards in s.
NR 463.04, the composite mesh-pad system shall be
operated within ± 2 inches of water column of the pressure drop value
established during the initial performance test, or shall be operated within
the range of compliant values for pressure drop established during multiple
performance tests.
(c) The owner or
operator of an affected source complying with the emission limitation of s.
NR 463.04 through the use of a composite mesh-pad system
may repeat the performance test and establish as a new site-specific operating
parameter the pressure drop across the composite mesh-pad system according to
the requirements in par. (a) or (b). To establish a new site-specific operating
parameter for pressure drop, the owner or operator shall satisfy all of the
following requirements:
1. Determine the
outlet chromium concentration using the test methods and procedures in s.
NR 463.09(3).
2. Establish the site-specific operating
parameter value using the procedures in s.
NR 463.09(4).
3. Satisfy the recordkeeping requirements in
s.
NR 463.103.
4. Satisfy the reporting requirements in s.
NR 463.106.
(d) The requirement to operate a composite
mesh-pad system within the range of pressure drop values established under
pars. (a) to (c) does not apply during the automatic-washdown cycles of the
composite-mesh pad system.
(2) PACKED-BED SCRUBBER SYSTEMS.
(a) During the initial performance test, the
owner or operator of an affected source, or group of affected sources under
common control, complying with the emission limitations in s.
NR 463.04 through the use of a packed-bed scrubber system
shall determine the outlet chromium concentration using the procedures in s.
NR 463.09(3), and shall establish as
site-specific operating parameters the pressure drop across the system and the
velocity pressure at the common inlet of the control device, setting the value
that corresponds to compliance with the applicable emission limitation using
the procedures in s.
NR 463.09(4) (d) and (e). An owner or
operator may conduct multiple performance tests to establish a range of
compliant operating parameter values. Alternatively, the owner or operator may
set as the compliant value the average pressure drop and inlet velocity
pressure measured over the 3 test runs of one performance test, and accept
± 1 inch of water column from the pressure drop value and ± 10%
from the velocity pressure value as the compliant range.
(b) On and after the date on which the
initial performance test is required to be completed under s.
NR 460.06, the owner or operator of an affected source,
or group of affected sources under common control, shall monitor and record the
velocity pressure at the inlet to the packed-bed scrubber and the pressure drop
across the scrubber system once each day that any affected source is operating.
To be in compliance with the standards in s.
NR 463.04, the scrubber system shall be operated within
±10% of the velocity pressure value established during the initial
performance test, and within ±1 inch of water column of the pressure
drop value established during the initial performance test, or within the range
of compliant operating parameter values established during multiple performance
tests.
(3) PACKED-BED
SCRUBBER/COMPOSITE MESH-PAD SYSTEM. The owner or operator of an affected
source, or group of affected sources under common control, that uses a
packed-bed scrubber in conjunction with a composite mesh-pad system to meet the
emission limitations of s.
NR 463.04 shall comply with the monitoring requirements
for composite mesh-pad systems as identified in sub. (1).
(4) FIBER-BED MIST ELIMINATOR.
(a) During the initial performance test, the
owner or operator of an affected source, or group of affected sources under
common control, complying with the emission limitations in s.
NR 463.04 through the use of a fiber-bed mist eliminator
shall determine the outlet chromium concentration using the procedures in s.
NR 463.09(3), and shall establish as a
site-specific operating parameter the pressure drop across the fiber-bed mist
eliminator and the pressure drop across the control device installed upstream
of the fiber bed to prevent plugging, setting the value that corresponds to
compliance with the applicable emission limitation using the procedures in s.
NR 463.09(4) (e). An owner or operator
may conduct multiple performance tests to establish a range of compliant
pressure drop values, or may set as the compliant value the average pressure
drop measured over the 3 test runs of one performance test and accept ±
1 inch of water column from this value as the compliant range.
(b) On and after the date on which the
initial performance test is required to be completed under s.
NR 460.06, the owner or operator of an affected source,
or group of affected sources under common control, shall monitor and record the
pressure drop across the fiber-bed mist eliminator, and the control device
installed upstream of the fiber bed to prevent plugging, once each day that any
affected source is operating. To be in compliance with the standards in s.
NR 463.04, the fiber-bed mist eliminator and the upstream
control device shall be operated within ± 1 inch of water column of the
pressure drop value established during the initial performance test, or shall
be operated within the range of compliant values for pressure drop established
during multiple performance tests.
(5) WETTING AGENT-TYPE OR COMBINATION WETTING
AGENT-TYPE/FOAM BLANKET FUME SUPPRESSANTS.
(a) During the initial performance test, the
owner or operator of an affected source complying with the emission limitations
in s.
NR 463.04 through the use of a wetting agent in the
electroplating or anodizing bath shall determine the outlet chromium
concentration using the procedures in s.
NR 463.09(3). The owner or operator
shall establish as the site-specific operating parameter the surface tension of
the bath using Method 306B in Appendix A of 40 CFR part 63, incorporated by
reference in s.
NR 484.04(25), setting the maximum value
that corresponds to compliance with the applicable emission limitation. In lieu
of establishing the maximum surface tension during the performance test, the
owner or operator may accept 45 dynes/cm (3.1 x 10-3 pound-force per foot (lbf
/ft)) as measured by a stalagmometer or 35 dynes/cm (2.4 x 10-3 lbf /ft) as
measured by a tensiometer as the maximum surface tension value that corresponds
to compliance with the applicable emission limitation. However, the owner or
operator is exempt from conducting a performance test only if the criteria of
s.
NR 463.06(3)
(b) are met.
(b) On and after the date on which the
initial performance test is required to be completed under s.
NR 460.06, the owner or operator of an affected source
shall monitor the surface tension of the electroplating or anodizing bath.
Operation of the affected source at a surface tension greater than the value
established during the performance test or greater than 45 dynes/cm (3.1 x 10-3
lbf /ft) as measured by a stalagmometer or 35 dynes/cm (2.4 x 10-3 lbf /ft) as
measured by a tensiometer if the owner or operator is using this value in
accordance with par. (a), shall constitute noncompliance with the standards in
s.
NR 463.04. The surface tension shall be monitored
according to the following schedule:
1. The
surface tension shall be measured once every 4 hours during operation of the
tank with a stalagmometer or a tensiometer as specified in Method 306B in
Appendix A of 40 CFR part 63, incorporated by reference in s.
NR 484.04.
2.
The time between monitoring may be increased if there have been no exceedances.
The surface tension shall be measured once every 4 hours of tank operation for
the first 40 hours of tank operation after the compliance date. Once there are
no exceedances during 40 hours of tank operation, surface tension measurement
may be conducted once every 8 hours of tank operation. Once there are no
exceedances during 40 more hours of tank operation, surface tension measurement
may be conducted once every 40 hours of tank operation on an ongoing basis,
until an exceedance occurs. The minimum frequency of monitoring allowed by this
subchapter is once every 40 hours of tank operation.
3. Once an exceedance occurs as indicated
through surface tension monitoring, the original monitoring schedule of once
every 4 hours shall be resumed. A subsequent decrease in frequency shall follow
the schedule laid out in subd. 2. For example, if an owner or operator had been
monitoring an affected source once every 40 hours and an exceedance occurs,
subsequent monitoring would take place once every 4 hours of tank operation.
Once an exceedance does not occur for 40 hours of tank operation, monitoring
may occur once every 8 hours of tank operation. Once an exceedance does not
occur for 40 hours of tank operation on this schedule, monitoring may occur
once every 40 hours of tank operation.
(c) Once a bath solution is drained from the
affected tank and a new solution added, the original monitoring schedule of
once every 4 hours shall be resumed, with a decrease in monitoring frequency
allowed following the procedures of par. (b) 2. and 3.
(6) FOAM BLANKET-TYPE FUME SUPPRESSANTS.
(a) During the initial performance test, the
owner or operator of an affected source complying with the emission limitations
in s.
NR 463.04 through the use of a foam blanket in the
electroplating or anodizing bath shall determine the outlet chromium
concentration using the procedures in s.
NR 463.09(3), and shall establish as the
site-specific operating parameter the thickness of the foam blanket, setting
the minimum thickness that corresponds to compliance with the applicable
emission limitation. In lieu of establishing the minimum foam blanket thickness
during the performance test, the owner or operator may accept 2.54 centimeters
(1 inch) as the minimum foam blanket thickness that corresponds to compliance
with the applicable emission limitation. All foam blanket measurements shall be
taken in close proximity to the workpiece or cathode area in the plating
tank.
(b) On and after the date on
which the initial performance test is required to be completed under s.
NR 460.06, the owner or operator of an affected source
shall monitor the foam blanket thickness of the electroplating or anodizing
bath. Operation of the affected source at a foam blanket thickness less than
the value established during the performance test, or less than 2.54 cm (1
inch) if the owner or operator is using this value in accordance with par. (a),
constitutes noncompliance with the standards in s.
NR 463.04. The foam blanket thickness shall be measured
according to the following schedule:
1. The
foam blanket thickness shall be measured once every hour of tank
operation.
2. The time between
monitoring may be increased if there have been no exceedances. The foam blanket
thickness shall be measured once every hour of tank operation for the first 40
hours of tank operation after the compliance date. Once there are no
exceedances for 40 hours of tank operation, foam blanket thickness measurement
may be conducted once every 4 hours of tank operation. Once there are no
exceedances during 40 more hours of tank operation, foam blanket thickness
measurement may be conducted once every 8 hours of tank operation on an ongoing
basis, until an exceedance occurs. The minimum frequency of monitoring allowed
by this subchapter is once per 8 hours of tank operation.
3. Once an exceedance occurs as indicated
through foam blanket thickness monitoring, the original monitoring schedule of
once every hour shall be resumed. A subsequent decrease in frequency shall
follow the schedule laid out in subd. 2. For example, if an owner or operator
had been monitoring an affected source once every 8 hours and an exceedance
occurs, subsequent monitoring would take place once every hour of tank
operation. Once an exceedance does not occur for 40 hours of tank operation,
monitoring may occur once every 4 hours of tank operation. Once an exceedance
does not occur for 40 hours of tank operation on this schedule, monitoring may
occur once every 8 hours of tank operation.
(c) Once a bath solution is drained from the
affected tank and a new solution added, the original monitoring schedule of
once every hour shall be resumed, with a decrease in monitoring frequency
allowed following the procedures of par. (b) 2. and 3.
(7) FUME SUPPRESSANT/ADD-ON CONTROL DEVICE.
(a) If the owner or operator of an affected
source uses both a fume suppressant and add-on control device and both are
needed to comply with the applicable emission limit, monitoring requirements as
identified in subs. (1) to (6), and the work practice standards of Table 1 of
this subchapter, apply for each of the control techniques used.
(b) If the owner or operator of an affected
source uses both a fume suppressant and add-on control device, but only one of
these techniques is needed to comply with the applicable emission limit,
monitoring requirements as identified in subs. (1) to (6), and work practice
standards of Table 1 of this subchapter, apply only for the control technique
used to achieve compliance.
(8) USE OF AN ALTERNATIVE MONITORING METHOD.
(a) Requests and approvals of alternative
monitoring methods shall be considered in accordance with s.
NR 460.07(6).
(b) After receipt and consideration of an
application for an alternative monitoring method, the department may approve
alternatives to any monitoring methods or procedures of this subchapter
including, but not limited to, the following:
1. Alternative monitoring requirements when
installation or use of monitoring devices specified in this subchapter would
not provide accurate measurements due to interferences caused by substances
within the effluent gases.
2.
Alternative locations for installing monitoring devices when the owner or
operator can demonstrate that installation at alternate locations will enable
accurate and representative measurements.