Current through August 26, 2024
(1) ABOVEGROUND TANK DESIGN.
(a)
General. Tanks designed
and built for underground use may not be used aboveground.
(b)
Tanks for Class I, II, or IIIA
liquids. Tanks used for aboveground storage of Class I, II, or IIIA
liquids shall comply with the tank construction and marking requirements in s.
ATCP 93.250.
(c)
Tanks for Class IIIB
liquids. Tanks which have a capacity of 1,100 gallons or more and
which are used for aboveground storage of Class IIIB liquids shall be listed or
shall be acceptable to the department.
Note: See s.
ATCP 93.130(5) for listing and labeling
requirements for aboveground tanks.
(d)
Tank foundations. Tank
foundations shall be designed to prevent uneven settling of the tank. Tank
supports shall be placed on a prepared, flat, smooth, and solid surface.
(2) CORROSION
PROTECTION.
(a)
General.
Aboveground storage tank systems shall be protected from excessive external
corrosion through the use of paint, protective coatings, or corrosion resistant
materials that are applied after the surface has been prepared in accordance
with the manufacturer's recommendations.
(b)
Tank systems. Any
portion of an aboveground tank system that is in contact with the ground shall
be protected from corrosion by one of the following methods:
1. The tank system is constructed of an
inherently corrosion-resistant material.
2. The tank system is isolated from the
ground by a method acceptable to the department.
Note: Methods of isolation acceptable to the
department include dielectric coating, placement on clean concrete, placement
on an elevated ring wall, or mounting on listed saddles.
3. The tank system is protected by a
sacrificial anode or impressed current system.
4.
a.
Single- or double-wall tanks which are constructed of material subject to
corrosion and which are supported on runners or tank supports shall be
constructed such that the bottom of the tank shell is at least 3 inches but no
more than 12 inches above grade, as measured from the lowest point of the tank
shell, except the 12-inch maximum does not apply where subd. 4. b. is
met.
b. The 12-inch maximum in
subd. 4.a. may be exceeded where structural fire resistance is provided that
complies with NFPA 30 section 22.5.2.4.
(c)
Underground piping. All
new and existing underground piping connected to an aboveground tank shall be
protected from corrosion using one of the methods in s.
ATCP 93.520(1).
(d)
Designed corrosion protection
systems.
1. Aboveground tank systems
equipped with a new sacrificial anode or impressed current corrosion protection
system shall follow the installation, operation, maintenance and testing
requirements in s.
ATCP 93.520.
2.
Existing sacrificial anode or impressed current corrosion protection systems
shall follow the operation, maintenance and testing requirements in s.
ATCP 93.520.
(3) SECONDARY CONTAINMENT FOR PIPING.
(a) When any underground piping is installed
as part of a new tank system or when 50 percent or more of a run is replaced,
the piping shall be provided with approved secondary containment with approved
non-discriminating interstitial monitoring, except as specified in par.
(g).
(b)
1. The material used for fabricating both the
primary and secondary containment shall be listed in accordance with a standard
that assures liquid- and vapor-tightness.
2. Secondary containment sumps shall be
fabricated and installed in a manner that prevents release of liquids. These
sumps shall be tested for leaks hydrostatically at installation, in accordance
with the manufacturer's instructions and the adopted standard PEI RP
1200.
(c) All pipe
connections at a dispenser for motor vehicle fueling that are installed or
replaced on or after February 1, 2009, shall be placed within a secondary
containment sump at the time of installation or replacement, except as exempted
in par. (e).
(d) All pipe
connections at a dispenser for motor vehicle fueling that were in existence or
under construction before February 1, 2009, shall be placed within a secondary
containment sump by January 1, 2021, except as exempted in par. (e).
(e) A secondary containment sump is not
required under the pipe connections at a dispenser if the storage tank system
meets all of the following conditions:
1. All
piping is aboveground and readily accessible for inspection.
2. The dispenser and all the pipe connections
at the dispenser are on or above a surface that is at least as impermeable as
concrete.
(f) All pipe
connections at a transition between aboveground and underground piping that are
installed or replaced on or after February 1, 2009, shall be placed within a
secondary containment sump at the time of installation or
replacement.
(g) Secondary
containment is not required for underground piping that is evaluated and
maintained in accordance with API 570, by organizations that maintain or use an
authorized inspection agency, a repair organization, and technically qualified
piping engineers, inspectors and examiners, all as defined in API
570.
(h)
1. Secondary containment sumps provided under
this subsection shall have non-discriminating electronic sensors that will
detect liquids in the sump, unless approved otherwise by the
department.
2. Piping that is
installed or replaced on or after August 1, 2009, at secondary containment
sumps provided under this subsection may not pass through the bottom of the
sump.
3. All electrical conduit and
wiring that is installed or replaced on or after August 1, 2009, at secondary
containment sumps provided under this subsection for dispensers shall pass over
the top of the sump wall rather than through the wall or bottom of the sump.
Note: This subsection recognizes dispenser
pans, spray-on liners, brushed-on liners, formed-in-place containment products,
and other effective secondary containment practices that are currently in
use.
(4)
LEAK DETECTION FOR PIPING.
(a) All new and
existing underground piping connected to an aboveground tank shall be provided
with approved leak detection in accordance with s.
ATCP 93.510(4), except as specified in
par. (c).
(b) Leak detection in
accordance with par. (a) shall be installed immediately at the time of new
installation or replacement of pipe.
(c)
1.
Piping over 4 inches in diameter shall follow the plan and system requirements
and deadlines in s.
ATCP 93.517, except as specified in subd. 2. Leak detection
for piping of 4 inches in diameter or less may be provided as specified in
subd. 2. only if approved in writing by the department.
2. Leak detection for piping may consist of
evaluations that are performed in accordance with API 570, by organizations
that maintain or use an authorized inspection agency, a repair organization,
and technically qualified piping engineers, inspectors and examiners, all as
defined in API 570.
(5) INSTALLATION.
(a)
1. The
installation of shop-built tanks and associated piping shall be performed or
supervised by a certified installer under s.
ATCP 93.240(16).
2. A certified installer shall verify that
the installation of the electrical components for a tank system does not
conflict with this chapter, except this verification is not required for the
electrical criteria in ch. SPS 316.
(b)
1. All
installation shall be in accordance with the manufacturer's instructions, the
applicable national standards adopted in s.
ATCP 93.200, and plans and specifications approved under s.
ATCP 93.100 and this
chapter.
2. All tank and pipe
systems that are installed on or after November 1, 2019, including replacement
systems, shall undergo all of the following before the tank and pipe systems
are placed into service:
a. Pressure testing
that shall assure that the tank, pipe, and all connections are tight in
accordance with PEI RP200 sections 6.6 and 9.6 and chapter 14.
b. Pre-operational testing and inspection in
accordance with PEI RP200 chapter 14.
(c) Single wall horizontal-cylindrical and
rectangular aboveground storage tanks shall be installed to allow full visual
inspection of the outer tank shell, except for any portion of the shell that is
in contact with a support for it.
(d) The foundations for all types of tanks
shall be designed to minimize the possibility of uneven settling and to
minimize corrosion in any part of the tank resting on the foundation.
(e) Tank supports shall be placed on a
prepared, flat, compacted surface.
(em) Vent piping shall meet the requirements
of NFPA 30 Subchapter 27.8 except the termination height of normal vent piping
for Class II and Class III liquids shall be a minimum of 4 feet above the
ordinary snow line.
(f) Upon
completion of any installation of new or replacement shop-built tanks or
piping, or any modification or upgrade thereto that requires plan approval or
registration, the certified installer shall provide the authorized agent or the
department with a completed tank installation checklist, form TR-WM-120.
Note: Form TR-WM-120 - Checklist for
Aboveground Storage Tank Installation is available from the Bureau of Weights
and Measures, PO Box 8911, Madison, WI 53708-8911, or at telephone (608)
224-4942, or from the Bureau's Web site at
https://datcp.wi.gov/Pages/Programs_Services/PetroleumHazStorageTanksForms.aspx.
(6) MOVING
SHOP-BUILT TANKS. Aboveground shop-built tanks that are moved from one location
to another shall meet all of the following requirements, except for tanks
covered in s.
ATCP 93.610:
(a) The tank
shall meet all the plan review, installation, and registration requirements in
this chapter for the new location.
(b) If the tank contained Class I liquids, it
shall be rendered free of flammable vapors before the move and maintained
vapor-free until placed into service at the new location.
(c) If the tank is relocated to a property
with a different street address, a revised tank registration, form TR-WM-118 or
TR-WM-153, and part A of a tank system service and closure assessment report,
form TR-WM-140, shall be completed and submitted to the department for the
former location.
Note: Form TR-WM-118 - Aboveground
Flammable/Combustible/Hazardous Liquid Storage Tank Registration; form
TR-WM-140 - Tank System Service and Closure Assessment Report; and form
TR-WM-153 - Change of Ownership, Flammable/Combustible/Hazardous Liquid Storage
Tank Registration are available from the Bureau of Weights and Measures, PO Box
8911, Madison, WI 53708-8911, or at telephone (608) 224-4942. Forms TR-WM-118
and TR-WM-140 are also available from the Bureau's Web site at
https://datcp.wi.gov/Pages/Programs_Services/PetroleumHazStorageTanksForms.aspx.
(cm) If the tank is relocated on the same
property, part A of a tank system service and closure assessment report, form
TR-WM-140, shall be completed and submitted to the department for the former
location.
(d) The tank shall
undergo pre-operational testing and inspection in accordance with PEI RP200
chapter 14.
(e) The tank shall have
an inspection performed by a certified tank system inspector before being
placed into operation.
(f) The tank
shall continue to follow the inspection schedule in STI SP001 that was
established at the former location.
(7) ABOVEGROUND TANK MARKING.
(a)
1. All
aboveground tanks, whether new or existing, that store Class I liquids, other
than at refineries or at marine, pipeline, or transport terminals, shall have
attached the wording, "FLAMMABLE-KEEP FIRE AWAY."
2. The wording shall be clearly visible and
written in letters of a contrasting color at least 5 inches high with a minimum
stroke width of one inch.
(b)
1. All
aboveground tanks, whether new or existing, that store flammable or combustible
liquids shall be labeled in accordance with NFPA 704.
2. The
Table 93.400
Tank Label
Tank Capacity in
Gallons |
Distance From Which the Label Shall Be
Visible |
Minimum Size of Label |
Up to 5,000 |
75 feet |
5" x 5" |
5,001 to 50,000 |
100 feet |
10" x 10" |
50,001 to 250,000 |
200 feet |
12" x 12" |
Greater than 250,000 |
300 feet |
15" x 15" |
(8) MAINTENANCE AND REPAIRS.
(a)
Tanks.
1.
a. All
shop-built aboveground steel storage tanks, whether new or existing, shall be
maintained and repaired in accordance with STI SP031.
b. All repairs or modifications under STI
SP031 shall be recorded on the department's TR-WM-134 form.
Note: Form TR-WM-134-STI SP031 Tank
Repair/Modification Summary, is available from the Bureau of Weights and
Measures, P. O. Box 8911, Madison, WI 53708-8911, or at telephone (608)
224-4942, or from the Bureau's Web site at
https://datcp.wi.gov/Pages/Programs_Services/PetroleumHazStorageTanksForms.aspx.
c. A copy of the completed TR-WM-134 form
shall be provided to the tank operator.
d. The tank operator shall have the completed
TR-WM-134 form on site and available for inspection within 30 days after
receiving it from the party that performed the repair, except as provided in
sub. (11) (b) 2. for unattended sites.
2. Field-erected aboveground storage tanks
shall be maintained and repaired in accordance with API 653.
(b)
Other system
components.
1. Repairs to any of the
following tank system components shall be recorded on the department's
TR-WM-136 form:
a. Below-grade
components.
b. Tank containment and
piping sumps.
c. Overfill valves
and vent whistles.
d. Emergency
vents.
e. Normal vent pressure or
vacuum valves and flame arrestors.
f. Anti-siphon valves.
Note: Form TR-WM-136-STI SP031 Tank System
Repair Report, is available from the Bureau of Weights and Measures, P. O. Box
8911, Madison, WI 53708-8911, or at telephone (608) 224-4942, or from the
Bureau's Web site at
https://datcp.wi.gov/Pages/Programs_Services/PetroleumHazStorageTanksForms.aspx.
2. A copy of the completed
TR-WM-136 form shall be provided to the tank operator.
3. The tank operator shall have the completed
TR-WM-136 form on site and available for inspection within 30 days after
receiving it from the party that performed the repair, except as provided in
sub. (11) (b) 2. for unattended sites.
(c)
Testing of repairs.
1. `Interstitial space.' Any repair that
affects any portion of an interstitial space for an AST system shall include
testing of the affected portion in accordance with methods prescribed in s.
ATCP 93.500(6) (b) and
(c) and PEI RP 200, or other methods approved
by the department, to verify that the containment complies with this chapter
before that portion is placed back into service.
2. `Secondary containment sumps.' Repair of
any secondary containment sumps that are addressed in s. ATCP 93.400(3) shall
include testing in accordance with the methods prescribed in s. ATCP 93.400(3)
(b) before placing the sumps back into service.
3. `Overfill prevention equipment.' Repair of
overfill prevention equipment shall include testing in accordance with the
methods prescribed in s.
ATCP 93.410(12) before placing the
equipment back into service.
(d)
Reporting. Repairs that
are recorded under par. (a) 1. b. or (b) 1. because of a leak shall be reported
to the department within 15 days of the repair.
Note: See ss.
ATCP 93.230(8) to
(10) for additional facility maintenance
requirements.
(e)
Property. Tank yards and diked areas shall be kept free from
weeds, high grass, rubbish, and combustible materials that are not essential to
the operation and shall be kept clean and orderly.
(9) FACILITY LIGHTING. Adequate lighting
shall be provided for loading, unloading, and dispensing operations.
(10) SYSTEM ACCESS.
(a) All new aboveground storage tank systems
shall be designed and constructed to allow access to all connections between
the tank and piping, venting, and appurtenances that require maintenance or
replacement.
(b) The means of
access shall be sufficient in size to allow for installation, maintenance, and
inspection of all connections and appurtenances.
(11) RECORD KEEPING.
(a)
General. Operators of
new and existing aboveground storage tank systems shall maintain all of the
following records:
1. Documentation of any
system repairs, alterations or upgrades- including software and hardware
upgrades - and any inspections or testing required under this
chapter.
2. Testing results
obtained from any leak detection equipment, as retained from the equipment's
printer or a handwritten log kept on-site.
3. Documentation maintained for all
calibration, inspection, monitoring, testing, repair, and annual performance
verification of any leak detection equipment, if so equipped.
4. Response to and investigation of any leak
detection alarms.
5. Documentation
maintained for all calibration, inspection, monitoring, testing, repair, and
periodic performance verification of any corrosion protection equipment
permanently located on-site.
6.
Records of any environmental information that has accrued for a site, such as
from site investigations, phase I or II environmental site assessments, repairs
and tank-system site assessments.
7. Results of functional testing of impact
and emergency shutoff valves.
7m.
Results of functional testing of emergency electrical shutoffs.
8. Electrical continuity testing for
dispensers of motor fuels that are Class I liquids.
9. One set of stamped, approved plans and
specifications and a copy of the approval letter.
10. Documentation of compliance with the
compatibility requirements in s.
ATCP 93.680(3) (c) 1. or
(6) (c) 1., if the ethanol or biodiesel
blends addressed therein are stored or dispensed.
(b)
Availability of records.
1. Operators shall maintain the required
records at the site, except as provided in subds. 2. and 3., and par. (c)
9.
2. Operators of unattended sites
shall make the records available for inspection at the site when given 72 hours
of prior notice.
3. The approved
plans and specifications and approval letter shall be kept on site and
available to the authorized agent or the department during all phases of
installation. After installation is completed, the approved plans and
specifications and approval letter shall be made available to the authorized
agent or the department upon request.
4. Records may be kept electronically,
provided they are in a format acceptable to the department.
(c)
Maintenance of records.
Records shall be maintained for the following periods from the date of the most
recent test, inspection or upgrade:
1.
Monthly leak detection monitoring for underground piping - one year.
2. Annual precision tightness testing for
underground piping - one year.
3.
Impressed current corrosion protection system, 60-day inspection - the previous
3 inspections.
4. Corrosion
protection system, annual test - the previous 3 tests.
5. Annual performance verification of leak
detection equipment and flow restrictor, for underground piping - 2
years.
6. Results of functional
testing of impact and emergency shutoff valves and electrical continuity
testing for dispensers - 2 years.
7. The owner's manual provided by the leak
detection equipment manufacturer - until the leak detection system is replaced
or no longer used.
8. Any tank or
pipe system modification or repair - the operational life of the
system.
9. Inspection or testing
records - 3 years or the interval between required inspections or testing,
whichever is longer.
10.
Tank-system site assessments and other environmental assessments, such as
assessments for property transactions - 3 years after completion of any
permanent closure, upgrade, repair, or change in service. These records shall
be maintained at one of the following locations:
a. With the owner or operator who took the
AST system out of service.
b. With
the current operator of the AST system site.
c. With the department if records cannot be
maintained at the closed facility.
11. Leak detection alarm investigation - 2
years.
Note: All leak detection records should be
retained. The documentation could be helpful to exclude the site as a possible
source of contamination at a later date.
12. One set of stamped, approved plans and
specifications and a copy of the approval letter - the operational life of the
system.
13. Equipment or component
compatibility for ethanol or biodiesel blends under s.
ATCP 93.680(3) (c) 1. or
(6) (c) 1. - the operational life of the
equipment or component.
(12) TANKS AT REMEDIATION SITES.
(a)
1.
Recovery systems using oil water separators or recovery systems pumping free
product at the rate of 60 gallons or more per week shall comply with this
paragraph.
2. Recovery product
piping and storage tanks shall comply with either the plan review requirements
in s.
ATCP 93.100 or the
design and construction requirements in s.
ATCP 93.350(2) for hazardous
substances.
3. Tanks shall be
registered in accordance with s.
ATCP 93.140.
4.
Tank construction and marking shall comply with ss.
ATCP 93.250 and 93.400(7).
(b) Tanks used in recovery systems that pump
free product at the rate of less than 60 gallons per week shall be constructed
and marked in accordance with ss.
ATCP 93.250 and 93.400(7).