Current through August 26, 2024
(1) APPLICABILITY.
The storage, recordkeeping and maintenance requirements of subs. (2), (3) and
(4) apply to all storage vessels for petroleum liquids of more than 151,412
liter (40,000 gallon) capacity on which construction or modification is
commenced after July 1, 1975, with the exception of:
(a) Storage vessels being used for number 2
through number 6 fuel oils as specified in ASTM D396-02, gas turbine fuel oils
numbers 2-GT through 4-GT as specified in ASTM D2880-00, or diesel fuel oils
numbers 2-D and 4-D as specified in ASTM D975-02. These ASTM standards are
incorporated by reference in s.
NR 484.10(8), (13) and (40).
(b) Storage vessels for the crude petroleum
or condensate stored, processed or treated at a drilling and production
facility outside a metropolitan county prior to custody transfer.
(c) Pressure vessels which are designed to
operate at pressures in excess of 104 kPa (15 psig) without emissions except
under emergency conditions.
(d)
Subsurface caverns or porous rock reservoirs.
(e) Horizontal underground storage tanks used
to store JP-4 jet fuel.
(2) STORAGE REQUIREMENTS. The owner or
operator of any storage vessel to which this section applies shall store
petroleum liquids as follows:
(a) If the true
vapor pressure of the petroleum liquid, as stored, is equal to or greater than
10.5 kPa (1.52 psia) but not greater than 77 kPa (11.1 psia), the storage
vessel shall be equipped with a floating roof, a vapor recovery system or an
equally effective alternative control method approved by the
department.
(b) If the true vapor
pressure of the petroleum liquid, as stored, is greater than 77 kPa (11.1
psia), the storage vessel shall be equipped with a vapor recovery system or an
equally effective alternative control method approved by the
department.
(3)
RECORDKEEPING.
(a)
General
records. The owner or operator of any storage vessel to which this
section applies shall, for each such storage vessel, maintain a file of each
type of petroleum liquid stored, the typical Reid vapor pressure of each type
of petroleum liquid stored and the dates of storage. Dates on which the storage
vessel is empty shall be indicated.
(b)
Vapor pressure dependent
records. The owner or operator of any storage vessel to which this
section applies shall, for each such storage vessel, determine and record the
average monthly storage temperature and true vapor pressure of the petroleum
liquid stored at that temperature if one of the following applies:
1. The petroleum liquid has a true vapor
pressure, as stored, greater than 3.5 kPa (0.51 psia) but less than 10.5 kPa
(1.52 psia) and is stored in a vessel other than one equipped with a floating
roof, a vapor recovery system or their equivalents.
2. The petroleum liquid has a true vapor
pressure, as stored, greater than 63 kPa (9.1 psia) and is stored in a storage
vessel other than one equipped with a vapor recovery system or its
equivalent.
(c)
Vapor pressure determination. The true vapor pressure shall be
determined by application of the procedures in API Publication 2517, 3rd
edition, incorporated by reference in s.
NR 484.11(5), in accord with this
paragraph. This procedure is dependent upon determination of the average
monthly storage temperature and the Reid vapor pressure, which requires
sampling of the petroleum liquids in the storage vessels. Unless the department
requires in specific cases that the stored petroleum liquid be sampled, the
true vapor pressure may be determined by using the average monthly storage
temperature and the typical Reid vapor pressure. For those liquids for which
certified specifications limiting the Reid vapor pressure exist, that Reid
vapor pressure may be used. For other liquids, supporting analytical data shall
be made available on request to the department when typical Reid vapor pressure
is used.
(4) EQUIPMENT
MAINTENANCE.
(a)
Applicability. In addition to the vessels identified in sub.
(1) this subsection applies to all storage vessels for petroleum liquids of
more than 7,571 liter (2,000 gallon) capacity.
(b)
Requirements. No person
may place, hold or store in a storage vessel any petroleum liquid which has a
true vapor pressure as stored greater than 10.5 kPa (1.52 psia) unless all of
the following requirements are met:
1. Any
tank surface exposed to the rays of the sun is painted and maintained white so
as to prevent excessive temperature and vapor pressure increases.
2. The seals of any floating roof are
maintained so as to minimize emissions.
3. All gauging and sampling devices are vapor
tight except when gauging or sampling is taking place.
(5) FIXED ROOF VESSELS.
(a)
Applicability. This
subsection applies, subject to the provisions of s.
NR 425.03,
to all fixed roof storage vessels with capacities greater than 151,412 liters
(40,000 gallons) with the exception of those having capacities less than
1,600,000 liters (416,000 gallons) used to store crude petroleum and condensate
prior to custody transfer.
(b)
Storage requirements. No owner or operator of a fixed roof
storage vessel to which this subsection applies may permit the storage vessel
to be used for storing any petroleum liquid which has a true vapor pressure as
stored greater than 10.5 kPa (1.52 psia), unless all of the following
requirements are met:
1. The vessel has been
retrofitted with an internal floating roof equipped with a closure seal, or
seals, to close the space between the roof edge and tank wall, or with equally
effective alternative controls approved by the department.
3. The vessel is maintained such that there
are no visible holes, tears, or other openings in the seal or any seal fabric
or materials.
4. All openings,
except stub drains, are equipped with covers, lids, or seals such that:
a. The cover, lid or seal is in the closed
position at all times except when in actual use.
b. Automatic bleeder vents are closed at all
times except when the roof is floated off or landed on the roof leg
supports.
c. Rim vents, if
provided, are set to open when the roof is being floated off the roof leg
supports or at the manufacturer's recommended setting.
5. Routine inspections are conducted through
roof hatches at monthly intervals during the ozone season. These routine
inspections shall include, at a minimum, a visual examination to determine that
the roof is resting on the liquid surface, no liquid has accumulated on the
roof, no seal is detached and that there are no tears or holes in the seal
material.
6. The vessel is repaired
or removed from service as expeditiously as practicable, but no later than 45
days after any routine inspection in which any of the defects described in
subd. 5. are found, unless an extension is granted by the department. If a
defect identified in subd. 5. cannot be repaired or the vessel removed from
service within 45 days, a one time 30 day extension may be requested by the
owner or operator. The department may grant such a request if the owner or
operator demonstrates that alternative storage capacity is not available or
that repair or removal of the tank from service is infeasible for reasons
beyond the control of the owner or operator.
7. A complete inspection of cover and seal is
conducted periodically as required by par. (c)
8. Records are maintained and retained for a
minimum of 5 years, unless otherwise noted, that shall include both of the
following:
a. The results of inspections
conducted under subds. 5. and 7., including LEL readings, if applicable. All
LEL readings and inspection report records shall be maintained for a minimum of
10 years if the facility elects to comply with par. (c) through use of par. (c)
2.
b. The information required
under sub. (3).
(c)
Complete inspection
requirements. All fixed roof storage vessels at a facility to which
this subsection applies are required to periodically undergo a complete
inspection of cover and seal, and all shall use either subd. 1. or 2. to
demonstrate compliance. No facility may use different compliance methods for
different fixed roof storage vessels to comply with this paragraph. The
complete inspection shall be conducted according to one of the following
schedules:
1. Whenever a fixed roof storage
vessel is emptied and degassed or at least every 5 years, whichever is more
frequent.
2. Whenever a fixed roof
storage vessel is emptied and degassed or at least every 10 years, whichever is
more frequent, if all of the following requirements are met:
a. The routine monthly inspections during the
ozone season, in addition to meeting the requirements of par. (b) 5., include
the measurement with an explosimeter of the organic vapor space above the
internal floating roof to demonstrate that the organic vapor concentration does
not exceed 50% of the lower explosive limit (LEL) for the stored petroleum
liquid.
b. The fixed roof storage
vessel is repaired or removed from service as expeditiously as practicable, but
no later than 45 days after the completion of the routine inspection, if any of
the defects described in par. (b) 5. are found or if the measurement required
under subd. 2. a. exceeds 50% of the LEL.
c. Repair steps meeting the requirements of
subd. 2. b. may include tests, maintenance or inspections followed by LEL
measurements below 50% within 45 days of the initial LEL reading exceeding 50%
that confirm further repair or removal of the tank from service is not
warranted.
(d)
Notification and change of
compliance method requirements. All existing facilities which have one
or more storage vessels subject to par. (c) shall notify the department in
writing, by January 3, 2000, as to whether the facility will comply with this
section under the provisions of par. (c) 1. or 2. After January 3, 2000, a
facility owner or operator may only change the compliance option from par. (c)
1. to par. (c) 2. after completing a complete inspection of every affected
fixed roof storage vessel at the facility. For any newly constructed facility,
the owner or operator shall notify the department prior to commencing operation
as to which compliance option will be used. A facility owner or operator may at
any time elect to change the compliance option from par. (c) 2. to par. (c) 1.
provided the following conditions are met:
1.
The facility owner or operator notified the department, in writing, at least 30
days prior to the date on which the facility owner or operator plans to begin
meeting the requirements of par. (c) 1.
2. All tanks at the facility were found to be
in compliance with the 50% LEL requirement of par. (c) 2. during their last LEL
measurement.
(6) EXTERNAL FLOATING ROOF VESSELS.
(a)
Applicability. This
subsection applies, subject to the provisions of s.
NR 425.03(4) or
(5), to all storage vessels equipped with
external floating roofs having capacities greater than 151,412 liters (40,000
gallons) with the exception of:
1. Storage
vessels having capacities less than 1,500,000 liters (396,270 gallons) used to
store crude petroleum and condensate prior to custody transfer.
2. Storage vessels used to store waxy, heavy
pour crude petroleum.
3. Storage
vessels used solely for petroleum liquids with a true vapor pressure of less
than 10.5 kPa (1.52 psia).
4.
Storage vessels used solely for petroleum liquids with a true vapor pressure of
less than 27.6 kPa (4.0 psia), and which are of welded construction, and
presently possess a metallic-type shoe seal, a liquid-mounted foam seal, a
liquid-mounted liquid filled type seal, or equally effective alternative
control, approved by the department.
5. Storage vessels of welded construction,
equipped with metallic-type shoe primary seal which has a secondary seal from
the top of the shoe seal to the tank wall.
(b)
Storage requirements. No
owner or operator of a storage vessel equipped with an external floating roof
to which this subsection applies may permit such storage vessel to be used for
storing any petroleum liquid unless all of the following requirements are met:
1. The vessel has been fitted with a
continuous secondary seal extending from the floating roof to the tank wall, or
the vessel has been fitted with an equally effective alternative control,
approved by the department.
2. The
vessel is maintained such that all seal closure devices meet the following
requirements:
a. There are no visible holes,
tears, or other openings in the seal or any seal fabric or material.
b. The seal or seals are intact and uniformly
in place around the circumference of the floating roof between the floating
roof and the tank wall.
c. For
vapor-mounted seals, the accumulated area of gaps exceeding 0.32 cm (1/8 in) in
width between the secondary seal and tank wall may not exceed 21.2
cm2 per meter (1.00 in2
per foot) of tank diameter.
3. All openings in the external floating
roof, except for automatic bleeder vents, rim space vents, and leg sleeves,
are:
a. Equipped with covers, seals, or lids
kept in the closed position except when in actual use.
b. Equipped with projections into the tank
which remain below the liquid surface at all times.
4. Automatic bleeder vents are closed at all
times except when the roof is floated off or landed on the roof leg
supports.
5. Rim vents are set to
open only when the roof is being floated off the leg supports or at the
manufacturer's recommended setting.
6. Emergency roof drains are provided with
slotted membrane fabric covers or equivalent covers which cover at least 90% of
the area of the opening.
7. Routine
visual inspections are conducted of all seals and seal closure devices at
monthly intervals during the ozone season.
8. The secondary seal gap of vapor-mounted
seals is measured annually, in a manner approved by the department.
9. The vessel is repaired or removed from
service as expeditiously as practicable, but no later than 45 days after the
completion of the routine inspection under subd. 7. or the annual inspection
under subd. 8., if the inspection reveals a failure to meet any of the
requirements of subd. 2.
10.
Records are maintained and retained for a minimum of 5 years that shall
include:
a. The results of inspections
conducted under subds. 7. and 8.
b.
The information required under sub. (3) (a) and (b) (intro.).
(7) EXTERNAL
FLOATING ROOF VESSELS WITH NO SECONDARY SEAL REQUIREMENT.
(a)
Applicability. This
subsection applies to all storage vessels with capacities greater than 151,412
liters (40,000 gallons) equipped with external floating roofs operating without
secondary seals or their approved equivalent pursuant to sub. (6) (a) 1. to
4.
(b)
Recordkeeping. The owner or operator of a petroleum liquid
storage vessel with an external floating roof not covered under sub. (6) but
containing a petroleum liquid with a true vapor pressure greater than 7.0 kPa
(1.0 psia), shall maintain and retain for at least 2 years records of the
average monthly storage temperature, the type of liquid, throughput quantities
and the maximum true vapor pressure for all petroleum liquids with a true vapor
pressure greater than 7.0 kPa (1.0 psia).
(8) ALTERNATIVE CONTROL. Any alternative
control method approved by the department under sub. (2), (5) (b) 1. or (6) (b)
1. shall be submitted to, and will not become effective for federal purposes
until approved by, the administrator or designee as a source-specific revision
to the department's state implementation plan for ozone.