Section 246-272B-06700 - Sand-lined trenches and beds
Current through Register Vol. 24-18, September 15, 2024
(1) Sand-lined trenches or beds may be used to meet Treatment Level B.
(2) The minimum dosing frequency is:
(3) The maximum allowable hydraulic loading rate is one gallon per square foot per day.
(4) The design engineer shall:
(5) The minimum depth of sand media is twenty-four inches.
(6) The design engineer shall:
Table 8: Coarse Sand -- Required Particle Size Distribution
Sieve |
Particle Diameter, mm |
Percent Passing by Weight |
||
3/8 inch |
9.50 |
100 |
||
No. 4 |
4.75 |
95 to 100 |
||
No. 8 |
2.36 |
80 to 100 |
||
No. 16 |
1.18 |
45 to 85 |
||
No. 30 |
0.6 |
15 to 60 |
||
No. 50 |
0.3 |
3 to 15 |
||
No. 100 |
0.15 |
0 to 4 |
Table 9: Fine Aggregate -- ASTM C-33 Sand -- Particle Size Distribution
Sieve |
Particle Diameter, mm |
Percent Passing by Weight |
||
3/8 inch |
9.50 |
100 |
||
No. 4 |
4.75 |
95 to 100 |
||
No. 8 |
2.36 |
80 to 100 |
||
No. 16 |
1.18 |
50 to 85 |
||
No. 30 |
0.6 |
25 to 60 |
||
No. 50 |
0.3 |
5 to 30 |
||
No. 100 |
0.15 |
0 to 10; prefer < 4 |
||
No. 200 |
0.075 |
0 - 3; prefer 0 |
Statutory Authority: RCW 70.118B.020. 11-12-035, § 246-272B-06700, filed 5/25/11, effective 7/1/11.