Washington Administrative Code
Title 246 - Health, Department of
SEWER SYSTEMS
Chapter 246-272B - Large on-site sewage system regulations
Part 6 - DESIGN AND TECHNICAL STANDARDS
Subpart B - Specific Technologies
Section 246-272B-06650 - Subsurface drip systems
Current through Register Vol. 24-18, September 15, 2024
(1) Subsurface drip systems must have a:
(2) Where Treatment Level C or better is provided, the return line may be double-plumbed to the primary treatment tank and pump chamber to return flush water to the pump chamber under normal operation, and to the primary tank during chemical cleaning flushes.
(3) The dripline must be installed to a minimum depth of eight inches into original, undisturbed soil. Where frost is a concern, the design engineer should consider deeper placement.
(4) Maximum dripline installation depth is three feet below finished grade.
(5) For determining vertical separation, the infiltrative surface for a drip system may be assumed to be the same as installed dripline depth.
(6) Air and vacuum relief valves must be installed:
(7) All mechanical and electrical components must be rated for wastewater applications.
(8) Electrical components and wiring used in drip system design must comply with requirements of WAC 296-46B-501, Special occupancies NEC Class I locations.
(9) Electrical control and other electrical components must be approved by Underwriters Laboratories (UL) or an equivalent rating agency.
(10) Duplex alternating pumps that provide timed dosing to the drainfield are required.
(11) Quick disconnect couplers or an equivalent quick disconnect system for all sewage pumps are required.
(12) If float switches are used, they must be mounted independently of the pump discharge and transport line.
(13) The control panel for the pumps must:
(14) Automatic flushing of the filters, manifolds, and dripline is required.
(15) A chemical injector port must be installed at an appropriate location in the drip system to allow future injection of chemicals when needed for cleaning.
(16) Any additional filtration recommended by the dripline manufacturer must be provided.
(17) A flow meter with totalizer feature and a pressure gauge, both with remote read-out capability, are required for all drip systems.
(18) All components requiring regular service or used to monitor system performance, such as filters, actuated valves, flow meters, and pressure gauges, must be installed in a valve box with locking lid and access at finished grade.
(19) A minimum of twelve equally spaced timed doses per day per distribution zone is required.
(20) Calculation of the absorption area must be based on:
(21) Maximum nominal emitter discharge rates are:
(22) The values in Table 7 must be used to determine the minimum number of emitters and minimum dripfield area required for a subsurface drip system.
Table 7: Maximum Daily Emitter Discharge Rates
Maximum Daily Emitter Discharge (gpd/Emitter)* |
|||||||||||||||
Soil Types |
|||||||||||||||
Emitter Spacing (inches) |
Dripline Spacing (inches) |
Area per Emitter (ft2) |
1** |
2 |
3 |
4 |
5 |
||||||||
6 |
12 |
0.5 |
0.5 |
0.5 |
0.25 |
0.2 |
0.125 |
||||||||
12 |
12 |
1.0 |
1 |
1 |
0.5 |
0.4 |
0.25 |
||||||||
12 |
18 |
1.5 |
1 |
1 |
0.8 |
0.6 |
0.4 |
||||||||
12 |
24 |
2.0 |
1 |
1 |
0.8 |
0.8 |
0.4 |
||||||||
24 |
24 |
4.0 |
1 |
1 |
1 |
1 |
0.4 |
* |
Table values apply regardless of additional treatment. |
** |
Requires treatment to Treatment Level B or better. |
Statutory Authority: RCW 70.118B.020. 11-12-035, § 246-272B-06650, filed 5/25/11, effective 7/1/11.