(1) GENERAL.
(a) All new and existing underground tank
systems used to store regulated substances shall be provided with a method of
leak detection that complies with this section and s.
ATCP 93.515, except as exempted in par. (d).
(b) The method of leak detection shall be
approved in accordance with s.
ATCP 93.130.
(c) All monitoring equipment used to satisfy
the requirements of this section shall be installed, calibrated, operated, and
maintained to perform as originally intended in accordance with the
manufacturer's instructions and the department's approval as issued under s.
ATCP 93.130.
(d) Leak detection is not required for any of
the following tanks:
1. Tanks which have a
capacity of less than 1,100 gallons and which are located on farm premises or
at private residences.
2. Tanks
storing Class IIIB liquids that are neither petroleum nor CERCLA-listed
products.
(e) If a tank
system exhibits a continuing pattern of failing and then not failing leak
detection testing, a precision tightness test shall be performed within 10
business days in accordance with s.
ATCP 93.515(4), and if a tank system fails
to pass that test, the site shall be assessed for the presence of a release in
accordance with ss.
ATCP 93.575 to 93.585.
Note: This section primarily addresses the
leak detection that is required on a routine, ongoing basis during normal
operation of an underground storage tank system. Several other sections of this
chapter require additional UST leakage or tightness testing.
(2) ANNUAL EQUIPMENT VERIFICATION.
(a) The following equipment shall be verified
by a qualified person every 12 months for the same degree of operability and
capability as when the equipment was newly installed using either requirements
developed by the manufacturer, or code of practice developed by a nationally
recognized association in Table 93.200.
1.
Equipment for measuring product levels that is used for manual tank gauging or
statistical inventory reconciliation.
2. Automatic tank gauging equipment used for
monthly monitoring, statistical inventory reconciliation or precision tightness
testing.
3. Interstitial monitoring
equipment.
4. Sensors used to
detect leaks in tanks, lines or sumps.
5. Overfill prevention equipment automatic
high-level alarm at 90 percent tank capacity and automatic overfill prevention
shut off device at 95 percent capacity. The automatic overfill prevention
device does not have to be removed from the tank if designed to be tested in
place by the manufacturer and the manufacturer provides a test procedure that
includes verification of operation and shut off level at 95 percent tank
capacity.
(b) Under this
subsection, a qualified person is a person certified by the equipment
manufacturer as being trained in the operational characteristics of the
equipment.
(c)
1. Annual monitoring equipment certification
shall be made on the department's underground tank system functionality
verification form, TR-WM-139, and on the department's electronic-mechanical
line leak detector annual functionality form, TR-WM-123, and line test report
form, TR-WM-125, if applicable and shall be maintained onsite in accordance
with s.
ATCP 93.500(9)
(a).
2. If all deficiencies found during the
equipment verification have not been corrected, the first page of the TR-WM-139
form shall be sent to the department email address on the form within 5
business days of the completion of the verification.
Note: Form TR-WM-123, Electronic/Mechanical
Line Leak Detector Annual Functionality, Form TR-WM-125, Line Tightness Test
Report, and Form TR-WM-139, Underground Tank System Functionality Verification,
are available from the Bureau of Weights and Measures, PO Box 8911, Madison, WI
53708-8911, or at telephone (608) 224-4942, or from the Bureau's Web site at
https://datcp.wi.gov/Pages/Programs_Services/PetroleumHazStorageTanks.aspx.
See s. ATCP 93.165 for use of alternate forms approved by the
department.
(3) LEAK DETECTION FOR TANKS.
(a)
General.
1. Tanks shall be monitored at least every 30
days for leaks using one of the methods listed in s.
ATCP 93.515, except as provided in subd. 2. and s.
ATCP 93.500(1)
(a).
2. Tanks installed prior to February 1, 2009,
that have a capacity of 1,000 gallons or less may use manual tank gauging
conducted in accordance with s.
ATCP 93.515(3) as the sole means of leak
detection provided it is performed weekly.
Note: Under s.
ATCP 93.500(1)
(a), continuous electronic interstitial
monitoring is generally required for all secondary containment installed on or
after February 1, 2009.
(b)
Failed tests. If a
passing test using monthly monitoring is not achieved, the site shall be
assessed for the presence of a release in accordance with ss.
ATCP 93.575 to 93.585.
(c)
Inconsistent results.
The authorized agent or the department may require a precision tightness test
to be performed where any of the following events occur:
1. A tank system is accumulating water for no
apparent reason.
2. A leak
detection method is providing erratic results.
3. A tank system is tested with multiple leak
detection methods that show different results.
(d)
Inventory control as leak
detection. Tank systems installed prior to February 1, 2009, may use
monthly inventory control performed in accordance with s.
ATCP 93.515(2) as leak detection provided
all of the following conditions are met:
1.
The tank is 10 years old or less.
2. The tank has precision tank tightness
testing performed in accordance with s.
ATCP 93.515(4) at least once every 5 years
from the date of installation until the tank is 10 years old.
3. The tank system has corrosion protection
in accordance with s.
ATCP 93.520.
(4) LEAK DETECTION FOR PIPING.
(a)
Pressurized piping.
Underground piping that conveys regulated substances under pressure shall
comply with all of the following requirements:
1. The system shall be equipped with an
automatic line leak detector in accordance with s.
ATCP 93.515(8)
(b).
2. Single-wall piping systems shall have at
least one of the following leak detection methods:
a. An annual precision tightness test in
accordance with s.
ATCP 93.515(4).
b. Monthly monitoring to the 0.2 gallon per
hour rate.
3. Double-wall
piping systems shall use one of the leak detection methods in subd. 2., or
statistical inventory reconciliation, or continuous interstitial monitoring,
except as provided in s.
ATCP 93.500(1)
(a).
Note: Under s.
ATCP 93.500(1)
(a), continuous electronic interstitial
monitoring is generally required for all secondary containment installed on or
after February 1, 2009.
4.
If a passing test using monthly monitoring is not achieved, the site shall be
assessed for the presence of a release in accordance with ss.
ATCP 93.575 to 93.585.
(b)
Suction piping.
1. Piping which conveys regulated substances
under suction and which is not entirely visible shall use one of the following
leak detection methods, except as provided in subd. 2.:
a. A precision tightness test performed in
accordance with s.
ATCP 93.515(4) at least every three
years.
b. Interstitial
monitoring.
2. Leak
detection may be omitted for suction piping that meets all of the following
requirements:
a. The below-grade piping
operates at less than atmospheric pressure.
b. The below-grade piping is sloped so that
the contents of the pipe will drain back into the storage tank if the suction
is released.
c. Only one check
valve is included in each suction line.
d. The check valve is visibly located
directly below and as close as practical to the suction pump.
e. A method is provided that allows
compliance with subd. 2. b. to d. to be readily observed or otherwise
determined.
(c)
Inventory control as leak detection. Piping connected to a
tank using inventory control in accordance with sub. (3) (d) shall comply with
one of the following:
1. Pressurized piping
shall have leak detection complying with par. (a).
2. Suction piping shall have leak detection
complying with par. (b).