Washington Administrative Code
Title 246 - Health, Department of
WATER SYSTEMS
Chapter 246-290 - Group A public water supplies
Part 6 - SURFACE WATER TREATMENT
Subpart A - Introduction and General Requirements
Section 246-290-638 - Analytical requirements
Current through Register Vol. 24-18, September 15, 2024
(1) The purveyor shall ensure that only qualified persons conduct measurements for pH, temperature, turbidity, and residual disinfectant concentrations. In this section, qualified means:
(2) The purveyor shall ensure that measurements for temperature, turbidity, pH, and residual disinfectant concentration are made in accordance with "standard methods," or other EPA approved methods.
(3) The purveyor shall ensure that samples for coliform and HPC analysis are:
(4) Turbidity monitoring.
(5) Purveyors shall verify instruments used for continuous monitoring of free and total chlorine residual with a grab sample measurement at least every five days, or with a protocol approved by the department as required under 40 C.F.R. 141.74(a)(2).
(6) Purveyors monitoring for Cryptosporidium or E. coli as required under 40 C.F.R. 141.701 shall collect samples and have them analyzed under 40 C.F.R. 141.704 and 141.705.
Statutory Authority: RCW 70.119A.180 and 43.20.050. 08-03-061, § 246-290-638, filed 1/14/08, effective 2/14/08. Statutory Authority: RCW 43.20.050(2) and (3) and 70.119A.080. 03-08-037, § 246-290-638, filed 3/27/03, effective 4/27/03. Statutory Authority: RCW 43.02.050 [43.20.050]. 99-07-021, § 246-290-638, filed 3/9/99, effective 4/9/99. Statutory Authority: RCW 43.20.050. 93-08-011 (Order 352B), § 246-290-638, filed 3/25/93, effective 4/25/93.