Washington Administrative Code
Title 296 - Labor and Industries, Department of
Chapter 296-863 - Forklifts and other powered industrial trucks
Section 296-863-50005 - Use the appropriate PITs in hazardous (classified) locations

Universal Citation: WA Admin Code 296-863-50005

Current through Register Vol. 24-06, March 15, 2024

(1) You must make sure PITS are used in hazardous (classified) locations as follows:

(a) PITS authorized to be used in Class 1 locations are shown in Table 1, Approved PIT Use in Class 1 Locations;

(b) PITS authorized to be used in Class 2 locations are shown in Table 2, Approved PIT Use in Class 2 Locations;

(c) PITS authorized to be used in Class 3 locations are shown in Table 3, Approved PIT Use in Class 3 Locations.

(2) You must ensure PITS authorized to be used in unclassified locations are:

(a) Approved PITS designated as Type D, E, G, or LP; and

(b) PITs that meet the requirements of a Type D, E, G, or LP PIT.

Definitions:

Unclassified location. An area that is not designated as a Class 1, 2, or 3 location.

Designations. A a code used to show the different types of hazardous (classified) locations where PITs can be safely used:

D. Refers to trucks that are diesel engine powered that have minimum safeguards against inherent fire hazards.

DS. Refers to diesel powered trucks that, in addition to meeting all the requirements for type D trucks, are provided with additional safeguards to the exhaust, fuel and electrical systems.

DY. Refers to diesel powered trucks that have all the safeguards of the DS trucks and, in addition, any electrical equipment is completely enclosed. They are equipped with temperature limitation features.

E. Refers to electrically powered trucks that have minimum acceptable safeguards against inherent fire hazards.

ES. Refers to electrically powered trucks that, in addition to all of the requirements for the E trucks, have additional safeguards to the electrical system to prevent emission of hazardous sparks and to limit surface temperatures.

EE. Refers to electrically powered trucks that have, in addition to all of the requirements for the E and ES type trucks, have their electric motors and all other electrical equipment completely enclosed.

EX. Refers to electrically powered trucks that differ from E, ES, or EE type trucks in that the electrical fittings and equipment are designed, constructed and assembled to be used in atmospheres containing flammable vapors or dusts.

G. Refers to gasoline powered trucks that have minimum acceptable safeguards against inherent fire hazards.

GS. Refers to gasoline powered trucks that are provided with additional exhaust, fuel, and electrical systems safeguards.

LP. Refers to liquefied petroleum gas-powered trucks that, in addition to meeting all the requirements for type G trucks, have minimum acceptable safeguards against inherent fire hazards.

LPS. Refers to liquefied petroleum gas-powered trucks that in addition to meeting the requirements for LP type trucks, have additional exhaust, fuel, and electrical systems safeguards.

Note:

1. Tables 1, 2, and 3 show the type of approved PITs that can be used in the appropriate divisions and groups.

2. PITS cannot be used in divisions and groups that do not have a PIT designation listed.

3. Approved PITs will be marked or labeled with the designation of the PIT. See WAC 296-863-20010, Make sure PITs are properly labeled.

Table 1

Approved PIT Use in Class 1 Locations

Class 1

Locations in which flammable gases or vapors are, or may be, present in the air in quantities sufficient to produce explosive or ignitable mixtures.

Division 1

Conditions exist continuously, intermittently, or periodically under normal operating conditions.

Division 2

Conditions may occur accidentally, for example, due to a puncture of a storage drum.

Group A

Group B

Group C

Group D

Group A

Group B

Group C

Group D

Acetylene

Hydrogen

Ethyl ether

Acetone

Alcohols

Benzene

Gasoline

Lacquer

solvent

Acetylene

Hydrogen

Ethyl ether

Acetone

Alcohols

Benzene

Gasoline

Lacquer

solvent

No PIT type can be used

No PIT type can be used

No PIT type can be used

Use this PIT type:

EX

No PIT type can be used

No PIT type can be used

No PIT type can be used

Use this PIT type:

DS

DY

ES

EE

EX

GS

LPS

Table 2

Approved PIT Use in Class 2 Locations

Class 2

Locations which are hazardous because of the presence of combustible dust.

Division 1

Explosive mixture may be present under normal operating conditions, or where failure of equipment may cause the condition to exist simultaneously with arcing or sparking of electrical equipment, or where dusts of an electrically conducting nature may be present.

Division 2

Explosive mixture not normally present, but where deposits of dust may cause heat rise in electrical equipment, or where such deposits may be ignited by arcs or sparks from electrical equipment.

Group E

Group F

Group G

Group E

Group F

Group G

Metal dust

Carbon black

Coal dust

Coke dust

Grain dust

Flour dust

Starch dust

Organic dust

Metal dust

Carbon black

Coal dust

Coke dust

Grain dust

Flour dust

Starch dust

Organic dust

No PIT type can be used

Use this PIT type:

EX

Use this PIT type:

EX

No PIT type can be used

Use this PIT type:

EX

DY

EE

Use this PIT type:

DS

DY

ES

EE

EX

GS

LPS

Table 3

Approved PIT Use in Class 3 Locations

Class 3

Locations where easily ignitable fibers or flyings are present but not likely to be in suspension in quantities sufficient to produce ignitable mixtures.

Division 1

Division 2

Locations in which easily ignitable fibers or materials producing combustible flyings are handled, manufactured, or used.

Locations in which easily ignitable fibers are stored or handled (except in the process of manufacture).

Use this PIT type:

DY

EE

EX

Use this PIT type:

DS

DY

E

ES

EE

EX

GS

LPS

Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, 49.17.060. 07-03-163, § 296-863-50005, filed 1/24/07, effective 4/1/07; 04-19-051, § 296-863-50005, filed 9/14/04, effective 2/1/05.

Disclaimer: These regulations may not be the most recent version. Washington may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.