Current through August 26, 2024
(1) APPLICABILITY
AND DESIGNATION OF AFFECTED FACILITY.
(a) The
provisions of this section are applicable to the following affected facilities
in steel plants that produce carbon, alloy, or specialty steels: electric arc
furnaces and dust-handling systems.
(b) The provisions of this section apply to
each affected facility identified under par. (a) that commenced construction,
modification, or reconstruction after October 21, 1974 and on or before August
17, 1983.
(2)
DEFINITIONS. As used in this section, terms not defined in this subsection have
the meanings given in s.
NR 440.02.
(a) "Bag leak
detection system" means a system that is capable of continuously monitoring
relative particulate matter (dust) loadings in the exhaust of a baghouse to
detect bag leaks and other conditions that result in increases in particulate
loadings. A bag leak detection system includes an instrument that operates on
triboelectric, electrodynamic, light scattering, light transmittance, or other
effect to continuously monitor relative particulate matter loadings.
(am) "Capture system" means the equipment
(including ducts, hoods, fans, dampers, etc.) used to capture or transport
particulate matter generated by an EAF to the air pollution control
device.
(b) "Charge" means the
addition of iron and steel scrap or other materials into the top of an electric
arc furnace.
(c) "Charging period"
means the time period commencing at the moment an EAF starts to open and ending
either 3 minutes after the EAF roof is returned to its closed position or 6
minutes after commencement of opening of the roof, whichever is
longer.
(d) "Control device" means
the air pollution control equipment used to remove particulate matter generated
by one or more EAFs from the effluent gas stream.
(e) "Direct shell evacuation control system"
or "DEC system" means any system that maintains a negative pressure within the
EAF above the slag or metal and ducts these emissions to the control
device.
(f) "Dust-handling
equipment" means any equipment used to handle particulate matter collected by
the control device and located at or near the control device for an EAF subject
to this section.
(g) "Electric arc
furnace" or "EAF" means any furnace that produces molten steel and heats the
charge materials with electric arcs from carbon electrodes. Furnaces that
continuously feed direct-reduced iron ore pellets as the primary source of iron
are not affected facilities within the scope of this definition.
(h) "Heat time" means the period commencing
when scrap is charged to an empty EAF and terminating when the EAF tap is
completed.
(i) "Meltdown and
refining" means that phase of the steel production cycle when charge material
is melted and undesirable elements are removed from the metal.
(j) "Meltdown and refining period" means the
time period commencing at the termination of the initial charging period and
ending at the initiation of the tapping period, excluding any intermediate
charging periods and times when power to the EAF is off.
(k) "Shop" means the building which houses
one or more EAFs.
(L) "Shop
opacity" means the arithmetic average of 24 or more opacity observations of
emissions from the shop taken in accordance with Method 9 of 40 CFR part 60, Appendix A, incorporated by reference in s.
NR 440.17, for the applicable time periods.
(m) "Tap" means the pouring of molten steel
from an EAF.
(n) "Tapping period"
means the time period commencing at the moment an EAF begins to pour molten
steel and ending either 3 minutes after steel ceases to flow from an EAF, or 6
minutes after steel begins to flow, whichever is longer.
(3) STANDARD FOR PARTICULATE MATTER.
(a) On and after the date on which the
performance test required to be conducted by s.
NR 440.08 is
completed, no owner or operator subject to the provisions of this section may
cause to be discharged into the atmosphere from an electric arc furnace any
gases which:
1. Exit from a control device
and contain particulate matter in excess of 12 mg/dscm (0.0052
gr/dscf).
2. Exit from a control
device and exhibit 3% opacity or greater.
3. Exit from a shop and, due solely to
operations of any EAFs, exhibit 6% opacity or greater except:
a. Shop opacity less than 20% may occur
during charging periods.
b. Shop
opacity less than 40% may occur during tapping periods.
c. The shop opacity standards of this
subdivision shall apply only during periods when the monitoring parameter
limits specified in sub. (5) (b) are being established according to sub. (5)
(c) and (g), unless the owner or operator elects to perform daily shop opacity
observations in lieu of furnace static pressure monitoring as provided for
under sub. (4) (d).
d. Where the
capture system is operated such that the roof of the shop is closed during the
charge and the tap, and emissions to the atmosphere are prevented until the
roof is opened after completion of the charge or tap, the shop opacity
standards of this subdivision apply when the roof is opened and continue to
apply for the length of time defined by the charging or tapping periods, or
both.
(b) On
and after the date on which the performance test required to be conducted by s.
NR 440.08 is
completed, no owner or operator subject to the provisions of this section may
cause to be discharged into the atmosphere from dust-handling equipment any
gases which exhibit 10% opacity or greater.
(4) EMISSION MONITORING.
(a) A continuous monitoring system for the
measurement of the opacity of emissions discharged into the atmosphere from
control devices shall be installed, calibrated, maintained and operated by the
owner or operator subject to the provisions of this section.
(b) For the purpose of reports under s.
NR 440.07(3), all 6-minute periods
during which the average opacity is 3% or greater shall indicate a period of
excess emission, and shall be reported to the department
semi-annually.
(c) A continuous
monitoring system for the measurement of the opacity of emissions discharged
into the atmosphere from the control device is not required on any modular,
multiple-stack, negative-pressure or positive-pressure fabric filter if
observations of the opacity of the visible emissions from the control device
are performed by a certified visible emissions observer; or on any single-stack
fabric filter if visible emissions from the control device are performed by a
certified visible emission observer and the owner installs and continuously
operates a bag leak detection system according to par. (e). Visible emission
observations shall be conducted at least once per day for at least 3 6-minute
periods when the furnace is operating in the melting and refining period. All
visible emissions observations shall be conducted in accordance with Method 9.
If visible emissions occur from more than one point, the opacity shall be
recorded for any point where visible emissions are observed. Where it is
possible to determine that a number of visible emission sites relate to only
one incident of the visible emission, only one set of 3 6-minute observations
will be required. In that case, Method 9 observations shall be made for the
site of highest opacity that directly relates to the cause, or location, of
visible emissions observed during a single incident. Records shall be
maintained of any 6-minute average that is in excess of the emission limit
specified in sub. (3) (a).
(d) A
furnace static pressure monitoring device is not required on any EAF equipped
with a DEC system if observations of shop opacity are performed by a certified
visible emission observer as follows: Shop opacity observations shall be
conducted at least once per day when the furnace is operating in the meltdown
and refining period. Shop opacity shall be determined as the arithmetic average
of 24 or more consecutive 15-second opacity observations of emissions from the
shop taken in accordance with Method 9. Shop opacity shall be recorded for any
points where visible emissions are observed in proximity to an affected EAF.
Where it is possible to determine that a number of visible emission sites
relate to only one incident of visible emissions, only one observation of shop
opacity shall be required. In this case, the shop opacity observations shall be
made for the site of highest opacity that directly relates to the cause or
location of visible emissions observed during a single incident.
(e) A bag leak detection system shall be
installed and continuously operated on all single-stack fabric filters if the
owner or operator elects not to install and operate a continuous opacity
monitoring system as provided for under par. (c). In addition, the owner or
operator shall meet the visible emissions observation requirements in par. (c).
The bag leak detection system shall meet the specifications and requirements of
subds. 1. to 8.
1. The bag leak detection
system shall be certified by the manufacturer to be capable of detecting
particulate matter emissions at concentrations of one milligram per actual
cubic meter (0.00044 grains per actual cubic foot) or less.
2. The bag leak detection system sensor shall
provide output of relative particulate matter loadings and the owner or
operator shall continuously record the output from the bag leak detection
system using electronic or other means such as a strip chart recorder or a data
logger.
3. The bag leak detection
system shall be equipped with an alarm system that will sound when an increase
in relative particulate loading is detected over the alarm set point
established according to subd. 4., and the alarm shall be located such that it
can be heard by the appropriate plant personnel.
4. For each bag leak detection system
required by this paragraph, the owner or operator shall develop and submit to
the department, for approval, a site-specific monitoring plan that addresses
the items identified in subd. 4. a. to e. For each bag leak detection system
that operates based on the triboelectric effect, the monitoring plan shall be
consistent with the recommendations contained in the EPA guidance document
"Fabric Filter Bag Leak Detection Guidance" (EPA-454/R-98-015). The owner or
operator shall operate and maintain the bag leak detection system according to
the site-specific monitoring plan at all times. The plan shall describe all of
the following:
a. Installation of the bag
leak detection system.
b. Initial
and periodic adjustment of the bag leak detection system including how the
alarm set-point will be established.
c. Operation of the bag leak detection system
including quality assurance procedures.
d. How the bag leak detection system will be
maintained including a routine maintenance schedule and spare parts inventory
list.
e. How the bag leak detection
system output will be recorded and stored.
5. The initial adjustment of the system
shall, at a minimum, consist of establishing the baseline output by adjusting
the sensitivity (range) and the averaging period of the device, and
establishing the alarm set points and the alarm delay time, if
applicable.
6. Following initial
adjustment, the owner or operator may not adjust the averaging period, alarm
set point, or alarm delay time without approval from the department except as
provided for in subd. 6. a. and b.
a. Once
per quarter, the owner or operator may adjust the sensitivity of the bag leak
detection system to account for seasonal effects including temperature and
humidity according to the procedures identified in the site-specific monitoring
plan required under subd. 4.
b. If
opacities greater than zero percent are observed over 4 consecutive 15-second
observations during the daily opacity observations required under par. (c) and
the alarm on the bag leak detection system does not sound, the owner or
operator shall lower the alarm set point on the bag leak detection system to a
point where the alarm would have sounded during the period when the opacity
observations were made.
7. For negative pressure, induced air
baghouses, and positive pressure baghouses that are discharged to the
atmosphere through a stack, the bag leak detection sensor shall be installed
downstream of the baghouse and upstream of any wet scrubber.
8. Where multiple detectors are required, the
system's instrumentation and alarm may be shared among detectors.
(f) For each bag leak detection
system installed according to par. (e), the owner or operator shall initiate
procedures to determine the cause of all alarms within one hour of an alarm.
Except as provided for in par. (g), the cause of the alarm shall be alleviated
within 3 hours of the time the alarm occurred by taking whatever corrective
actions are necessary. Corrective actions may include the following:
1. Inspecting the baghouse for air leaks,
torn or broken bags or filter media, or any other condition that may cause an
increase in particulate emissions.
2. Sealing off defective bags or filter
media.
3. Replacing defective bags
or filter media or otherwise repairing the control device.
4. Sealing off a defective baghouse
compartment.
5. Cleaning the bag
leak detection system probe or otherwise repairing the bag leak detection
system.
6. Shutting down the
process producing the particulate emissions.
(g) In approving the site-specific monitoring
plan required in par. (e) 4., the department may allow owners or operators more
than 3 hours to alleviate specific conditions that cause an alarm if the owner
or operator identifies the condition that could lead to an alarm in the
monitoring plan, adequately explains why it is not feasible to alleviate the
condition within 3 hours of the time the alarm occurred, and demonstrates that
the requested additional time will ensure alleviation of the condition as
expeditiously as practicable.
(5) MONITORING OF OPERATIONS.
(a) The owner or operator subject to the
provisions of this section shall maintain records daily of the following
information:
1. Time and duration of each
charge;
2. Time and duration of
each tap;
3. All flow rate data
obtained under par. (b), or equivalent obtained under
40 CFR
60.274(d); and
4. All pressure data obtained under par.
(f).
(b) Except as
provided under
40 CFR
60.274(d), the owner or
operator subject to the provisions of this section shall check and record on a
once-per-shift basis the furnace static pressure (if a DEC system is in use,
and a furnace static pressure gauge is installed according to par. (f)) and
either: check and record the control system fan motor amperes and damper
positions on a once-per-shift basis; install, calibrate and maintain a
monitoring device that continuously records the volumetric flow rate through
each separately ducted hood; or install, calibrate and maintain a monitoring
device that continuously records the volumetric flow rate at the control device
inlet and check and record damper positions on a once-per-shift basis. The
monitoring devices may be installed in any appropriate location in the exhaust
duct such that reproducible flow rate monitoring will result. Flow rate
monitoring devices shall have an accuracy of + 10% over their normal operating
range and shall be calibrated according to the manufacturer's instructions. The
department may require the owner or operator to demonstrate the accuracy of the
monitoring devices relative to Methods 1 and 2 of 40 CFR part 60, Appendix A,
incorporated by reference in s.
NR 440.17(1).
(c) When the owner or operator of an affected
facility is required to demonstrate compliance with the standard under sub. (3)
(a) 3., and at any other time, the department may require that either: the
control system fan motor amperes and all damper positions, the volumetric flow
rate through each separately ducted hood, or the volumetric flow rate at the
control device inlet and all damper positions shall be determined during all
periods in which the hood is operated for the purpose of capturing emissions
from the affected facility subject to par. (b). The owner or operator may
petition the department for reestablishment of these parameters whenever the
owner or operator can demonstrate to the department's satisfaction that the EAF
operating conditions upon which the parameters were previously established are
no longer applicable. The values of these parameters as determined during the
most recent demonstration of compliance shall be maintained at the appropriate
level for each applicable period. Operation at other than baseline values may
be subject to the requirements of sub. (7) (a).
Note: Under
40 CFR
60.274(d), the owner or
operator may petition the administrator to approve any alternative method that
will provide a continuous record of operation of each emission capture
system.
(e) The owner or
operator shall perform monthly operational status inspections of the equipment
that is important to the performance of the total capture system (i.e.,
pressure sensors, dampers and damper switches). This inspection shall include
observations of the physical appearance of the equipment (e.g., presence of
hole in ductwork or hoods, flow constrictions caused by dents or accumulated
dust in ductwork, and fan erosion). Any deficiencies shall be noted and proper
maintenance performed.
(f) Except
as provided for under sub. (4) (d), where emissions during any phase of the
heat time are controlled by use of a DEC system, the owner or operator shall
install, calibrate and maintain a monitoring device that continuously records
the pressure in the free space inside the EAF. The pressure shall be recorded
as 15-minute integrated averages. The monitoring device may be installed in any
appropriate location in the EAF or DEC system duct prior to the introduction of
ambient air such that reproducible results will be obtained. The pressure
monitoring device shall have an accuracy of ± 5 mm of water gauge over
its normal operating range and shall be calibrated according to the
manufacturer's instructions.
(g)
Except as provided for under sub. (4) (d), when the owner or operator of an EAF
is required to demonstrate compliance with the standard under sub. (3) (a) 3.
and at any other time the department may require, the pressure in the free
space inside the furnace shall be determined during the meltdown and refining
periods using the monitoring device under par. (f). The owner or operator may
petition the department for reestablishment of the 15-minute integrated average
pressure whenever the owner or operator can demonstrate to the department's
satisfaction that the EAF operating conditions upon which the pressures were
previously established are no longer applicable. The pressure determined during
the most recent demonstration of compliance shall be maintained at all times
the EAF is operating in a meltdown and refining period. Operation at higher
pressures may be considered by the department to be unacceptable operation and
maintenance of the affected facility.
(h) Where the capture system is designed and
operated such that all emissions are captured and ducted to a control device,
the owner or operator will not be subject to the requirements of this
subsection.
(i) During any
performance test required under s.
NR 440.08 and
for any report thereof required under sub. (7) (c) or to determine compliance
with sub. (3) (a) 3., the owner or operator shall monitor the following
information for all heats covered by the test:
1. Charge weights and materials, and tap
weights and materials;
2. Heat
times, including start and stop times, and a log of process operation,
including periods of no operation during testing and the pressure inside the
furnace where direct-shell evacuation systems are used;
3. Control device operation log;
and
4. Continuous monitor data or
Method 9 of 40 CFR part 60, Appendix A, incorporated by reference in s.
NR 440.17, data.
(6) TEST METHODS AND PROCEDURES.
(a) During performance tests required in s.
NR 440.08, the
owner or operator may not add gaseous diluent to the effluent gas after the
fabric in any pressurized fabric collector, unless the amount of dilution is
separately determined and considered in the determination of
emissions.
(b) When emissions from
any EAF are combined with emissions from facilities not subject to the
provisions of this section but controlled by a common capture system and
control device, the owner or operator shall use either or both of the following
procedures during a performance test:
Note: See also sub. (7) (b).
1. Determine compliance using the combined
emissions.
2. Use a method that is
acceptable to the department and that compensates for the emissions from the
facilities not subject to the provisions of this section.
(c) When emissions from any EAF are combined
with emissions from facilities not subject to the provisions of this section,
the owner or operator shall use either or both of the following procedures to
demonstrate compliance with sub. (3) (a) 3.:
1. Determine compliance using the combined
emissions.
2. Shut down operation
of facilities not subject to the provisions of this section during the
performance test.
(d) In
conducting the performance tests required in s.
NR 440.08, the
owner or operator shall use as reference methods and procedures the test
methods in Appendix A of 40 CFR part 60, incorporated by reference in s.
NR 440.17, or other methods and procedures as specified
in this subsection, except as provided in s.
NR 440.08(2).
(e) The owner or operator shall determine
compliance with the particulate matter standards in sub. (3) as follows:
1. Method 5 shall be used for
negative-pressure fabric filters and other types of control devices and Method
5D shall be used for positive-pressure fabric filters to determine the
particulate matter concentration and, if applicable, the volumetric flow rate
of the effluent gas. The sampling time and sample volume for each run shall be
at least 4 hours and 4.5 dscm (160 dscf) and, when a single EAF is sampled, the
sampling time shall include an integral number of heats.
2. When more than one control device serves
the EAF being tested, the concentration of particulate matter shall be
determined using the following equation:
See
PDF for diagram
where:
cst is the average concentration of particulate matter,
mg/dscm (gr/dscf)
csi is the concentration of particulate matter from
control device "i", mg/dscm (gr/dscf)
n is the total number of control devices tested
Qsdi is the volumetric flow rate of stack gas from control
device "i", dscm/hr (dscf/hr)
3. Method 9 and the procedures of s.
NR 440.11 shall be used to determine opacity.
4. To demonstrate compliance with sub. (3)
(a) 1. to 3., the Method 9 test runs shall be conducted concurrently with the
particulate matter test runs, unless inclement weather interferes.
(f) To comply with sub. (5) (c),
(f), (g) and (i), the owner or operator shall obtain the information in these
paragraphs during the particulate matter runs.
(g) Where emissions from any EAFs are
combined with emissions from facilities not subject to the provisions of this
section but controlled by a common capture system and control device, the owner
or operator may use any of the following procedures during a performance test:
1. Base compliance on control of the combined
emissions.
2. Utilize a method
acceptable to the department which compensates for the emissions from the
facilities not subject to the provisions of this section.
3. Any combination of the criteria of subds.
1. and 2.
(h) Where
emissions from any EAFs are combined with emissions from facilities not subject
to the provisions of this section, the owner or operator may use any of the
following procedures for demonstrating compliance with sub. (3) (a) 3.:
1. Base compliance on control of the combined
emissions.
2. Shut down operation
of facilities not subject to the provisions of this section.
3. Any combination of the criteria of subds.
1. and 2.
(i) If
visible emissions observations are made in lieu of using a continuous opacity
monitoring system, as allowed for by sub. (4) (c), visible emissions
observations shall be conducted at least once per day for at least 3 6-minute
periods when the furnace is operating in the melting and refining period. All
visible emissions observations shall be conducted in accordance with Method 9.
If visible emissions occur from more than one point, the opacity shall be
recorded for any points where visible emissions are observed. Where it is
possible to determine that a number of visible emission sites relate to only
one incident of the visible emissions, only one set of 3 6-minute observations
shall be required. In that case the Method 9 observations shall be made for the
site of highest opacity that directly relates to the cause, or location, of
visible emissions observed during a single incident. Records shall be
maintained of any 6-minute average that is in excess of the emission limit
specified in sub. (3) (a).
(j)
Unless the presence of inclement weather makes concurrent testing infeasible
the owner or operator shall conduct concurrently the performance tests required
under s.
NR 440.08 to
demonstrate compliance with sub. (3) (a) 1., 2., and 3.
(7) RECORDKEEPING AND REPORTING REQUIREMENTS.
(a) Operation at a furnace static pressure
that exceeds the value established under sub. (5) (g) and either operation of
control system fan motor amperes at values exceeding " 15% of the value
established under sub. (5) (c) or operation at flow rates lower than those
established under sub. (5) (c) may be considered by the department to be
unacceptable operation and maintenance of the affected facility. Operation at
such values shall be reported to the department semiannually.
(b) When the owner or operator of an EAF is
required to demonstrate compliance with the standard under sub. (6) (b) 2. or a
combination of sub. (6) (b) 1. and 2. the owner or operator shall obtain
approval from the department of the procedure that will be used to determine
compliance. Notification of the procedure to be used must be postmarked at
least 30 days prior to the performance test.
(c) For the purpose of this section, the
owner or operator shall conduct the demonstration of compliance with sub. (3)
(a) and furnish the department a written report of the results of the test. The
report shall include the following information:
1. Facility name and address.
2. Plant representative.
3. Make and model of process, control device
and continuous monitoring equipment.
4. Flow diagram of process and emissions
capture equipment including other equipment or processes ducted to the same
control device.
5. Rated design
capacity of process equipment.
6.
The following data required under sub. (5) (i):
a. List of charge and tap weights and
materials.
b. Heat times and
process log.
c. Control device
operation log.
d. Continuous
opacity monitor or Method 9 data.
7. Test dates and test times.
8. Test company.
9. Test company representative.
10. Test observers from outside the
department.
11. Description of test
methodology used, including any deviation from standard reference
methods.
12. Schematic of sampling
location.
13. Number of sampling
points.
14. Description of sampling
equipment.
15. Listing of sampling
equipment calibrations and procedures.
16. Field and laboratory data
sheets.
17. Description of sample
recovery procedures.
18. Sampling
equipment leak check results.
19.
Description of quality assurance procedures.
20. Description of analytical
procedures.
21. Notation of sample
blank corrections.
22. Sample
emission calculations.
(d) The owner or operator shall maintain
records of all shop opacity observations made in accordance with sub. (4) (d).
All shop opacity observations in excess of the emission limit specified in sub.
(3) (a) 3. shall indicate a period of excess emission, and shall be reported to
the department semi-annually, according to s.
NR 440.07(3).
(e) The owner or operator shall maintain all
the following records for each bag leak detection system required under sub.
(4) (e):
1. Records of the bag leak detection
system output.
2. Records of bag
leak detection system adjustments, including the date and time of the
adjustment, the initial bag leak detection system settings, and the final bag
leak detection system settings.
3.
An identification of the date and time of all bag leak detection system alarms,
the time that procedures to determine the cause of the alarm were initiated, if
procedures were initiated within one hour of the alarm, the cause of the alarm,
an explanation of the actions taken, the date and time the cause of the alarm
was alleviated, and if the alarm was alleviated within 3 hours of the
alarm.