Washington Administrative Code
Title 212 - State Patrol (Fire Protection) (See also Titles 204, 446 and 448)
Chapter 212-80 - Fire protection sprinkler system contractors
FIRE SPRINKLER CERTIFICATE HOLDER
Section 212-80-088 - Contractor's materials and test certificates
Current through Register Vol. 24-18, September 15, 2024
(1) The certificate of competency holder must complete the contractor's material and test certificate(s), affix his or her certificate stamp, and forward the certificate(s) to the authority having jurisdiction.
(2) Contractor's material and test certificate forms must be of such form as accepted or approved by the authority having jurisdiction.
(3) The authority having jurisdiction and the building owner must retain copies of the contractor's materials and test certificate for a minimum of five years.
(4) The certificate of competency holder will not allow his or her stamp to be used to complete the contractor's materials and test certificate(s) that were not prepared personally by the certificate of competency holder or under his or her direct supervision. Failure to comply with this subsection constitutes a Level 2 violation.
Statutory Authority: RCW 18.270.900. 09-01-114, § 212-80-088, filed 12/19/08, effective 1/19/09. Statutory Authority: Chapters 43.43 and 18.160 RCW. 05-05-006, amended and recodified as § 212-80-088, filed 2/4/05, effective 3/7/05. Statutory Authority: Chapters 43.63A and 18.160 RCW. 94-24-032, § 212-80-040, filed 12/1/94, effective 1/1/95; 91-14-086 (Order 91-06), § 212-80-040, filed 7/1/91, effective 8/1/91.