Washington Administrative Code
Title 246 - Health, Department of
FACILITY STANDARDS AND LICENSING
Chapter 246-359 - Temporary worker housing construction standard
Section 246-359-350 - Roof connections for concrete masonry units (CMU)

Universal Citation: WA Admin Code 246-359-350

Current through Register Vol. 24-18, September 15, 2024

(1) Framing members must bear on a two-inch nominal thickness pressure treated plate anchored to the CMU wall with one-half inch diameter bolts. The anchor bolts must be spaced at maximum of six feet on center and a minimum of twelve inches from end of each plate member, and must be embedded into the top of the wall bond beam a minimum of four inches.

(2) Each roof framing member must be secured to the treated plate by installation of a metal tie as approved by the department of health.

Statutory Authority: RCW 70.114A.081. 99-03-065, § 246-359-350, filed 1/18/99, effective 2/18/99.

Disclaimer: These regulations may not be the most recent version. Washington may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.