Washington Administrative Code
Title 246 - Health, Department of
FACILITY STANDARDS AND LICENSING
Chapter 246-359 - Temporary worker housing construction standard
Section 246-359-760 - Gas connections to factory assembled structures (FAS)

Universal Citation: WA Admin Code 246-359-760

Current through Register Vol. 24-18, September 15, 2024

(1) A FAS, when using gas for heating or cooking purposes, must be connected to the gas outlet by an approved mobile or manufactured home connector. Gas connectors must be of adequate size to supply the total demand of the connected FAS and have a maximum length of six feet.

(2) A shutoff valve controlling the flow of gas to the entire gas piping system must be:

(a)Installed for each FAS;

(b)Readily accessible;

(c)Identified as the "shutoff valve"; and

(d)Installed near the point of connection to the service piping or supply connection of the liquified petroleum gas (LP-gas) tank.

(3) The installation and size of each section of LP-gas piping is determined by the mechanical code as adopted by the state building code council.

Statutory Authority: RCW 70.114A.081. 99-03-065, § 246-359-760, filed 1/18/99, effective 2/18/99.

Disclaimer: These regulations may not be the most recent version. Washington may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.