Washington Administrative Code
Title 246 - Health, Department of
FACILITY STANDARDS AND LICENSING
Chapter 246-359 - Temporary worker housing construction standard
Section 246-359-410 - Foundations and footings for concrete masonry units (CMU) walls

Universal Citation: WA Admin Code 246-359-410

Current through Register Vol. 24-18, September 15, 2024

(1) Footings for load bearing CMU walls must be continuous concrete having a minimum twelve width-by-ten inch thickness, placed a minimum eighteen inches below the finished grade, and reinforced with a minimum of two No. 4 continuous rebar.

(2) Foundations must be one of the following:

(a) Concrete reinforced vertically and horizontally with No. 4 rebar at twenty-four inches on center; or

(b) CMU reinforced vertically and horizontally with No. 4 rebar and having all cells below finished grade fully grouted.

(3) Vertical reinforcement must be spaced at four feet on center, within twelve inches of each corner, extend at least twenty inches up into the CMU wall, and extend at least six inches into the footing with an additional six inches bent at ninety degrees and tied to the horizontal footing rebar.

(4) Foundations must be six inches in width or the width of the CMU wall, whichever is greater.

Statutory Authority: RCW 70.114A.081. 99-03-065, § 246-359-410, filed 1/18/99, effective 2/18/99.

Disclaimer: These regulations may not be the most recent version. Washington may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.