Current through August 26, 2024
(1) APPLICABILITY.
(a) The provisions of this section are
applicable to the following facilities in steel plants that produce carbon,
alloy, or specialty steels: electric arc furnaces, argon-oxygen decarburization
vessels and dust-handling systems.
(b) The provisions of this section apply to
each affected facility identified in par. (a) that commences construction,
modification, or reconstruction after August 17, 1983.
(2) DEFINITIONS. As used in this section,
terms not defined in this subsection have the meanings given in s.
NR 440.02.
(a)
"Argon-oxygen decarburization vessel" or "AOD vessel" means any closed-bottom,
refractory-lined converter vessel with submerged tuyeres through which gaseous
mixtures containing argon and oxygen or nitrogen may be blown into molten steel
for further refining.
(am) "Bag
leak detection system" means a system that is capable of continuously
monitoring relative particulate matter (dust) loadings in the exhaust of a
baghouse to detect bag leaks and other conditions that result in increases in
particulate loadings. A bag leak detection system includes an instrument that
operates on triboelectric, electrodynamic, light scattering, light
transmittance, or other effect to continuously monitor relative particulate
matter loadings.
(b) "Capture
system" means the equipment (including ducts, hoods, fans, dampers, etc.) used
to capture or transport particulate matter generated by an electric arc furnace
or AOD vessel to the air pollution control device.
(c) "Charge" means the addition of iron and
steel scrap or other materials into the top of an electric arc furnace or the
addition of molten steel or other materials into the top of an AOD
vessel.
(d) "Control device" means
the air pollution control equipment used to remove particulate matter from the
effluent gas stream generated by an electric arc furnace or AOD
vessel.
(e) "Direct-shell
evacuation control system" or "DEC system" means a system that maintains a
negative pressure within the electric arc furnace above the slag or metal and
ducts emissions to the control device.
(f) "Dust-handling system" means equipment
used to handle particulate matter collected by the control device for an
electric arc furnace or AOD vessel subject to this section. For the purposes of
this section the dust-handling system shall consist of the control device dust
hoppers, the dust-conveying equipment, any central dust storage equipment, the
dust-treating equipment (e.g., pug mill, pelletizer), dust transfer equipment
(from storage to truck) and any secondary control devices used with the dust
transfer equipment.
(g) "Electric
arc furnace" or "EAF" means a furnace that produces molten steel and heats the
charge materials with electric arcs from carbon electrodes. For the purposes of
this section an EAF shall consist of the furnace shell and roof and the
transformer. Furnaces that continuously feed direct-reduced iron ore pellets as
the primary source of iron are not affected facilities within the scope of this
definition.
(h) "Heat cycle" means
the period beginning when scrap is charged to an empty EAF and ending when the
EAF tap is completed or beginning when molten steel is charged to an empty AOF
vessel and ending when the AOD vessel tap is completed.
(hm) "Meltdown and refining period" means the
time period commencing at the termination of the initial charging period and
ending at the initiation of the tapping period, excluding any intermediate
charging periods and times when power to the EAF is off.
(i) "Melting" means that phase of steel
production cycle during which the iron and steel scrap is heated to the molten
state.
(j) "Negative-pressure
fabric filter" means a fabric filter with the fans on the downstream side of
the filter bags.
(k)
"Positive-pressure fabric filter" means a fabric filter with the fans on the
upstream side of the filter bags.
(L) "Refining" means the phase of the steel
production cycle during which undesirable elements are removed from the molten
steel and alloys are added to reach the final metal chemistry.
(m) "Shop" means the building which houses
one or more EAF's or AOD vessels.
(n) "Shop opacity" means the arithmetic
average of 24 observations of the opacity of emissions from the shop taken in
accordance with Method 9 of 40 CFR part 60, Appendix A, incorporated by
reference in s.
NR 440.17.
(o) "Tap" means the pouring of molten steel
from an EAF or AOD vessel.
(om)
"Tapping period" means the time period commencing at the moment an EAF begins
to pour molten steel and ending either 3 minutes after steel ceases to flow
from an EAF, or 6 minutes after steel begins to flow, whichever is
longer.
(3) STANDARD FOR
PARTICULATE MATTER.
(a) On and after the date
on which the performance test required to be conducted by s.
NR 440.08 is
completed no owner or operator subject to the provisions of this section may
cause to be discharged into the atmosphere from an EAF or an AOD vessel any
gases which:
1. Exit from a control device
and contain particulate matter in excess of 12 mg/dscm (0.0052
gr/dscf);
2. Exit from a control
device and exhibit 3% opacity or greater; and
3. Exit from a shop and, due solely to the
operations of any affected EAF(s) or AOD vessel(s), exhibit 6% opacity or
greater.
(b) On and
after the date on which the performance test required to be conducted by s.
NR 440.08 is
completed, no owner or operator subject to the provisions of this section may
cause to be discharged into the atmosphere from the dust-handling system any
gases that exhibit 10% opacity or greater.
(4) EMISSION MONITORING.
(a) Except as provided under pars. (b) and
(c) a continuous monitoring system for the measurement of the opacity of
emissions discharged into the atmosphere from the control device(s) shall be
installed, calibrated, maintained and operated by the owner or operator subject
to the provisions of this section.
(b) No continuous monitoring system is
required on any control device serving the dust-handling system.
(c) A continuous monitoring system for the
measurement of opacity of emissions discharged into the atmosphere from the
control device is not required on modular, multiple-stack, negative-pressure or
positive-pressure fabric filter if observations of the opacity of the visible
emissions from the control device are performed by a certified visible
emissions observer; or on any single-stack fabric filter if visible emissions
from the control device are performed by a certified visible emission observer
and the owner installs and continuously operates a bag leak detection system
according to par. (e). Visible emission observations are shall be conducted at
least once per day for at least 3 6-minute periods when the furnace is
operating in the melting and refining period. All visible emissions
observations shall be conducted in accordance with Method 9. If visible
emissions occur from more than one point, the opacity shall be recorded for any
point where visible emissions are observed. Where it is possible to determine
that a number of visible emission sites relate to only one incident of the
visible emission, only one set of 3 6-minute observations will be required. In
that case, the Method 9 observations shall be made for the site of highest
opacity that directly relates to the cause, or location, of visible emissions
observed during a single incident. Records shall be maintained of any 6-minute
average that is in excess of the emission limit specified in sub. (3)
(a).
(d) A furnace static pressure
monitoring device is not required on any EAF equipped with a DEC system if
observations of shop opacity are performed by a certified visible emission
observer as follows: Shop opacity observations shall be conducted at least once
per day when the furnace is operating in the meltdown and refining period. Shop
opacity shall be determined as the arithmetic average of 24 or more consecutive
15-second opacity observations of emissions from the shop taken in accordance
with Method 9. Shop opacity shall be recorded for any points where visible
emissions are observed. Where it is possible to determine that a number of
visible emission sites relate to only one incident of visible emissions, only
one observation of shop opacity shall be required. In this case, the shop
opacity observations shall be made for the site of highest opacity that
directly relates to the cause or location of visible emissions observed during
a single incident.
(e) A bag leak
detection system shall be installed and continuously operated on all
single-stack fabric filters if the owner or operator elects not to install and
operate a continuous opacity monitoring system as provided for under par. (c).
In addition, the owner or operator shall meet the visible emissions observation
requirements in par. (c). The bag leak detection system shall meet the
specifications and requirements of subds. 1. to 8.
1. The bag leak detection system shall be
certified by the manufacturer to be capable of detecting particulate matter
emissions at concentrations of one milligram per actual cubic meter (0.00044
grains per actual cubic foot) or less.
2. The bag leak detection system sensor shall
provide output of relative particulate matter loadings and the owner or
operator shall continuously record the output from the bag leak detection
system using electronic or other mean such as a strip chart recorder or a data
logger.
3. The bag leak detection
system shall be equipped with an alarm system that will sound when an increase
in relative particulate loading is detected over the alarm set point
established according to subd. 4., and the alarm shall be located such that it
can be heard by the appropriate plant personnel.
4. For each bag leak detection system
required by this paragraph, the owner or operator shall develop and submit to
the department, for approval, a site-specific monitoring plan that addresses
the items identified in subd. 4. a. to e. For each bag leak detection system
that operates based on the triboelectric effect, the monitoring plan shall be
consistent with the recommendations contained in the EPA guidance document
"Fabric Filter Bag Leak Detection Guidance" (EPA-454/R-98-015), incorporated by
reference in s.
NR 440.17(2) (i) 4. The owner or
operator shall operate and maintain the bag leak detection system according to
the site-specific monitoring plan at all times. The plan shall describe all the
following:
a. Installation of the bag leak
detection system.
b. Initial and
periodic adjustment of the bag leak detection system including how the alarm
set-point will be established.
c.
Operation of the bag leak detection system including quality assurance
procedures.
d. How the bag leak
detection system will be maintained including a routine maintenance schedule
and spare parts inventory list.
e.
How the bag leak detection system output will be recorded and stored.
5. The initial adjustment of the
system shall, at a minimum, consist of establishing the baseline output by
adjusting the sensitivity (range) and the averaging period of the device, and
establishing the alarm set points and the alarm delay time, if
applicable.
6. Following initial
adjustment, the owner or operator may not adjust the averaging period, alarm
set point, or alarm delay time without approval from the department except as
provided for in subd. 6. a. and b.
a. Once
per quarter, the owner or operator may adjust the sensitivity of the bag leak
detection system to account for seasonal effects including temperature and
humidity according to the procedures identified in the site-specific monitoring
plan required under subd. 4.
b. If
opacities greater than zero percent are observed over 4 consecutive 15-second
observations during the daily opacity observations required under par. (c) and
the alarm on the bag leak detection system does not sound, the owner or
operator shall lower the alarm set point on the bag leak detection system to a
point where the alarm would have sounded during the period when the opacity
observations were made.
7. For negative pressure, induced air
baghouses, and positive pressure baghouses that are discharged to the
atmosphere through a stack, the bag leak detection sensor shall be installed
downstream of the baghouse and upstream of any wet scrubber.
8. Where multiple detectors are required, the
system's instrumentation and alarm may be shared among detectors.
(f) For each bag leak detection
system installed according to par. (e), the owner or operator shall initiate
procedures to determine the cause of all alarms within one hour of an alarm.
Except as provided for under par. (g), the cause of the alarm shall be
alleviated within 3 hours of the time the alarm occurred by taking whatever
corrective actions are necessary. Corrective actions may include the following:
1. Inspecting the baghouse for air leaks,
torn or broken bags or filter media, or any other condition that may cause an
increase in particulate emissions.
2. Sealing off defective bags or filter
media.
3. Replacing defective bags
or filter media or otherwise repairing the control device.
4. Sealing off a defective baghouse
compartment.
5. Cleaning the bag
leak detection system probe or otherwise repairing the bag leak detection
system.
6. Shutting down the
process producing the particulate emissions.
(g) In approving the site-specific monitoring
plan required in par. (e) 4., the department may allow owners or operators more
than 3 hours to alleviate specific conditions that cause an alarm if the owner
or operator identifies the condition that could lead to an alarm in the
monitoring plan, adequately explains why it is not feasible to alleviate the
condition within 3 hours of the time the alarm occurred, and demonstrates that
the requested additional time will ensure alleviation of the condition as
expeditiously as practicable.
(5) MONITORING OF OPERATIONS.
(a) The owner or operator subject to the
provisions of this section shall maintain records of the following information:
1. All data obtained under par. (b);
and
2. All monthly operational
status inspections performed under par. (c).
(b) Except as provided under
40 CFR
60.274a(e), the owner or
operator subject to the provisions of this section shall check and record on a
once-per-shift basis the furnace static pressure (if a DEC system is in use,
and a furnace static pressure gauge is installed according to par. (f)) and
either: check and record the control system fan motor amperes and damper
position on a once-per-shift basis; install, calibrate and maintain a
monitoring device that continuously records the volumetric flow rate through
each separately ducted hood, or install, calibrate and maintain a monitoring
device that continuously records the volumetric flow rate at the control device
inlet and check and record damper positions on a once-per-shift basis. The
monitoring device may be installed in any appropriate location in the exhaust
duct such that reproducible flow rate monitoring will result. The flow rate
monitoring device shall have an accuracy of ± 10% over its normal
operating range and shall be calibrated according to the manufacturer's
instructions. The department may require the owner or operator to demonstrate
the accuracy of the monitoring device relative to Methods 1 and 2 of 40 CFR
part 60, Appendix A, incorporated by reference in s.
NR 440.17(1).
(c) When the owner or operator of an affected
facility is required to demonstrate compliance with the standards under sub.
(3) (a) 3., and at any other time that the department may require either: the
control system fan motor amperes and all damper positions, the volumetric flow
rate through each separately ducted hood, or the volumetric flow rate at the
control device inlet and all damper positions shall be determined during all
periods in which a hood is operated for the purpose of capturing emissions from
the affected facility subject to par. (b). The owner or operator may petition
the department for reestablishment of these parameters whenever the owner or
operator can demonstrate to the department's satisfaction that the affected
facility operating conditions upon which the parameters were previously
established are no longer applicable. The values of these parameters as
determined during the most recent demonstration of compliance shall be
maintained at the appropriate level for each applicable period. Operation at
other than baseline values may be subject to the requirements of sub. (7)
(c).
(d) Except as provided under
40 CFR
60.274a(e), the owner or
operator shall perform monthly operational status inspections of the equipment
that is important to the performance of the total capture system, that is,
pressure sensors, dampers and damper switches. This inspection shall include
observations of the physical appearance of the equipment such as presence of
holes in ductwork or hoods, flow constrictions caused by dents or accumulated
dust in ductwork and fan erosion. Any deficiencies shall be noted and proper
maintenance performed.
Note: Under
40 CFR
60.274a(e), the owner or
operator may petition the administrator to approve any alternative to monthly
operational status inspections that will provide a continuous record of the
operation of each emission capture system.
(f) Except as provided for under
40 CFR
60.274a(e), if emissions
during any phase of the heat time are controlled by the use of a DEC system the
owner or operator shall install, calibrate and maintain a monitoring device
that allows the pressure in the free space inside EAF to be monitored. The
pressure shall be recorded as 15-minute integrated averages. The monitoring
device may be installed in any appropriate location in the EAF or DEC duct
prior to the introduction of ambient air such that reproducible results will be
obtained. The pressure monitoring device shall have an accuracy of "5mm of
water gauge over its normal operating range and shall be calibrated according
to the manufacturer's instruction.
(g) Except as provided in
40 CFR
60.274a(e), when the owner
or operator of an EAF controlled by a DEC is required to demonstrate compliance
with the standard under sub. (3) (a) 3., and at any other time the department
may require, the pressure in the free space inside the furnace shall be
determined during the melting and refining periods using the monitoring device
required under par. (f). The owner or operator may petition the department for
reestablishment of the 15-minute integrated average of the pressure whenever
the owner or operator can demonstrate to the department's satisfaction that the
EAF operating conditions upon which the pressures were previously established
are no longer applicable. The pressure determined during the most recent
demonstration of compliance shall be maintained at all times when the EAF is
operating in a meltdown and refining period. Operation at higher pressures may
be considered by the department to be unacceptable operation and maintenance of
the affected facility.
(h) During
any performance test required under s.
NR 440.08 and
for any report thereof required by sub. (6) (f), or to determine compliance
with sub. (3) (a) 3., the owner or operator shall monitor the following
information for all heats covered by the test:
1. Charge weights and materials and tap
weights and materials;
2. Heat
times, including start and stop times, and a log of process operation including
periods of no operation during testing and the pressure inside an EAF when
direct-shell evacuation control system are used;
3. Control device operation log;
and
4. Continuous opacity monitor
or Method 9 of 40 CFR part 60, Appendix A, incorporated by reference in s.
NR 440.17(1), data.
(6) TEST METHODS AND PROCEDURES.
(a) During performance tests required in s.
NR 440.08, the
owner or operator may not add gaseous diluents to the effluent gas stream after
the fabric in any pressurized fabric filter collector, unless the amount of
dilution is separately determined and considered in the determination of
emissions.
(b) When emissions from
any EAF or AOD vessel are combined with emissions from facilities not subject
to the provisions of this section but controlled by a common capture system and
control device, the owner or operator shall use either or both of the following
procedures during a performance test:
Note: See also sub. (7) (e).
1. Determine compliance using the combined
emissions.
2. Use a method that is
acceptable to the department and that compensates for the emissions from the
facilities not subject to the provisions of this section.
(c) When emission from any EAF or AOD vessel
are combined with emissions from facilities not subject to the provisions of
this section, the owner or operator shall demonstrate compliance with sub. (3)
(a) 3. based on emissions from only the affected facility.
(d) In conducting the performance tests
required in s.
NR 440.08, the
owner or operator shall use as reference methods and procedures the test
methods in Appendix A of 40 CFR part 60, incorporated by reference in s.
NR 440.17, or other methods and procedures as specified
in this subsection, except as provided in s.
NR 440.08(2).
(e) The owner or operator shall determine
compliance with the particulate matter standards in sub. (3) as follows:
1. Method 5 shall be used for
negative-pressure fabric filters and other types of control devices and Method
5D shall be used for positive-pressure fabric filters to determine the
particulate matter concentration and volumetric flow rate of the effluent gas.
The sampling time and sample volume for each run shall be at least 4 hours and
4.50 dscm (160 dscf) and, when a single EAF or AOD vessel is sampled, the
sampling time shall include an integral number of heats.
2. When more than one control device serves
the EAF being tested, the concentration of particulate matter shall be
determined using the following equation:
See PDF for
diagram
where:
cst is the average concentration of particulate matter,
mg/dscm (gr/dscf)
csi is the concentration of particulate matter from
control device "i", mg/dscm (gr/dscf)
n is the total number of control devices tested
Qsdi is the volumetric flow rate of stack gas from control
device "i", dscm/hr (dscf/hr)
3. Method 9 and the procedures of s.
NR 440.11 shall be used to determine opacity.
4. To demonstrate compliance with sub. (3)
(a) 1. to 3., the Method 9 of 40 CFR part 60, Appendix A, incorporated by
reference in s.
NR 440.17(1), test runs shall be
conducted concurrently with the particulate matter test runs, unless inclement
weather interferes.
(f)
To comply with sub. (5) (c) and (f) to (h), the owner or operator shall obtain
the information required in these paragraphs during the particulate matter
runs.
(g) Any control device
subject to the provisions of this section shall be designed and constructed to
allow measurement of emissions using applicable test methods and
procedures.
(h) Where emissions
from any EAF or AOD vessel are combined with emissions from facilities not
subject to the provisions of this section but controlled by a common capture
system and control device the owner or operator may use any of the following
procedures during a performance test:
1. Base
compliance on control of the combined emissions;
2. Utilize a method acceptable to the
department that compensates for the emissions from the facilities not subject
to the provisions of this section or;
3. Any combination of the criteria of subd.
1. and 2.
(i) Where
emissions from any EAF or AOD vessel are combined with emissions from
facilities not subject to the provisions of this section determinations of
compliance with sub. (3) (a) 3. will only be based upon emissions originating
from the affected facility(ies).
(j) Unless the presence of inclement weather
makes concurrent testing infeasible the owner or operator shall conduct
concurrently the performance tests required under s.
NR 440.08 to
demonstrate compliance with sub. (3) (a) 1., 2. and 3.
(7) RECORDKEEPING AND REPORTING REQUIREMENTS.
(a) Records of the measurements required in
sub. (5) must be retained for at least 2 years following the date of the
measurement.
(b) Each owner or
operator shall submit a written report of exceedances of the control device
opacity to the department semiannually. For the purposes of these reports
exceedances are defined as all 6-minute periods during which the average
opacity is 3% or greater.
(c)
Operation at a furnace static pressure that exceeds the value established under
sub. (5) (g) and either operation of control system fan motor amperes at values
exceeding " 15% of the value established under sub. (5) (c) or operation at
flow rates lower than those established under sub. (5) (c) may be considered by
the department to be unacceptable operation and maintenance of the affected
facility. Operation at such values shall be reported to the department
semiannually.
(e) When the owner or
operator of an EAF or AOD is required to demonstrate compliance with the
standard under sub. (6) (b) 2. or a combination of sub. (6) (b) 1. and 2., the
owner or operator shall obtain approval from the department of the procedure
that will be used to determine compliance. Notification of the procedure to be
used shall be postmarked at least 30 days prior to the performance
test.
(f) For the purpose of this
section the owner or operator shall conduct the demonstration of compliance
with sub. (3) (a) and furnish the department a written report of the results of
the test. This report shall include the following information:
1. Facility name and address;
2. Plant representative;
3. Make and model of process, control device,
and continuous monitoring equipment;
4. Flow diagram of process and emission
capture equipment including other equipment or process(es) ducted to the same
control device;
5. Rated (design)
capacity of process equipment;
6.
Those data required under sub. (5) (h):
a.
List of charge and tap weights and materials;
b. Heat times and process log;
c. Control device operation log;
and
d. Continuous opacity monitor
or reference method data.
7. Test dates and test times;
8. Test company;
9. Test company representative;
10. Test observers from outside
agency;
11. Description of test
methodology used, including any deviation from standard reference
methods;
12. Schematic of sampling
location;
13. Number of sampling
points;
14. Description of sampling
equipment;
15. Listing of sampling
equipment calibrations and procedures;
16. Field and laboratory data
sheets;
17. Description of sample
recovery procedures;
18. Sampling
equipment leak check results;
19.
Description of quality assurance procedures;
20. Description of analytical
procedures;
21. Notation of sample
blank corrections; and
22. Sample
emission calculations.
(g) The owner or operator shall maintain
records of all shop opacity observations in accordance with sub. (4) (d). All
shop opacity observations in excess of the emission limit specified in sub. (3)
(a) 3. shall indicate a period of excess emission, and shall be reported to the
department semi-annually, according to s.
NR 440.07(3).
(h) The owner or operator shall maintain all
the following records for each bag leak detection system required under sub.
(4) (e):
1. Records of the bag leak detection
system output.
2. Records of bag
leak detection system adjustments, including the date and time of the
adjustment, the initial bag leak detection system settings, and the final bag
leak detection system settings.
3.
An identification of the date and time of all bag leak detection system alarms,
the time that procedures to determine the cause of the alarm were initiated, if
procedures were initiated within one hour of the alarm, the cause of the alarm,
an explanation of the actions taken, the date and time the cause of the alarm
was alleviated, and if the alarm was alleviated within 3 hours of the
alarm.