Chapter 246-274 - Greywater reuse for subsurface irrigation
Section 246-274-300 - Tier 3 greywater irrigation systems
Universal Citation: WA Admin Code 246-274-300
Current through Register Vol. 24-18, September 15, 2024
(1) A Tier 3 greywater irrigation system is a system that uses a treatment component.
(2) A treatment component is required when the system:
(a) Reuses dark
greywater;
(b) Involves storage of
greywater for more than twenty-four hours;
(c) Irrigates a green roof;
(d) Serves a high public exposure area such
as a playground or sports field; or
(e) Is otherwise deemed by the local health
officer to require treatment to protect public health or water
quality.
(3) The following conditions and restrictions apply to Tier 3 systems:
(a) The greywater may be light or dark
greywater.
(b) The total flow of
greywater must be less than three thousand five hundred gallons per
day.
(c) The greywater may
originate from a residential or nonresidential building.
(d) The building must be served by an
approved public sewer system or large on-site sewage system, except as provided
in subsection (e) of this section.
(e) If the building is served by an approved
on-site sewage system with design flows of less than three thousand five
hundred gallons per day, the greywater must originate from a single-family
residence and the total flow of greywater must not exceed three hundred gallons
per day. If the building is something other than a single-family residence, the
local health officer may allow the use of a Tier 3 system if he or she
determines that applicable requirements can be met.
(f) Application of the greywater must be even
throughout the irrigation field. This is typically achieved through pressure
distribution.
(g) Warning signs
must be visible at each fixture from which greywater is diverted at a
nonresidential building. The signs must notify the employees and the public
that water from the fixture is reused for subsurface irrigation of plants and
that chemicals and other hazardous materials may not be poured down the
drain.
(h) The owner shall maintain
a record of the Tier 3 system that:
(i) Shows
the location of the system;
(ii)
Identifies the fixture(s) that are the source of the greywater;
(iii) Describes the design of the system and
how it meets the requirements of WAC
246-274-410 and
246-274-415;
(iv) Identifies the person responsible for
designing the system;
(v) Describes
the maintenance requirements of the system; and
(vi) Includes an estimated calculation of the
total irrigation area pursuant to WAC
246-274-415(1) and
(2).
(4) The building owner shall obtain a permit from the local health officer, in accordance with WAC 246-274-425, before installing the system.
Statutory Authority: RCW 90.46.015. 11-02-011, § 246-274-300, filed 12/28/10, effective 7/31/11.
Disclaimer: These regulations may not be the most recent version. Washington may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.