Section 246-337-127 - Restraint or seclusion room requirements
Current through Register Vol. 24-18, September 15, 2024
This section only applies to an RTF that is approved to use restraint or seclusion. In new construction or modification, each restraint or seclusion room must:
(1) Be designed to minimize potential for stimulation, escape, hiding, injury, or death, including:
(2) Have a maximum capacity of one resident.
(3) Be located and designed to permit visual and audible observation of the resident by direct or electronic means.
(4) Be designed to facilitate entrance, transfer and containment of resident, including:
(5) Provide appropriate space for the level of treatment being provided, including:
(6) Have negative air pressure with all air exhausted to the exterior of the building with the exhaust fan at the discharge end of the system.