Wisconsin Administrative Code
Department of Natural Resources
NR 400-499 - Environmental Protection - Air Pollution Control
Chapter NR 440 - Standards of performance for new stationary sources
Subchapter II - Standards of Performance
Section NR 440.28 - Storage vessels for petroleum liquids for which construction, reconstruction or modification commenced after May 18, 1978, and prior to July 23, 1984
Universal Citation: WI Admin Code ยง NR 440.28
Current through August 26, 2024
(1) APPLICABILITY AND DESIGNATION OF AFFECTED FACILITY.
(a) Except as provided in par. (b), the
affected facility to which this section applies is each storage vessel with a
storage capacity greater than 151,416 liters (40,000 gallons) that is used to
store petroleum liquids for which construction is commenced after May 18,
1978.
(b) Each petroleum liquid
storage vessel with a capacity of less than 1,589,873 liters (420,000 gallons)
used for petroleum or condensate stored, processed, or treated prior to custody
transfer is not an affected facility and, therefore, is exempt from the
requirements of this section.
(c)
1. Owners or operators may choose to comply
with 40 CFR part 65, subpart C, as in effect on December 14, 2000, to satisfy
the requirements of subs. (3) to (5) for storage vessels that are subject to
this section that store petroleum liquies that, as stored, have a maximum true
vapor pressure equal to or greater than 10.3 kPa (1.5 psia). Other provisions
applying to owners or operators who choose to comply with 40 CFR part 65 are
provided in
40
CFR 65.1.
2. Owners or operators who choose to comply
with 40 CFR part 65, subpart C, as in effect on December 14, 2000, shall also
comply with ss.
NR 440.01, 440.02, 440.05, 440.06, 440.07 (1) and (d), 440.14 and for those 440.15 storage
vessels. Any section or subsection from ss.
NR 440.01
to not specified 440.19 in this subdivision does not apply to owners or
operators of storage vessels complying with 40 CFR part 65, subpart C, except
that provisions required to be met prior to implementing 40 CFR part 65 still
apply. Owners and operators who choose to comply with 40 CFR part 65, subpart
C, shall comply with 40 CFR part 65, subpart A, as in effect on December 14,
2000.
(2) DEFINITIONS. As used in this section, terms not defined in this subsection have the meanings given in s. NR 440.02.
(a)
"Condensate" means hydrocarbon liquid separated from natural gas which
condenses due to changes in the temperature or pressure, or both, and remains
liquid at standard conditions.
(b)
"Custody transfer" means the transfer of produced petroleum or condensate, or
both, after processing or treating, or both, in the producing operations, from
storage tanks or automatic transfer facilities to pipelines or any other forms
of transportation.
(c)
"Liquid-mounted seal" means a foam or liquid-filled primary seal mounted in
contact with the liquid between the tank wall and the floating roof
continuously around the circumference of the tank.
(d) "Metallic shoe seal" includes but is not
limited to a metal sheet held vertically against the tank wall by springs or
weighted levers and is connected by braces to the floating roof. A flexible
coated fabric (envelope) spans the annular space between the metal sheet and
the floating roof.
(e) "Petroleum"
means the crude oil removed from the earth and the oils derived from tar sands,
shale and coal.
(f) "Petroleum
liquids" means petroleum, condensate, and any finished or intermediate products
manufactured in a petroleum refinery but does not mean Nos. 2 through 6 fuel
oils as specified in ASTM D396-98, gas turbine fuel oils Nos. 2-GT through 4-GT
as specified in ASTM D2880-96, or diesel fuel oils Nos. 2-D and 4-D as
specified in ASTM D975-98a. These 3 ASTM methods are incorporated by reference
in s.
NR 440.17(2) (a) 13., 36. and 14.,
respectively.
(g) "Petroleum
refinery" means each facility engaged in producing gasoline, kerosene,
distillate fuel oils, residual fuel oils, lubricants, or other products through
distillation of petroleum or through redistillation, cracking, extracting or
reforming of unfinished petroleum derivatives.
(h) "Reid vapor pressure" is the absolute
vapor pressure of volatile crude oil and volatile nonviscous petroleum liquids,
except liquified petroleum gases, as determined by ASTM D323-94, incorporated
by reference in s.
NR 440.17(2) (a) 11.
(i) "Storage vessel" means each tank,
reservoir or container used for the storage of petroleum liquids, but does not
include:
1. Pressure vessels which are
designed to operate in excess of 204.9 kPa (15 psig) without emissions to the
atmosphere except under emergency conditions.
2. Subsurface caverns or porous rock
reservoirs, or
3. Underground tanks
if the total volume of petroleum liquids added to and taken from the tank
annually does not exceed twice the volume of the tank.
(j) "True vapor pressure" means the
equilibrium partial pressure exerted by a petroleum liquid such as determined
in accordance with methods described in American Petroleum Institute
Publication 2517, Evaporation Loss from External Floating Roof Tanks, Second
Edition, February 1980, incorporated by reference in s.
NR 440.17.
(k) "Vapor-mounted seal" means a foam-filled
primary seal mounted continuously around the circumference of the tank so there
is an annular vapor space underneath the seal. The annular vapor space is
bounded by the bottom of the primary seal, the tank wall, the liquid surface,
and the floating roof.
(3) STANDARD FOR VOLATILE ORGANIC COMPOUNDS (VOC).
(a) The owner or operator of each
storage vessel to which this section applies which contains a petroleum liquid
which, as stored, has a true vapor pressure equal to or greater than 10.3 kPa
(1.5 psia) but not greater than 76.6 kPa (11.1 psia) shall equip the storage
vessel with one of the following:
1. An
external floating roof, consisting of a pontoon-type or double-deck-type cover
that rests on the surface of the liquid contents and is equipped with a closure
device between the tank wall and the roof edge. Except as provided in subd. 1.
b. 4), the closure device shall consist of 2 seals, one above the other. The
lower seal is referred to as the primary seal and the upper seal is referred to
as the secondary seal. The roof shall be floating on the liquid at all times
(i.e., off the roof leg supports) except during initial fill and when the tank
is completely emptied and subsequently refilled. The process of emptying and
refilling when the roof is resting on the leg supports shall be continuous and
shall be accomplished as rapidly as possible.
a. The primary seal shall be either a
metallic shoe seal, a liquid-mounted seal, or a vapor-mounted seal. Each seal
shall meet the following requirements:
1) The
accumulated area of gaps between the tank wall and the metallic shoe seal or
the liquid-mounted seal may not exceed 212 cm2 per meter of tank diameter (10.0
in2 per ft of tank diameter) and the width of any portion of any gap may not
exceed 3.81 cm (1.50 in).
2) The
accumulated area of gaps between the tank wall and the vapor-mounted seal may
not exceed 21.1 cm2 per meter of tank diameter (1.0 in2 per ft of tank
diameter) and the width of any portion of any gap may not exceed 1.27 cm (0.50
in).
3) One end of the metallic
shoe shall extend into the stored liquid and the other end shall extend a
minimum vertical distance of 61 cm (24 in) above the stored liquid surface.
4) There may be no holes, tears or
other openings in the shoe, seal fabric or seal envelope.
b. The secondary seal shall meet the
following requirements:
1) The secondary seal
shall be installed above the primary seal so that it completely covers the
space between the roof edge and the tank wall except as provided in subd. 1. b.
2).
2) The accumulated area of
gaps between the tank wall and the secondary seal used in combination with a
metallic shoe or liquid-mounted primary seal may not exceed 21.1 cm2 per meter
of tank diameter (1.0 in2 per ft of tank diameter) and the width of any portion
of any gap may not exceed 1.27cm (0.50 in). There may be no gaps between the
tank wall and the secondary seal used in combination with a vapor-mounted
primary seal.
3) There may be no
holes, tears or other openings in the seal or seal fabric.
4) The owner or operator is exempted from the
requirements for secondary seals and the secondary seal gap criteria when
performing gap measurements or inspections of the primary seal.
c. Each opening in the roof except
for automatic bleeder vents and rim space vents shall provide a projection
below the liquid surface. Each opening in the roof except for automatic bleeder
vents, rim space vents and leg sleeves shall be equipped with a cover, seal or
lid which shall be maintained in a closed position at all times (i.e., no
visible gap) except when the device is in actual use or as described in subd.
1. d. Automatic bleeder vents shall be closed at all times when the roof is
being floated off or is being landed on the roof leg supports. Rim vents shall
be set to open when the roof is being floated off the roof legs supports or at
the manufacturer's recommended setting.
d. Each emergency roof drain shall be
provided with a slotted membrane fabric cover that covers at least 90% of the
area of the opening.
2.
A fixed roof with an internal floating type cover equipped with a continuous
closure device between the tank wall and the cover edge. The cover shall be
floating at all times (i.e., off the leg supports), except during initial fill
and when the tank is completely emptied and subsequently refilled. The process
of emptying and refilling when the cover is resting on the leg supports shall
be continuous and shall be accomplished as rapidly as possible. Each opening in
the cover except for automatic bleeder vents and the rim space vents shall
provide a projection below the liquid surface. Each opening in the cover except
for automatic bleeder vents, rim space vents, stub drains and leg sleeves shall
be equipped with a cover, seal or lid which shall be maintained in a closed
position at all times (i.e., no visible gap) except when the device is in
actual use. Automatic bleeder vents shall be closed at all times when the cover
is floating except when the cover is being floated off or is being landed on
the leg supports. Rim vents shall be set to open only when the cover is being
floated off the leg supports or at the manufacturer's recommended
setting.
3. A vapor recovery system
which collects all VOC vapors and gases discharged from the storage vessel, and
a vapor return or disposal system which is designed to process such VOC vapors
and gases so as to reduce their emission to the atmosphere by at least 95% by
weight.
4. A system equivalent to
those described in subd. 1., 2. or 3. as provided in sub. (5).
(b) The owner or operator of each
storage vessel to which this section applies which contains a petroleum liquid
which, as stored, has a true vapor pressure greater than 76.6 kPa (11.1 psia),
shall equip the storage vessel with a vapor recovery system which collects all
VOC vapors and gases discharged from the storage vessel, and a vapor return or
disposal system which is designed to process such VOC vapors and gases so as to
reduce their emission to the atmosphere by at least 95% by weight.
(4) TESTING AND PROCEDURES.
(a) Except as provided in s.
NR 440.08(2), compliance with the
standard prescribed in sub. (3) shall be determined as follows or in accordance
with an equivalent procedure as provided in sub. (5).
1. The owner or operator of each storage
vessel to which this section applies which has an external floating roof shall
meet the following requirements:
a. Determine
the gap areas and maximum gap widths between the primary seal and the storage
vessel wall, and between the secondary seal and the storage vessel wall
according to the following frequency:
1) For
primary seals, gap measurements shall be performed within 60 days of the
initial fill with petroleum liquid and at least once every 5 years thereafter.
All primary seal inspections or gap measurements which require the removal or
dislodging of the secondary seal shall be accomplished as rapidly as possible
and the secondary seal shall be replaced as soon as possible.
2) For secondary seals, gap measurements
shall be performed within 60 days of the initial fill with petroleum liquid and
at least once every year thereafter.
3) If any storage vessel is out of service
for a period of one year or more, subsequent refilling with petroleum liquid
shall be considered initial fill for the purposes of subd. 1. a. 1) and 2).
4) Keep records of each gap
measurement at the plant for a period of at least 2 years following the date of
measurement. Each record shall identify the vessel on which the measurement was
performed and shall contain the date of the seal gap measurement, the raw data
obtained in the measurement process required by subd. 1. b. and the calculation
required by subd. 1. c.
5) If
either the seal gap calculated in accord with subd. 1. c. or the measured
maximum seal gap exceeds the limitations specified by sub. (3), a report shall
be furnished to the department within 60 days of the date of the measurement.
The report shall identify the vessel and list each reason why the vessel did
not meet the specifications of sub. (3). the report shall also describe the
actions necessary to bring the storage vessel into compliance with the
specifications of sub. (3).
b. Determine gap widths in the primary and
secondary seals individually by the following procedures:
1) Measure seal gaps, if any, at one or more
floating roof levels when the roof is floating off the roof leg supports.
2) Measure seal gaps around the
entire circumference of the tank in each place where a 1/8¶ diameter
uniform probe passes freely (without forcing or binding against seal) between
the seal and the tank wall and measure the circumferential distance of each
such location.
3) The total
surface area of each gap described in subd. 1. b. 2) shall be determined by
using probes of various widths to accurately measure the actual distance from
the tank wall to the seal and multiplying each such width by its respective
circumferential distance.
c. Add the gap surface area of each gap
location for the primary seal and the secondary seal individually. Divide the
sum for each seal by the nominal diameter of the tank and compare each ratio to
the appropriate ratio in the standard in sub. (3) (a) 1. a. and b.
d. Provide the department 30 days prior
notice of the gap measurement to afford it the opportunity to have an observer
present.
2. The owner or
operator of each storage vessel to which this section applies which has a vapor
recovery and return or disposal system shall provide the following information
to the department on or before the date on which construction of the storage
vessel commences:
a. Emission data, if
available, for a similar vapor recovery and return or disposal system used on
the same type of storage vessel, which can be used to determine the efficiency
of the system. A complete description of the emission measurement method used
shall be included.
b. The
manufacturer's design specifications and estimated emission reduction
capability of the system.
c. The
operation and maintenance plan for the system.
d. Any other information which will be useful
to the department in evaluating the effectiveness of the system in reducing VOC
emissions.
(5) ALTERNATIVE MEANS OF EMISSION LIMITATION.
(a) If, in the administrator's judgment, an
alternative means of emission limitation will achieve a reduction in emissions
at least equivalent to the reduction in emissions achieved by any requirements
in sub. (3), the administrator will publish in the federal register a notice
permitting the use of the alternative means for purpose of compliance with that
requirement.
(b) Any notice under
par. (a) will be published only after notice and an opportunity for a hearing.
(c) Any person seeking permission
to use an alternative means of emission limitation under this subsection shall
submit to the administrator a written application including:
1. An actual emissions test that uses a
full-sized or scale-model storage vessel that accurately collects and measures
all VOC emissions from a given control device and that accurately simulates
wind and accounts for other emission variables such as temperature and
barometric pressure.
2. An
engineering evaluation that the administrator determines is an accurate method
of determining equivalence.
(d) The administrator may condition the
permission on requirements that may be necessary to ensure operation and
maintenance to achieve the same emissions reduction as specified in sub.
(3).
(e) The primary vapor-mounted
seal in the "Volume-Maximizing Seal" manufactured by R.F.I. Services
Corporation is approved as equivalent to the vapor-mounted seal required by
sub. (3) (a) 1. a. and shall meet the gap criteria specified in sub. (3) (a) 1.
a. 2). There may be no gaps between the tank wall and any secondary seal used
in conjunction with the primary seal in the "Volume-Maximizing Seal."
(6) MONITORING OF OPERATIONS.
(a) Except as provided in par.
(d), the owner or operator subject to this section shall maintain a record of
the petroleum liquid stored, the period of storage, and the maximum true vapor
pressure of that liquid during the respective storage period.
(b) Available data on the typical Reid vapor
pressure and the maximum expected storage temperature of the stored product may
be used to determine the maximum true vapor pressure from nomographs contained
in API Publication 2517, incorporated by reference in s.
NR 440.17, unless the department specifically requests
that the liquid be sampled, the actual storage temperature determined, and the
Reid vapor pressure determined from samples.
(c) The true vapor pressure of each type of
crude oil with a Reid vapor pressure less than 13.8 kPa (2.0 psia) or whose
physical properties preclude determination by the recommended method shall be
determined from available data and recorded if the estimated true vapor
pressure is greater than 6.9 kPa (1.0 psia).
(d) The following are exempt from the
requirements of this subsection:
1. Each owner
or operator of each storage vessel storing a petroleum liquid with a Reid vapor
pressure of less than 6.9 kPa (1.0 psia) provided the maximum true vapor
pressure does not exceed 6.9 kPa (1.0 psia).
2. Each owner or operator of each storage
vessel equipped with a vapor recovery and return or disposal system in
accordance with the requirements of sub. (3) (a) 3. and (b), or a closed vent
system and control device meeting the specifications of
40 CFR 65.42(b) (4), (5) or
(c), as in effect on December 14,
2000.
Disclaimer: These regulations may not be the most recent version. Wisconsin may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google
Privacy Policy and
Terms of Service apply.