Washington Administrative Code
Title 212 - State Patrol (Fire Protection) (See also Titles 204, 446 and 448)
Chapter 212-80 - Fire protection sprinkler system contractors
FIRE SPRINKLER CERTIFICATE HOLDER
Section 212-80-093 - Certificate of competency holder certification
Current through Register Vol. 24-24, December 15, 2024
(1) The issuance of a certificate of competency is dependent on employment with a licensed contractor. All applications for a certificate of competency must be submitted with the fire protection sprinkler system contractor's license application or under an existing license. A certificate application will not be processed without the fire protection sprinkler system contractor's license application unless they are currently licensed. All applications must be made on the forms provided by the director and include the required fees provided by WAC 212-80-098 and documentation for the required level of certification as provided by this section.
(2) Proof of competency to the satisfaction of the director is mandatory.
Certificate of Competency Holder Requirements |
||||
Certificate of Competency Level |
Application Required |
Certification or Exam Required |
Stamp Issued |
Type of work performed by Certificate of Competency Holder |
Level 1 |
Yes |
NICET Level 2 or pass an exam (See WAC 212-80-093(1)(a)) |
Yes |
Designs NFPA 13D fire sprinkler systems (NFPA 25) for NFPA 13D |
Level 2 |
Yes |
NICET Level 2 (See WAC 212-80-093(1)(b)) |
Yes |
Designs NFPA 13D, 13R or certain NFPA 24 (Restricted to only certain NFPA 13R systems, see WAC 212-80-018(1)(b)) fire sprinkler systems (NFPA 25) for NFPA 13D or 13R |
Level 3 |
Yes |
NICET Level 3 or 4 (See WAC 212-80-093(1)(c)) |
Yes |
Designs NFPA 13, 13D, 13R or 24 fire sprinkler systems (NFPA 25) for NFPA 13, 13D or 13R |
Level "U" |
Yes |
Pass an exam (See WAC 212-80-093(1)(d)) |
Yes |
Supervises or performs the underground installation of fire sprinkler system piping |
Inspection, Testing Technician (ITT) Employed by an Inspection & Testing Contractor |
Yes |
NICET Level 2 or ASSE 15010 (See WAC 212-80-093(1)(e)) |
No |
Performs inspection or testing on NFPA 13R or 13, wet and dry pipe fire protection systems only |
Inspection, Testing Technician (ITT) Employed by a Level 2 Contractor |
Yes |
NICET Level 2 or ASSE 15010 (See WAC 212-80-093(1)(e)) |
No |
Performs inspection) and testing on NFPA 13R or 13, wet and dry pipe fire protection systems only |
Inspection, Testing Technician (ITT) Employed by a Level 3 Contractor |
Yes |
NICET Level 2 or ASSE 15010 (See WAC 212-80-093(1)(e)) |
No |
Same as ITT above and includes the testing of other fire protection systems such as preaction, deluge, foam, or fire pump |
Professional Engineer (P.E.) Licensed in Washington State |
Only if acting as a Level 1, 2 or 3 certificate of competency holder |
Licensed with department of licensing |
By DOL unless acting as a Level 1, 2, or 3 certificate of competency holder |
Designs, evaluates or consults on fire protection fire sprinkler systems |
(3) All information submitted by an applicant to the director to apply for a certificate must be true and accurate. If the director finds that information or documents submitted by an applicant is false, misleading, or has been altered in an effort to meet the requirements provided by this chapter, the finding will constitute a Level 3 violation.
(4) A violation of this section that involves a contractor allowing an employee to engage in performing fire protection sprinkler system work:
Statutory Authority: RCW 18.270.900. 09-01-114, § 212-80-093, filed 12/19/08, effective 1/19/09. Statutory Authority: Chapters 43.43 and 18.160 RCW. 05-17-099, § 212-80-093, filed 8/16/05, effective 9/16/05; 05-05-006, amended and recodified as § 212-80-093, filed 2/4/05, effective 3/7/05. Statutory Authority: Chapters 43.63A and 18.160 RCW. 94-24-032, § 212-80-045, filed 12/1/94, effective 1/1/95; 91-14-086 (Order 91-06), § 212-80-045, filed 7/1/91, effective 8/1/91.