A. The approved fuels for each CI affected unit are diesel fuel, biodiesel fuel, and biodiesel blends. These fuels shall meet the following specifications:
B. The approved fuels for each SI affected unit are natural gas and liquid petroleum gas (LPG). These fuels shall meet the following specifications:
C. The combined CI affected unit or units located in either an attainment or nonattainment area, shall consume no more than 502,766 gallons of diesel fuel or 554,230 gallons of biodiesel fuel per year, calculated monthly as the sum of each consecutive 12-month period.
A x (140,000 Btu/gal) + B x (127,000 Btu/gal) <= 70,387 x 106 Btu/yr
where:
A = Number of gallons of diesel fuel burned during any consecutive 12-month period.
B = Number of gallons of biodiesel burned during any consecutive 12-month period.
D. The combined SI affected unit or units located in an attainment area shall consume no more than 775,300 gallons of LPG or 72.88 x 106 cubic feet of natural gas per year, calculated monthly as the sum of each consecutive 12-month period.
A x (1,000 Btu/ft3) + B x (94,000 Btu/gal) <= 72,878 x 106 Btu/yr
where:
A = Number of cubic feet of natural gas burned during any consecutive 12-month period.
B = Number of gallons of LPG burned during any consecutive 12-month period.
E. The combined SI affected unit or units located in a nonattainment area shall consume no more than 480,032 gallons of LPG or 45.12 x 106 cubic feet of natural gas per year, calculated monthly as the sum of each consecutive 12-month period.
A x (1,000 Btu/ft3) + B x (94,000 Btu/gal) <= 45,123 x 106 Btu/yr
where:
A = Number of cubic feet of natural gas burned during any consecutive 12-month period.
B = Number of gallons of LPG burned during any consecutive 12-month period.