Chapter 246-335 - In-home services agencies
Part 8 - Specific Design Requirements
Section 246-335-752 - Heating, ventilating and air conditioning

Universal Citation: WA Admin Code 246-335-752

Current through Register Vol. 24-18, September 15, 2024

(1) Hospice care centers must have systems to provide individual temperature control for patient rooms to ensure patient preference and comfort. The hospice care center must have the capacity to maintain:

(a) Patient rooms at 70°F in summer and 80°F in winter; and

(b) Nonpatient care areas at 75°F in summer and 70°F in winter.

(2) Provide air pressurization differentials within the facility to promote the movement air from clean areas into dirty areas per American Society of Heating, Refrigerating and Air-conditioning Engineers (ASHRAE) 170.

(3) Provide air changes in areas per ASHRAE 170.

Disclaimer: These regulations may not be the most recent version. Washington may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.