(4) INSPECTION AND MONITORING. The
owner or operator of a waste management unit that is subject to requirements
under sub. (2) or (3) shall comply with the following inspection and monitoring
requirements, except that an owner and operator subject to and in compliance
with a subpart in 40 CFR part 63 as provided in sub. (3) (b), may comply with
the inspection, monitoring, and record keeping requirements of that subpart
instead of the requirements of this subsection.
(a) All seals, covers, closed vent systems,
and other equipment used to comply with sub. (2) or (3) shall be visually
inspected for leaks and improper conditions semiannually and upon repair as
specified in this paragraph. If any seal, cover, closed vent system, or other
equipment is found to have a leak or be in improper condition, the equipment
shall be repaired as soon as possible, but no later than 15 calendar days after
detection, unless the repair or correction is technically infeasible without
requiring a process unit shutdown, in which case the repair or correction shall
be made during the next process unit shutdown.
1. For a wastewater tank equipped with a
fixed roof and vapor control system, visually inspect the fixed roof, openings,
and the closed vent system for leaks, except for a cover and closed vent system
maintained under negative pressure, and take corrective action.
2. For a wastewater tank equipped with an
internal or external floating roof, visually inspect for and correct the
following improper conditions:
a. An access
door or other opening is left open when not in use.
b. The floating roof is not resting on either
the surface of the liquid or on the leg supports.
c. There is stored liquid on the floating
roof.
d. A rim seal is detached
from the floating roof.
e. There
are holes, tears, cracks, or gaps in the rim seal or seal fabric of the
floating roof.
f. There are visible
gaps between the seal of an internal floating roof and the wall of the
wastewater tank.
g. Where a
metallic shoe seal is used on an external floating roof, one end of the
metallic shoe does not extend into the stored liquid or one end of the metallic
shoe does not extend a minimum vertical distance of 61 centimeters above the
surface of the stored liquid.
h. A
gasket, joint, lid, cover, or door has a crack or gap, or is broken.
3. For a surface impoundment,
visually inspect the cover and all openings for leaks, except for a cover and
closed vent system maintained under negative pressure, and take corrective
action.
4. For a surface
impoundment, visually inspect for and correct the following improper
conditions:
a. An access hatch or other
opening is left open when not in use.
b. A joint, lid, cover, or door has a crack
or gap, or is broken.
5.
For a portable container, visually inspect the cover and all openings for leaks
and take corrective action.
6. For
a portable container that is located within an enclosure that is vented by
means of a closed vent system to a control device, visually inspect the
enclosure and closed vent system for leaks, except for an enclosure and closed
vent system maintained under negative pressure, and take corrective
action.
7. For a portable
container, visually inspect for and correct the following improper conditions:
a. An access hatch or other opening is left
open when not in use.
b. A cover or
door has a gap or crack, or is broken.
8. For an individual drain system, visually
inspect for and correct the following improper conditions:
a. A joint, lid, cover, or door has a gap,
crack, or hole or is broken.
b. An
access hatch or other opening is left open when not in use for sampling or
removal, or for equipment inspection, maintenance, or repair.
c. Sufficient water is not present to
properly maintain integrity of water seals.
d. Drains using tightly-fitted caps or plugs
have caps and plugs that are not in place or not properly installed.
e. Junction boxes do not have covers in place
or covers have visible gaps, cracks, or holes.
f. Unburied portion of sewer lines have
cracks or gaps.
9. For a
junction box vented to a process or through a closed vent system to a control
device, visually inspect for and correct leaks in the closed vent
system.
10. For oil-water
separators, visually inspect fixed roof and all openings for leaks and take
corrective action.
11. For
oil-water separators, visually inspect for and correct the following improper
conditions:
a. An access door of other
opening is left open when not in use, or not equipping the door or opening with
a gasket.
b. The floating roof is
not resting on either the surface of the liquid or on the leg
supports.
c. There is stored liquid
on the floating roof.
d. A rim seal
is detached from the floating roof.
e. There are holes, tears, or other open
spaces in the rim seal or seal fabric of the floating roof.
f. A gasket, joint, lid, cover, or door has a
gap or crack, or is broken.
(b) For a wastewater tank or oil-water
separator equipped with an external floating roof having primary and secondary
seals used to comply with sub. (2) or (3), the secondary seal shall be
inspected for seal gaps and repaired as follows:
1. The secondary seal shall be measured for
seal gaps annually and after repair as follows:
a. The width of any seal gap is the distance
between the seal and the tank wall and shall be determined by using probes of
various widths to accurately measure the actual distance from the seal to the
tank wall.
b. The area of any seal
gap shall be determined by multiplying the width of the seal gap, as determined
in subd. 1. a., by the circumferential length of the gap.
c. The total seal gap area is the accumulated
area of all gaps which are greater than 0.125 inch in width.
2. The accumulated area of gaps
that exceed 0.125 inch in width between the secondary seal and tank wall may
not exceed 1.0 square inch per foot (21 square centimeters per meter) of tank
diameter.
3. If the seal gap
requirement of subd. 2. is not being met, the secondary seal shall be repaired
or replaced within 45 days after detection of the improper seal gap unless the
repair or correction is technically infeasible without requiring a process unit
shutdown, in which case the repair or correction shall be made at the next
process unit shutdown.
(c) The following records shall be maintained
on leaks, improper conditions, and improper seal gaps:
1. The date on which a leak, improper
condition, or improper seal gap is discovered.
2. The date on which a first attempt at
repair was made to correct the leak or improper condition.
3. The date on which a leak, improper
condition, or improper seal gap is repaired.
(d)
1.
Monitors shall be installed and maintained to measure operational parameters of
any emission control device or other device installed to comply with sub. (2)
or (3). Monitoring parameters shall be sufficient to demonstrate proper
functioning of the devices to design specifications. Except as provided in
subd. 2., the following monitoring and data recording shall be performed as
applicable:
a. For an enclosed non-catalytic
combustion device, continuously monitor and record the temperature of the gas
stream either in the combustion chamber or immediately downstream before any
substantial heat exchange.
b. For a
catalytic incinerator, continuously monitor and record the temperature of the
gas stream immediately before and after the catalyst bed.
c. For a condenser, continuously monitor and
record the temperature of the gas stream at the condenser exit.
d. For a carbon adsorber, continuously
monitor and record the VOC concentration of exhaust gas stream to determine if
breakthrough has occurred. If the carbon adsorber does not regenerate the
carbon bed directly in the control device, that is, a carbon canister is used,
the exhaust gas stream shall be monitored daily or at intervals no greater than
20% of the design replacement interval, whichever is greater. As an alternative
to conducting daily monitoring, the carbon may be replaced with fresh carbon at
a regular predetermined time interval that is less than the carbon replacement
interval that is determined by the maximum design flow rate and the VOC
concentration in the gas stream vented to the carbon adsorber.
e. For a flare, meet the requirements
specified in
40 CFR
60.18(b).
f. For a steam stripper, continuously monitor
and record the steam flow rate, the wastewater feed mass flow rate, and either
the wastewater feed temperature, or the column operating temperature as
measured in the column top tray liquid phase at the downcomer.
g. For vapor control systems other than those
specified in subds. 1. a. to f., continuously monitor and record the
appropriate operating parameters.
2. In lieu of the monitoring in subd. 1.,
other monitoring may be approved or required by the department with written
concurrence from EPA.
(e)
For a closed-vent system that is used to comply with sub. (2) or (3), and that
is designed to operate at a pressure below atmospheric pressure, the
closed-vent system shall be equipped with at least one pressure gauge or other
pressure measurement device that can be read from a readily accessible location
to verify that negative pressure is being maintained in the closed-vent system
when the control device is operating.