Washington Administrative Code
Title 246 - Health, Department of
WATER SYSTEMS
Chapter 246-291 - Group B public water systems
Section 246-291-200 - Design standards
Current through Register Vol. 24-18, September 15, 2024
(1) A purveyor submitting a new or expanding Group B system design for approval shall use good engineering practices and apply industry standards in the design, such as those in:
(2) A purveyor submitting a new or expanding Group B system design for approval shall:
(3) A purveyor shall demonstrate that the source(s) of supply, pipes and other constructed conveyances are capable of meeting the minimum residential water supply as required under WAC 246-291-125(4) Table 1.
(4) A new or expanding Group B system must be designed with the capacity to deliver the PHD at 30 psi (210 kPa) measured along property lines adjacent to distribution mains, under the following conditions:
(5) If the design PHD exceeds the total source pumping capacity, then sufficient equalizing storage must be provided.
(6) The minimum design flow and duration required for fire flow and fire suppression storage, if provided, shall be determined by:
(7) In the design of a new or expanding Group B system that does not have to comply with minimum fire flow standards, a purveyor shall coordinate with the local fire protection authority to assess if any hydrants create adverse pressure problems as a result of expected fire suppression activities, and address any pressure problems in the design.
(8) If fire flow is provided, the distribution system must be designed to provide the MDD for the entire Group B system and the required fire flow at a pressure of at least 20 psi (140 kPa) at all points throughout the distribution system when the designed volume of fire suppression and equalizing storage has been depleted.
(9) The Group B system design must contain a water meter that measures the water use of the entire water system (totalizing source meter) and a source sample tap.
(10) The use of individual service booster pumps to meet the requirements of this section is prohibited.
(11) A purveyor shall equip a new or expanding Group B system with a generator disconnect switch.
(12) A purveyor shall use generally accepted industry standards and practices in the elimination or control of all cross-connections, such as:
(13) A pitless unit, pitless adaptor, and vented sanitary well cap must conform with the product, material, installation, and testing standards under the Water Systems Council PAS-97(04) Pitless Adapters and Watertight Well Caps (2004).
Statutory Authority: RCW 43.20.050 and chapter 70.119A RCW. 12-24-070, § 246-291-200, filed 12/4/12, effective 1/1/14. Statutory Authority: RCW 43.20.050. 94-14-002, § 246-291-200, filed 6/22/94, effective 7/23/94.