(1) APPLICABILITY.
(a) Except as provided in pars. (b) to (h),
the affected facility to which this section applies is each individual
hospital/medical/infectious waste incinerator (HMIWI) for which construction is
commenced after June 20, 1996 or for which modification is commenced after
March 16, 1998.
(b) A combustor is
not subject to this section during periods when only pathological waste,
low-level radioactive waste or chemotherapeutic waste is burned alone or in any
combination, provided the owner or operator of the combustor does all of the
following:
1. Notifies the department of an
exemption claim.
2. Keeps records
on a calendar quarter basis of the periods of time when only pathological
waste, low-level radioactive waste or chemotherapeutic waste is burned alone or
in any combination.
(c)
Any co-fired combustor is not subject to this section if the owner or operator
of the co-fired combustor does all of the following:
1. Notifies the department of an exemption
claim.
2. Provides an estimate of
the relative amounts of hospital waste, medical/infectious waste and other
fuels and wastes to be combusted.
3. Keeps records on a calendar quarter basis
of the weight of hospital waste and medical/infectious waste combusted and the
weight of all other fuels and wastes combusted at the co-fired
combustor.
(d) Any
combustor required to have a permit under section 3005 of the Solid Waste
Disposal Act (42
USC 6925), or a license under s.
291.25,
Stats., is not subject to this section.
(e) Any combustor which meets the
applicability requirements under 40 CFR part 60, subpart Cb, or s.
NR 440.215 or 440.216 is not subject to this
section.
(f) Any pyrolysis unit is
not subject to this section.
(g)
Cement kilns firing hospital waste or medical/infectious waste are not subject
to this section.
(h) Physical or
operational changes made to an existing HMIWI solely for the purpose of
complying with emission guidelines under 40 CFR part 60, subpart Ce, are not
considered a modification and do not result in an existing HMIWI becoming
subject to this section.
(j)
Affected facilities subject to this section are not subject to the requirements
of 40 CFR part 64 .
(L) Beginning
September 15, 2000, affected facilities subject to this section shall operate
pursuant to a permit issued under ch. NR 407.
Note: The federal rule,
40 CFR
60.50c(l), requires that an
affected facility operate pursuant to an operating permit issued no later than
the later of September 15, 2000 or the effective date of an EPA approved
operating permit program under Title V of the Act (42
USC 7661 to
7661 f) and 40 CFR
part 70. The department received final interim approval of its operating permit
program on April 5, 1995 and full approval on November 30, 2001. Any permit
issued to an affected facility prior to June 1, 2008, will contain references
to the appropriate federal rule provisions of 40 CFR part 60 subpart Ec.
(2) DEFINITIONS. As used
in this section, all terms not defined in this subsection have the meanings
given in s.
NR 440.02 or, for terms not defined in s.
NR 440.02, the meanings given in s.
NR 400.02. In this section:
(a) "Batch HMIWI" means an HMIWI that is
designed such that neither waste charging nor ash removal can occur during
combustion.
(am) "Biologicals"
means preparations made from living organisms and their products, including
vaccines, cultures, etc., intended for use in diagnosing, immunizing or
treating humans or animals or in research pertaining thereto.
(b) "Blood products" means any product
derived from human blood, including blood plasma, platelets, red or white blood
corpuscles and other derived licensed products, such as interferon, etc.
(bm) "Body fluids" means liquid
emanating or derived from humans and limited to blood; dialysate; amniotic,
cerebrospinal, synovial, pleural, peritoneal and pericardial fluids; and semen
and vaginal secretions.
(c) "Bypass
stack" means a device used for discharging combustion gases to avoid severe
damage to the air pollution control device or other equipment.
(cm) "Chemotherapeutic waste" means waste
material resulting from the production or use of antineoplastic agents used for
the purpose of stopping or reversing the growth of malignant cells.
(d) "Co-fired combustor" means a unit
combusting hospital waste or medical/infectious waste or both with other fuels
or wastes, for example, coal or municipal solid waste, and subject to an
enforceable requirement limiting the unit to combusting a fuel feed stream, 10%
or less of the weight of which is comprised, in aggregate, of hospital waste
and medical/infectious waste as measured on a calendar quarter basis. For
purposes of this definition, pathological waste, chemotherapeutic waste and
low-level radioactive waste are considered "other" wastes when calculating the
percentage of hospital waste and medical/infectious waste combusted.
(dm) "Continuous emission monitoring system"
or "CEMS" means a monitoring system for continuously measuring and recording
the emissions of a pollutant from an affected facility.
(e) "Continuous HMIWI" means an HMIWI that is
designed to allow waste charging and ash removal during combustion.
(em) "Dioxin/furan" means the combined
emissions of tetra- through octa-chlorinated dibenzo-para-dioxins and
dibenzofurans, as measured by Method 23 of 40 CFR part 60, Appendix A,
incorporated by reference in s.
NR 440.17(1).
(f) "Dry scrubber" means an add-on air
pollution control system that injects dry alkaline sorbent (dry injection) or
sprays an alkaline sorbent (spray dryer) to react with and neutralize acid
gases in the HMIWI exhaust stream forming a dry powder material.
(fm) "Fabric filter" or "baghouse" means an
add-on air pollution control system that removes particulate matter and
nonvaporous metals emissions by passing flue gas through filter bags.
(g) "Facilities manager" means the individual
in charge of purchasing, maintaining and operating the HMIWI or the owner's or
operator's representative responsible for the management of the HMIWI.
Alternative titles may include director of facilities or vice president of
support services.
(gm) "High-air
phase" means the stage of the batch operating cycle when the primary chamber
reaches and maintains maximum operating temperatures.
(h) "Hospital" means any facility which has
an organized medical staff, maintains at least 6 inpatient beds, and where the
primary function of the institution is to provide diagnostic and therapeutic
patient services and continuous nursing care primarily to human inpatients who
are not related and who stay on average in excess of 24 hours per admission.
This definition does not include facilities maintained for the sole purpose of
providing nursing or convalescent care to human patients who generally are not
acutely ill but who require continuing medical supervision.
(hm) "Hospital/medical/infectious waste
incinerator" or "HMIWI" or "HMIWI unit" means any device that combusts any
amount of hospital waste or medical/infectious waste.
(i) "Hospital/medical/infectious waste
incinerator operator" or "HMIWI operator" means any person who operates,
controls or supervises the day-to-day operation of an HMIWI.
(im) "Hospital waste" means discards
generated at a hospital, except unused items returned to the manufacturer. The
definition of hospital waste does not include human corpses, remains and
anatomical parts that are intended for interment or cremation.
(j) "Infectious agent" means any organism,
such as a virus or bacteria, that is capable of being communicated by invasion
and multiplication in body tissues and capable of causing disease or adverse
health impacts in humans.
(jm)
"Intermittent HMIWI" means an HMIWI that is designed to allow waste charging,
but not ash removal, during combustion.
(k) "Large HMIWI" means an HMIWI whose
maximum design waste burning capacity is more than 500 pounds per hour, a
continuous or intermittent HMIWI whose maximum charge rate is more than 500
pounds per hour or a batch HMIWI whose maximum charge rate is more than 4,000
pounds per day. A continuous or intermittent HMIWI whose maximum charge rate is
less than or equal to 500 pounds per hour, or a batch HMIWI whose maximum
charge rate is less than or equal to 4,000 pounds per day, is not a large
HMIWI.
(km) "Low-level radioactive
waste" means waste material which contains radioactive nuclides emitting
primarily beta or gamma radiation, or both, in concentrations or quantities
that exceed applicable federal or state standards for unrestricted release.
Low-level radioactive waste is not high-level radioactive waste, spent nuclear
fuel or byproduct material as defined by the Atomic Energy Act of 1954 (42
USC 2014(e) (2)).
(L) "Malfunction" means any
sudden, infrequent and not reasonably preventable failure of air pollution
control equipment, process equipment or a process to operate in a normal or
usual manner. Failures that are caused, in part, by poor maintenance or
careless operation are not malfunctions. During periods of malfunction the
operator shall operate within established parameters as much as possible, and
monitoring of all applicable operating parameters shall continue until all
waste has been combusted or until the malfunction ceases, whichever comes
first.
(Lm) "Maximum charge rate"
means the following:
1. For continuous and
intermittent HMIWI, 110% of the lowest 3-hour average charge rate measured
during the most recent performance test demonstrating compliance with all
applicable emission limits.
2. For
batch HMIWI, 110% of the lowest daily charge rate measured during the most
recent performance test demonstrating compliance with all applicable emission
limits.
(m) "Maximum
design waste burning capacity" means the following:
1. For intermittent and continuous HMIWI,
C = PV x 15,000/8,500
where:
C is the HMIWI capacity, lb/hr
PV is the primary chamber volume, ft3
15,000 is the primary chamber heat release rate factor,
Btu/ft3/hr
8,500 is the standard waste heating value, Btu/lb
2. For batch HMIWI,
C = PV x 4.5/8
where:
C is the HMIWI capacity, lb/hr
PV is the primary chamber volume, ft3
4.5 is the waste density, lb/ft3
8 is the typical hours of operation of a batch HMIWI,
hours
(mm)
"Maximum fabric filter inlet temperature" means 110% of the lowest 3-hour
average temperature at the inlet to the fabric filter, taken at a minimum once
every minute, measured during the most recent performance test demonstrating
compliance with the dioxin/furan emission limit.
(n) "Maximum flue gas temperature" means 110%
of the lowest 3-hour average temperature at the outlet from the wet scrubber,
taken at a minimum once every minute, measured during the most recent
performance test demonstrating compliance with the mercury emission
limit.
(nm) "Medical/infectious
waste" means any waste generated in the diagnosis, treatment or immunization of
human beings or animals, in research pertaining thereto, or in the production
or testing of biologicals that are listed in subds. 1. to 7. Medical/infectious
waste does not include hazardous waste identified or listed under the
regulations in 40 CFR part 261 ; household waste as defined in
40
CFR 261.4(b) (1); ash from
incineration of medical/infectious waste, once the incineration process has
been completed; human corpses, remains, and anatomical parts that are intended
for internment or cremation; and domestic sewage materials identified in
40
CFR 261.4(a) (1).
1. Cultures and stocks of infectious agents
and associated biologicals, including cultures from medical and pathological
laboratories; cultures and stocks of infectious agents from research and
industrial laboratories; wastes from the production of biologicals; discarded
live and attenuated vaccines; and culture dishes and devices used to transfer,
inoculate and mix cultures.
2.
Human pathological waste, including tissues, organs, and body parts and body
fluids that are removed during surgery or autopsy, or other medical procedures,
and specimens of body fluids and their containers.
3. Human blood and blood products including
all of the following:
a. Liquid waste human
blood.
b. Products of
blood.
c. Items saturated or
dripping with human blood.
d. Items
that were saturated or dripping with human blood that are now caked with dried
human blood; including serum, plasma, and other blood components, and their
containers, which were used or intended for use in either patient care, testing
and laboratory analysis or the development of pharmaceuticals. Intravenous bags
are also include in this category.
4. Sharps that have been used in animal or
human patient care or treatment or in medical, research or industrial
laboratories, including hypodermic needles, syringes with or without the
attached needle, pasteur pipettes, scalpel blades, blood vials, needles with
attached tubing and culture dishes regardless of presence of infectious agents.
Also included are other types of broken or unbroken glassware that were in
contact with infectious agents, such as used slides and cover slips.
5. Animal waste including contaminated animal
carcasses, body parts and bedding of animals that were known to have been
exposed to infectious agents during research, including research in veterinary
hospitals, production of biologicals or testing of pharmaceuticals.
6. Isolation wastes including biological
waste and discarded materials contaminated with blood, excretions, exudates or
secretions from humans who are isolated to protect others from certain highly
communicable diseases, or isolated animals known to be infected with highly
communicable diseases.
7. Unused
sharps including the following unused, discarded sharps: hypodermic needles,
suture needles, syringes and scalpel blades.
(o) "Medium HMIWI" means an HMIWI whose
maximum design waste burning capacity is more than 200 pounds per hour but less
than or equal to 500 pounds per hour, a continuous or intermittent HMIWI whose
maximum charge rate is more than 200 pounds per hour but less than or equal to
500 pounds per hour, or a batch HMIWI whose maximum charge rate is more than
1,600 pounds per day but less than or equal to 4,000 pounds per day. A
continuous or intermittent HMIWI whose maximum charge rate is less than or
equal to 200 pounds per hour or more than 500 pounds per hour or a batch HMIWI
whose maximum charge rate is more than 4,000 pounds per day or less than or
equal to 1,600 pounds per day is not a medium HMIWI.
(om) "Minimum dioxin/furan sorbent flow rate"
means 90% of the highest 3-hour average dioxin/furan sorbent flow rate, taken
at a minimum once every hour, measured during the most recent performance test
demonstrating compliance with the dioxin/furan emission limit.
(p) "Minimum mercury sorbent flow rate" means
90% of the highest 3-hour average mercury sorbent flow rate, taken at a minimum
once every hour, measured during the most recent performance test demonstrating
compliance with the mercury emission limit.
(pm) "Minimum hydrogen chloride sorbent flow
rate" means 90% of the highest 3-hour average hydrogen chloride (HCl) sorbent
flow rate, taken at a minimum once every hour, measured during the most recent
performance test demonstrating compliance with the HCl emission
limit.
(q) "Minimum horsepower or
amperage" means 90% of the highest 3-hour average horsepower or amperage to the
wet scrubber, taken at a minimum once every minute, measured during the most
recent performance test demonstrating compliance with the applicable emission
limits.
(qm) "Minimum pressure
drop across the wet scrubber" means 90% of the highest 3-hour average pressure
drop across the wet scrubber PM control device, taken at a minimum once every
minute, measured during the most recent performance test demonstrating
compliance with the PM emission limit.
(r) "Minimum scrubber liquor flow rate" means
90% of the highest 3-hour average liquor flow rate at the inlet to the wet
scrubber, taken at a minimum once every minute, measured during the most recent
performance test demonstrating compliance with all applicable emission limits.
(rm) "Minimum scrubber liquor pH"
means 90% of the highest 3-hour average liquor pH at the inlet to the wet
scrubber, taken at a minimum once every minute, measured during the most recent
performance test demonstrating compliance with the HCl emission
limit.
(s) "Minimum secondary
chamber temperature" means 90% of the highest 3-hour average secondary chamber
temperature, taken at a minimum once every minute, measured during the most
recent performance test demonstrating compliance with the PM, CO or
dioxin/furan emission limits.
(sm)
"Modification" or "modified HMIWI" means any changes to an HMIWI unit after
September 15, 1997 if the cumulative costs of the changes, over the life of the
unit, exceed 50% of the original cost of the construction and installation of
the unit, not including the cost of any land purchased in connection with the
construction or installation, updated to current costs; or any physical change
in, or change in the method of operation of the unit which increases the amount
of any air pollutant emitted by the unit for which standards have been
established under section 111 or 129 of the Act (42 USC
7411 or
7429).
(t) "Operating day" means a
24-hour period between 12:00 midnight and the following midnight during which
any amount of hospital waste or medical/infectious waste is combusted at any
time in the HMIWI.
(tm) "Operation"
means the period during which waste is combusted in the incinerator excluding
periods of startup or shutdown.
(u)
"Particulate matter" or "PM" means the total particulate matter emitted from an
HMIWI as measured by Method 5 or Method 29 of 40 CFR part 60, Appendix A,
incorporated by reference in s.
NR 440.17(1).
(um) "Pathological waste" means waste
material consisting of only human or animal remains, anatomical parts or
tissue; the bags or containers used to collect and transport the waste
material; and animal bedding if applicable.
(v) "Primary chamber" means the chamber in an
HMIWI that receives waste material, in which the waste is ignited, and from
which ash is removed.
(vm)
"Pyrolysis" means the endothermic gasification of hospital waste or
medical/infectious waste using external energy.
(w) "Secondary chamber" means a component of
the HMIWI that receives combustion gases from the primary chamber and in which
the combustion process is completed.
(wm) "Shutdown" means the period of time
after all waste has been combusted in the primary chamber. For continuous
HMIWI, shutdown shall commence no less than 2 hours after the last charge to
the incinerator. For intermittent HMIWI, shutdown shall commence no less than 4
hours after the last charge to the incinerator. For batch HMIWI, shutdown shall
commence no less than 5 hours after the high-air phase of combustion has been
completed.
(x) "Small HMIWI" means
an HMIWI whose maximum design waste burning capacity is less than or equal to
200 pounds per hour, a continuous or intermittent HMIWI whose maximum charge
rate is less than or equal to 200 pounds per hour, or a batch HMIWI whose
maximum charge rate is less than or equal to 1,600 pounds per day. A continuous
or intermittent HMIWI whose maximum charge rate is more than 200 pounds per
hour or a batch HMIWI whose maximum charge rate is more than 1,600 pounds per
day is not a small HMIWI.
(xm)
"Standard conditions" means a temperature of 205C and a pressure of 101.3
kilopascals.
(y) "Startup" means
the period of time between the activation of the system and the first charge to
the unit. For batch HMIWI, startup means the period of time between activation
of the system and ignition of the waste.
(ym) "Wet scrubber" means an add-on air
pollution control device that utilizes an alkaline scrubbing liquor to collect
particulate matter, including nonvaporous metals and condensed organics, or to
absorb and neutralize acid gases.
(4)
OPERATOR TRAINING AND QUALIFICATION REQUIREMENTS.
(a) No owner or operator of an affected
facility may allow the affected facility to operate at any time unless a fully
trained and qualified HMIWI operator is accessible, either at the facility or
available within one hour. The trained and qualified HMIWI operator may operate
the HMIWI directly or be the direct supervisor of one or more HMIWI
operators.
(b) Operator training
and qualification shall be obtained through ch. NR 499 or by completing all of
the requirements included in pars. (c) to (g).
(c) Training shall be obtained by completing
an HMIWI operator training course that includes, at a minimum, all of the
following provisions:
1. Twenty four hours of
training on the following subjects:
a.
Environmental concerns, including pathogen destruction and types of
emissions.
b. Basic combustion
principles, including products of combustion.
c. Operation of the type of incinerator to be
used by the operator, including proper startup, waste charging and shutdown
procedures.
d. Combustion controls
and monitoring.
e. Operation of air
pollution control equipment and factors affecting performance, if
applicable.
f. Methods to monitor
pollutants (continuous emission monitoring systems and monitoring of HMIWI and
air pollution control device operating parameters) and equipment calibration
procedures, where applicable.
g.
Inspection and maintenance of the HMIWI, air pollution control devices and
continuous emission monitoring systems.
h. Actions to correct malfunctions or
conditions that may lead to malfunction.
i. Bottom and fly ash characteristics and
handling procedures.
j. Applicable
federal, state and local regulations.
k. Work safety procedures.
L. Pre-startup inspections.
m. Recordkeeping requirements.
2. An examination designed and
administered by the instructor.
3.
Reference material distributed to the attendees covering the course
topics.
(d)
Qualification shall be obtained by satisfying all of the following:
1. Completion of a training course that
satisfies the criteria under par. (c).
2. Either 6 months experience as an HMIWI
operator, 6 months experience as a direct supervisor of an HMIWI operator, or
completion of at least 2 burn cycles under the observation of 2 qualified HMIWI
operators.
(e)
Qualification is valid from the date on which the examination is passed or the
completion of the required experience, whichever is later.
(f) To maintain qualification, the trained
and qualified HMIWI operator shall complete and pass an annual review or
refresher course of at least 4 hours covering, at a minimum, all of the
following:
1. Update of
regulations.
2. Incinerator
operation, including startup and shutdown procedures.
3. Inspection and maintenance.
4. Responses to malfunctions or conditions
that may lead to malfunction.
5.
Discussion of operating problems encountered by attendees.
(g) A lapsed qualification shall be renewed
by one of the following methods:
1. For a
lapse of less than 3 years, the HMIWI operator shall complete and pass a
standard annual refresher course described in par. (f).
2. For a lapse of 3 years or more, the HMIWI
operator shall complete and pass a training course with the minimum criteria
described in par. (c).
(h) The owner or operator of an affected
facility shall maintain documentation at the facility that addresses all of the
following:
1. Summary of the applicable
standards under this section.
2.
Description of basic combustion theory applicable to an HMIWI.
3. Procedures for receiving, handling and
charging waste.
4. HMIWI startup,
shutdown and malfunction procedures.
5. Procedures for maintaining proper
combustion air supply levels.
6.
Procedures for operating the HMIWI and associated air pollution control systems
within the standards established under this section.
7. Procedures for responding to periodic
malfunction or conditions that may lead to malfunction.
8. Procedures for monitoring HMIWI
emissions.
9. Reporting and
recordkeeping procedures.
10.
Procedures for handling ash.
(i) The owner or operator of an affected
facility shall establish a program for reviewing the information listed in par.
(h) annually with each HMIWI operator as follows:
1. The initial review of the information
listed in par. (h) shall be conducted within 6 months after the effective date
of this section or prior to assumption of responsibilities affecting HMIWI
operation, whichever date is later.
2. Subsequent reviews of the information
listed in par. (h) shall be conducted annually.
(j) The information listed in par. (h) shall
be kept in a readily accessible location for all HMIWI operators. This
information, along with records of training, shall be available for inspection
by the EPA or department upon request.
(7) COMPLIANCE AND PERFORMANCE TESTING.
(a) The emission limits under this section
apply at all times except during periods of startup, shutdown or malfunction,
provided that no hospital waste or medical/infectious waste is charged to the
affected facility during startup, shutdown or malfunction.
(b) The owner or operator of an affected
facility shall conduct an initial performance test as required under s.
NR 440.08 to
determine compliance with the emission limits using the procedures and test
methods listed in subds. 1. to 12. The use of the bypass stack during a
performance test shall invalidate the performance test. The procedures and test
methods are as follows:
1. All performance
tests shall consist of a minimum of 3 test runs conducted under representative
operating conditions.
2. The
minimum sample time shall be one hour per test run unless otherwise
indicated.
3. Method 1 of 40 CFR
part 60, Appendix A, incorporated by reference in s.
NR 440.17(1), shall be used to select
the sampling location and number of traverse points.
4. Method 3, 3A or 3B of 40 CFR part 60,
Appendix A, incorporated by reference in s.
NR 440.17(1), shall be used for gas
composition analysis, including measurement of oxygen concentration. Method 3,
3A or 3B shall be used simultaneously with each reference method.
5. The pollutant concentrations shall be
adjusted to 7% oxygen using the following equation:
See PDF
for diagram
where:
Cadj is the pollutant concentration adjusted to 7% oxygen.
Cmeas is the pollutant concentration measured on a dry
basis
(20.9 - 7) is 20.9% oxygen - 7% oxygen, the defined oxygen
correction basis
20.9 is the oxygen concentration in air, percent
%O2 is the oxygen concentration measured on a dry basis,
percent
6. Method 5 or 29
of 40 CFR part 60, Appendix A, incorporated by reference in s.
NR 440.17(1), shall be used to measure
the particulate matter emissions.
7. Method 9 of 40 CFR part 60, Appendix A,
incorporated by reference in s.
NR 440.17(1), shall be used to measure
stack opacity.
8. Method 10 or 10B
of 40 CFR part 60, Appendix A, incorporated by reference in s.
NR 440.17(1), shall be used to measure
the carbon monoxide emissions.
9.
Method 23 of 40 CFR part 60, Appendix A, incorporated by reference in s.
NR 440.17(1), shall be used to measure
total dioxin/furan emissions. The minimum sample time shall be 4 hours per test
run. If the affected facility has selected the toxic equivalency standards for
dioxin/furan, under sub. (3), the following procedures shall be used to
determine compliance:
a. Measure the
concentration of each dioxin/furan tetra- through octa- congener emitted using
Method 23.
b. For each dioxin/furan
congener measured in accordance with subd. 9. a., multiply the congener
concentration by its corresponding toxic equivalency factor specified in Table
2.
c. Sum the products calculated
in accordance with subd. 9. b. to obtain the total concentration of
dioxin/furan emitted in terms of toxic equivalency.
10. Method 26 or 26A of 40 CFR part 60,
Appendix A, incorporated by reference in s.
NR 440.17(1), shall be used to measure
hydrogen chloride emissions. If the affected facility has selected the
percentage reduction standards for hydrogen chloride under sub. (3), the
percentage reduction in hydrogen chloride emissions (%RHCl) shall be computed
using the following formula:
See PDF
for diagram
where:
%RHCl is the percentage reduction of hydrogen chloride
emissions achieved
Ei is the hydrogen chloride emission concentration
measured at the control device inlet, corrected to 7% oxygen, dry basis
Eo is the hydrogen chloride emission concentration
measured at the control device outlet, corrected to 7% oxygen, dry basis
11. Method 29 of 40 CFR
part 60, Appendix A, incorporated by reference in s.
NR 440.17(1), shall be used to measure
lead, cadmium and mercury emissions. If the affected facility has selected the
percentage reduction standards for metals under sub. (3), the percentage
reduction in emissions (%Rmetal) shall be computed using the following formula:
See PDF
for diagram
where:
%Rmetal is the percentage reduction of metal emission of
lead, cadmium or mercury achieved
Ei is the metal emission concentration of lead, cadmium or
mercury, measured at the control device inlet, corrected to 7% oxygen, dry
basis
Eo is the metal emission concentration of lead, cadmium or
mercury, measured at the control device outlet, corrected to 7% oxygen, dry
basis
12. Method 22 of 40
CFR part 60, Appendix A, incorporated by reference in s.
NR 440.17(1), shall be used to determine
compliance with the fugitive ash emission limit under sub. (3) (c). The minimum
observation time shall be a series of 3 1-hour observations.
(c) Following the date on which
the initial performance test is completed or is required to be completed under
s.
NR 440.08,
whichever date comes first, the owner or operator of an affected facility shall
do the following, as applicable:
1. Determine
compliance with the opacity limit by conducting an annual performance test, no
more than 12 months following the previous performance test, using the
applicable procedures and test methods listed in par. (b).
2. Determine compliance with the particulate
matter, carbon monoxide and hydrogen chloride emission limits by conducting an
annual performance test, no more than 12 months following the previous
performance test, using the applicable procedures and test methods listed in
par. (b). If all 3 performance tests over a 3-year period indicate compliance
with the emission limit for a pollutant (particulate matter, carbon monoxide or
hydrogen chloride), the owner or operator may forego a performance test for
that pollutant for the subsequent 2 years. At a minimum, a performance test for
particulate matter, carbon monoxide and hydrogen chloride shall be conducted
every third year, no more than 36 months following the previous performance
test. If a performance test conducted every third year indicates compliance
with the emission limit for a pollutant (particulate matter, carbon monoxide or
hydrogen chloride), the owner or operator may forego a performance test for
that pollutant for an additional 2 years. If any performance test indicates
noncompliance with the respective emission limit, a performance test for that
pollutant shall be conducted annually until all annual performance tests over a
3-year period indicate compliance with the emission limit. The use of the
bypass stack during a performance test shall invalidate the performance
test.
3. For large HMIWI, determine
compliance with the visible emission limits for fugitive emissions from
flyash/bottom ash storage and handling by conducting a performance test using
Method 22 of 40 CFR part 60, Appendix A, incorporated by reference in s.
NR 440.17(1), on an annual basis, no
more than 12 months following the previous performance test.
4. Facilities using a CEMS to demonstrate
compliance with any of the emission limits under sub. (3) shall do both of the
following:
a. Determine compliance with the
appropriate emission limits using a 12-hour rolling average, calculated each
hour as the average of the previous 12 operating hours, not including startup,
shutdown or malfunction.
b. Operate
all CEMS in accordance with the applicable procedures under 40 CFR part 60,
Appendices B and F, incorporated by reference in s.
NR 440.17(1).
(d) The owner or operator of an
affected facility equipped with a dry scrubber followed by a fabric filter, a
wet scrubber, or a dry scrubber followed by a fabric filter and wet scrubber
shall do both of the following:
1. Establish
the appropriate maximum and minimum operating parameters, indicated in Table 3
for each control system, as site specific operating parameters during the
initial performance test to determine compliance with the emission
limits.
2. Following the date on
which the initial performance test is completed or is required to be completed
under s.
NR 440.08,
whichever date comes first, ensure that the affected facility does not operate
above any of the applicable maximum operating parameters or below any of the
applicable minimum operating parameters listed in Table 3 and measured as
3-hour rolling averages, calculated each hour as the average of the previous 3
operating hours, at all times except during periods of startup, shutdown and
malfunction. Operating parameter limits do not apply during performance tests.
Operation above the established maximum or below the established minimum
operating parameters shall constitute a violation of established operating
parameters.
(e) Except
as provided in par. (h), the following shall constitute a violation of the
emission limit indicated for affected facilities equipped with a dry scrubber
followed by a fabric filter:
1. Operation of
the affected facility above the maximum charge rate and below the minimum
secondary chamber temperature, each measured on a 3-hour rolling average,
simultaneously shall constitute a violation of the carbon monoxide emission
limit.
2. Operation of the affected
facility above the maximum fabric filter inlet temperature, above the maximum
charge rate, and below the minimum dioxin/furan sorbent flow rate, each
measured on a 3-hour rolling average, simultaneously shall constitute a
violation of the dioxin/furan emission limit.
3. Operation of the affected facility above
the maximum charge rate and below the minimum hydrogen chloride sorbent flow
rate, each measured on a 3-hour rolling average, simultaneously shall
constitute a violation of the hydrogen chloride emission limit.
4. Operation of the affected facility above
the maximum charge rate and below the minimum mercury sorbent flow rate, each
measured on a 3-hour rolling average, simultaneously shall constitute a
violation of the mercury emission limit.
5. Use of the bypass stack, except during
startup, shutdown or malfunction, shall constitute a violation of the
particulate matter, dioxin/furan, hydrogen chloride, lead, cadmium and mercury
emission limits.
(f)
Except as provided in par. (h), the following shall constitute a violation of
the emission limit indicated for affected facilities equipped with a wet
scrubber:
1. Operation of the affected
facility above the maximum charge rate and below the minimum pressure drop
across the wet scrubber or below the minimum horsepower or amperage to the
system, each measured on a 3-hour rolling average, simultaneously shall
constitute a violation of the particulate matter emission limit.
2. Operation of the affected facility above
the maximum charge rate and below the minimum secondary chamber temperature,
each measured on a 3-hour rolling average, simultaneously shall constitute a
violation of the carbon monoxide emission limit.
3. Operation of the affected facility above
the maximum charge rate, below the minimum secondary chamber temperature, and
below the minimum scrubber liquor flow rate, each measured on a 3-hour rolling
average, simultaneously shall constitute a violation of the dioxin/furan
emission limit.
4. Operation of the
affected facility above the maximum charge rate and below the minimum scrubber
liquor pH, each measured on a 3-hour rolling average, simultaneously shall
constitute a violation of the hydrogen chloride emission limit.
5. Operation of the affected facility above
the maximum flue gas temperature and above the maximum charge rate, each
measured on a 3-hour rolling average, simultaneously shall constitute a
violation of the mercury emission limit.
6. Use of the bypass stack, except during
startup, shutdown or malfunction, shall constitute a violation of the
particulate matter, dioxin/furan, hydrogen chloride, lead, cadmium and mercury
emission limits.
(g)
Except as provided in par. (h), the following shall constitute a violation of
the emission limit indicated for affected facilities equipped with a dry
scrubber followed by a fabric filter and a wet scrubber:
1. Operation of the affected facility above
the maximum charge rate and below the minimum secondary chamber temperature,
each measured on a 3-hour rolling average, simultaneously shall constitute a
violation of the carbon monoxide emission limit.
2. Operation of the affected facility above
the maximum fabric filter inlet temperature, above the maximum charge rate, and
below the minimum dioxin/furan sorbent flow rate, each measured on a 3-hour
rolling average, simultaneously shall constitute a violation of the
dioxin/furan emission limit.
3.
Operation of the affected facility above the maximum charge rate and below the
minimum scrubber liquor pH, each measured on a 3-hour rolling average,
simultaneously shall constitute a violation of the hydrogen chloride emission
limit.
4. Operation of the affected
facility above the maximum charge rate and below the minimum mercury sorbent
flow rate, each measured on a 3-hour rolling average, simultaneously shall
constitute a violation of the mercury emission limit.
5. Use of the bypass stack, except during
startup, shutdown or malfunction, shall constitute a violation of the
particulate matter, dioxin/furan, hydrogen chloride, lead, cadmium and mercury
emission limits.
(h) The
owner or operator of an affected facility may conduct a repeat performance test
within 30 days of violation of an applicable operating parameter to demonstrate
that the affected facility is not in violation of the applicable emission
limits. Repeat performance tests conducted pursuant to this paragraph shall be
conducted using the identical operating parameters that indicated a violation
under par. (e), (f) or (g).
(i) The
owner or operator of an affected facility using an air pollution control device
other than a dry scrubber followed by a fabric filter, a wet scrubber, or a dry
scrubber followed by a fabric filter and a wet scrubber to comply with the
emission limits under sub. (3) shall petition the administrator for other
site-specific operating parameters to be established during the initial
performance test and continuously monitored thereafter. The owner or operator
may not conduct the initial performance test until after the petition has been
approved by the administrator.
(j)
The owner or operator of an affected facility may conduct a repeat performance
test at any time to establish new values for the operating parameters. The
department may request a repeat performance test at any time.
(9)
REPORTING AND RECORDKEEPING REQUIREMENTS.
(a)
The owner or operator of an affected facility shall submit notifications, as
provided by s.
NR 440.07. In addition, the owner or operator shall
submit the following information:
1. Prior to
commencement of construction, all of the following:
a. A statement of intent to
construct.
b. The anticipated date
of commencement of construction.
c.
All documentation produced as a result of the siting requirements of sub.
(5).
2. Prior to initial
startup, all of the following:
a. The types of
waste to be combusted.
b. The
maximum design waste burning capacity.
c. The anticipated maximum charge
rate.
d. If applicable, the
petition for site-specific operating parameters under sub. (7) (i).
(b) The owner or
operator of an affected facility shall maintain the following information, as
applicable, for a period of at least 5 years:
1. Calendar date of each record.
2. Records of the following data:
a. Concentrations of any pollutant listed in
sub. (3) or measurements of opacity as determined by the continuous emission
monitoring system, if applicable.
b. Results of fugitive emissions tests by
Method 22 of 40 CFR part 60, Appendix A, incorporated by reference in s.
NR 440.17(1), if applicable.
c. HMIWI charge dates, times, and weights and
hourly charge rates.
d. Fabric
filter inlet temperatures during each minute of operation, as
applicable.
e. Amount and type of
dioxin/furan sorbent used during each hour of operation, as
applicable.
f. Amount and type of
mercury sorbent used during each hour of operation, as applicable.
g. Amount and type of hydrogen chloride
sorbent used during each hour of operation, as applicable.
h. Secondary chamber temperatures recorded
during each minute of operation.
i.
Liquor flow rate to the wet scrubber inlet during each minute of operation, as
applicable.
j. Horsepower or
amperage to the wet scrubber during each minute of operation, as
applicable.
k. Pressure drop across
the wet scrubber system during each minute of operation, as applicable.
L. Temperature at the outlet from
the wet scrubber during each minute of operation, as applicable.
m. pH at the inlet to the wet scrubber during
each minute of operation, as applicable.
n. Records indicating use of the bypass
stack, including dates, times and durations.
o. For affected facilities complying with
subs. (7) (i) and (8) (c), records of all operating parameter data
collected.
3.
Identification of calendar days for which data on emission rates or operating
parameters specified under subd. 2. have not been obtained, with an
identification of the emission rates or operating parameters not measured,
reasons for not obtaining the data and a description of corrective actions
taken.
4. Identification of
calendar days, times and durations of malfunctions, a description of the
malfunction and the corrective action taken.
5. Identification of calendar days for which
data on emission rates or operating parameters specified under subd. 2.
exceeded the applicable limits, with a description of the exceedances, reasons
for the exceedances, and a description of corrective actions taken.
6. The results of the initial, annual and any
subsequent performance tests conducted to determine compliance with the
emission limits or to establish operating parameters, as applicable.
7. All documentation produced as a result of
the siting requirements of sub. (5).
8. Records showing the names of HMIWI
operators who have completed review of the information in sub. (4) (h) as
required by sub. (4) (i), including the date of the initial review and all
subsequent annual reviews.
9.
Records showing the names of the HMIWI operators who have completed the
operator training requirements, including documentation of training and the
dates of the training.
10. Records
showing the names of the HMIWI operators who have met the criteria for
qualification under sub. (4) and the dates of their qualification.
11. Records of calibration of any monitoring
devices as required under sub. (8) (a), (b) and (c).
(c) The owner or operator of an affected
facility shall submit the information specified in subds. 1. to 3. no later
than 60 days following the initial performance test. All reports shall be
signed by the facility's manager. The information to be submitted is as
follows:
1. The initial performance test data
as recorded under sub. (7) (b) 1. to 12., as applicable.
2. The values for the site-specific operating
parameters established pursuant to sub. (7) (d) or (i), as
applicable.
3. The waste management
plan as specified in sub. (6).
(d) An annual report shall be submitted one
year following the submission of the information in par. (c) and subsequent
reports shall be submitted no more than 12 months following the previous
report, except that once the unit is subject to permitting requirements under
ch. NR 407, the owner or operator of an affected facility shall submit these
reports semiannually. The annual report shall be signed by the facility's
manager and shall include all of the following information:
1. The values for the site-specific operating
parameters established pursuant to sub. (7) (d) or (i), as
applicable.
2. The highest maximum
operating parameter and the lowest minimum operating parameter, as applicable,
for each operating parameter recorded for the calendar year being reported,
pursuant to sub. (7) (d) or (i), as applicable.
3. The highest maximum operating parameter
and the lowest minimum operating parameter, as applicable, for each operating
parameter recorded pursuant to sub. (7) (d) or (i) for the calendar year
preceding the year being reported, in order to provide the department with a
summary of the performance of the affected facility over a 2-year
period.
4. Any information recorded
under par. (b) 3. to 5. for the calendar year being reported.
5. Any information recorded under par. (b) 3.
to 5. for the calendar year preceding the year being reported, in order to
provide the department with a summary of the performance of the affected
facility over a 2-year period.
6.
If a performance test was conducted during the reporting period, the results of
that test.
7. If no exceedances or
malfunctions were reported under par. (b) 3. to 5. for the calendar year being
reported, a statement that no exceedances occurred during the reporting
period.
8. Any use of the bypass
stack, the duration, reason for malfunction and corrective action
taken.
(e) The owner or
operator of an affected facility shall submit semiannual reports containing any
information recorded under par. (b) 3. to 5. no later than 60 days following
the reporting period. The first semiannual reporting period ends 6 months
following the submission of information in par. (c). Subsequent reports shall
be submitted no later than 6 calendar months following the previous report. All
reports shall be signed by the facilities manager.
(f) All records specified under par. (b)
shall be maintained onsite in either paper copy or computer-readable format,
unless an alternative format is approved by the department.
Table 1
Emission Limits For Small, Medium and Large
HMIWI
Pollutant
|
Units (7% oxygen, dry basis)
|
Emission Limits
|
HMIWI Size
|
Small
|
Medium
|
Large
|
1. Particulate matter |
Milligrams per dry standard cubic meter (grains per
dry standard cubic foot) |
69 (0.03) |
34 (0.015) |
34 (0.015) |
2. Carbon monoxide |
Parts per million by volume |
40 |
40 |
40 |
3. Dioxins/furans |
Nanograms per dry standard cubic meter total
dioxins/furans (grains per billion dry standard cubic feet) or nanograms per
dry standard cubic meter total dioxins/furans TEQ (grains per billion dry
standard cubic feet) |
125 (55) or 2.3 (1.0) |
25 (11) or 0.6 (0.26) |
25 (11) or 0.6 (0.26) |
4. Hydrogen chloride |
Parts per million or percent reduction |
15 or 99% |
15 or 99% |
15 or 99% |
5. Sulfur dioxide |
Parts per million by volume |
55 |
55 |
55 |
6. Nitrogen oxides |
Parts per million by volume |
250 |
250 |
250 |
7. Lead |
Milligrams per dry standard cubic meter (grains per
thousand dry standard cubic feet) or percent reduction |
1.2 (0.52) or 70% |
0.07 (0.03) or 98% |
0.07 (0.03) or 98% |
8. Cadmium |
Milligrams per dry standard cubic (grains per
thousand dry standard cubic feet) or percent reduction |
0.16 (0.07) or 65% |
0.04 (0.02) or 90% |
0.04 (0.02) or 90% |
9. Mercury |
Milligrams per dry standard cubic meter (grains per
thousand dry standard cubic feet) or percent reduction |
0.55 (0.24) or 85% |
0.55 (0.24) or 85% |
0.55 (0.24) or 85% |
Table 2
Toxic Equivalency Factors
Dioxin/furan Congener
|
Toxic Equivalency Factor
|
1. 2,3,7,8-tetrachlorinated dibenzo-p-dioxin |
1 |
2. 1,2,3,7,8-pentachlorinated dibenzo-p-dioxin |
0.5 |
3. 1,2,3,4,7,8-hexachlorinated dibenzo-p-dioxin
|
0.1 |
4. 1,2,3,7,8,9-hexachlorinated dibenzo-p-dioxin
|
0.1 |
5. 1,2,3,6,7,8-hexachlorinated dibenzo-p-dioxin
|
0.1 |
6. 1,2,3,4,6,7,8-heptachlorinated dibenzo-p-dioxin
|
0.01 |
7. octachlorinated dibenzo-p-dioxin |
0.001 |
8. 2,3,7,8-tetrachlorinated dibenzofuran |
0.1 |
9. 2,3,4,7,8-pentachlorinated dibenzofuran |
0.5 |
10. 1,2,3,7,8-pentachlorinated dibenzofuran |
0.05 |
11. 1,2,3,4,7,8-hexachlorinated dibenzofuran |
0.1 |
12. 1,2,3,6,7,8-hexachlorinated dibenzofuran |
0.1 |
13. 1,2,3,7,8,9-hexachlorinated dibenzofuran |
0.1 |
14. 2,3,4,6,7,8-hexachlorinated dibenzofuran |
0.1 |
15. 1,2,3,4,6,7,8-heptachlorinated dibenzofuran
|
0.01 |
16. 1,2,3,4,7,8,9-heptachlorinated dibenzofuran
|
0.01 |
17. Octachlorinated dibenzofuran |
0.001 |
Table 3
Operating Parameters To Be Monitored And Minimum
Measurement And Recording Frequencies
Operating Parameters To Be Monitored
|
Minimum Frequency
|
Control System
|
Data Measurement
|
Data Recording
|
Dry Scrubber Followed By Fabric Filter
|
Wet Scrubber
|
Dry Scrubber Followed By Fabric Filter
And
Wet Scrubber
|
1. Maximum operating parameters: |
a. Maximum charge rate |
Continuous |
1 x hour |
x
|
x
|
x
|
b. Maximum fabric filter inlet temperature |
Continuous |
1 x minute |
x
|
x
|
c. Maximum flue gas temperature |
Continuous |
1 x minute |
x
|
x
|
2. Minimum operating parameters: |
a. Minimum secondary chamber temperature |
Continuous |
1 x minute |
x
|
x
|
x
|
b. Minimum dioxin/furan sorbent flow rate |
Hourly |
1 x hour |
x
|
x
|
c. Minimum HCl sorbent flow rate |
Hourly |
1 x hour |
x
|
x
|
x
|
d. Minimum mercury (Hg) sorbent flow |
Hourly |
1 x hour |
x
|
x
|
rate |
e. Minimum pressure drop across the wet |
Continuous |
1 x minute |
x
|
scrubber or minimum horsepower or |
amperage to wet scrubber |
f. Minimum scrubber liquor flow rate |
Continuous |
1 x minute |
x
|
x
|
g. Minimum scrubber liquor pH |
Continuous |
1 x minute |
x
|
x
|