Wisconsin Administrative Code
Department of Natural Resources
NR 400-499 - Environmental Protection - Air Pollution Control
Chapter NR 419 - Control Of Organic Compound Emissions
Section NR 419.06 - Transfer of any organic compound
Current through August 26, 2024
(1) APPLICABILITY.
(2) TANK LOADING. For transfers to storage tanks having greater than 3,785 liter (1,000 gallon) capacity, a permanent submerged fill pipe shall be used, provided such a tank does not have controls mentioned in s. NR 419.05(2).
(3) TANK LOAD OUT FOR HIGH THROUGHPUT FACILITIES. At facilities with over 151,412 liters (40,000 gallons) per day throughput, a vapor collection and disposal system, vapor collection adaptors and vapor-tight seal, or an underfill method with the top hatches partially closed or a means of creating a slight back pressure when loading delivery vessels shall be used.
(4) TANK LOAD OUT FOR LOW THROUGHPUT FACILITIES. At facilities with 151,412 liters (40,000 gallons) or less per day throughput, the underfill method or a submerged fill pipe extending to within 6 inches of the tank bottom shall be employed when loading tank trucks or trailers.