Washington Administrative Code
Title 246 - Health, Department of
SEWER SYSTEMS
Chapter 246-272C - On-site Sewage System Tanks
DESIGN AND CONSTRUCTION REQUIREMENTS
Section 246-272C-0230 - Additional requirements for grease interceptor tanks
Current through Register Vol. 24-18, September 15, 2024
(1) Grease interceptor compartments. Grease interceptor tanks must be designed and constructed with a minimum of two compartments. This standard may be met by one tank with two compartments or by two single compartment tanks in series.
(2) Grease interceptor inlets. Grease interceptors must have inlets that meet the following:
(3) Grease interceptor outlets. Grease interceptors must have outlets that provide for adequate grease storage and the outlet sanitary tee or baffle must extend:
(4) Grease interceptor intercompartmental wall fittings.
(5) Grease interceptor intercompartmental walls. Grease interceptor intercompartmental walls must:
(6) Grease interceptor tank liquid depth. Grease interceptor tanks must contain a liquid depth of not less than three feet.
Statutory Authority: RCW 43.20.050(2) and (3). 09-23-119, § 246-272C-0230, filed 11/18/09, effective 12/19/09.