Section 246-337-140 - Lighting, emergency lighting, and electrical outlets

Universal Citation: WA Admin Code 246-337-140

Current through Register Vol. 24-18, September 15, 2024

The licensee shall ensure that lighting, emergency lighting, and electrical outlets are adequate and safe including:

(1) Protection of bulbs and tubes against breakage by using canned lights, appropriately fitted shields, or shatter resistant materials in all areas occupied by residents, and in medication and food preparation areas.

(2) Use of tamper resistant electrical outlets in each room or area occupied by children under age five or residents with unsafe behaviors.

(3) Use of electrical outlets of the ground fault interrupter type or be controlled by a ground fault circuit interrupter when the outlet is within six feet of a sink or wet area.

(4) Emergency lighting on each floor.

(5) Exterior lighting with solar or battery backup at the exit and entry doors.

Statutory Authority: Chapter 71.12 RCW. 05-15-157, § 246-337-140, filed 7/20/05, effective 8/20/05.

Disclaimer: These regulations may not be the most recent version. Washington may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.