Virginia Administrative Code
Title 9 - ENVIRONMENT
Agency 5 - STATE AIR POLLUTION CONTROL BOARD
Chapter 40 - EXISTING STATIONARY SOURCES
Part II - Emission Standards
Article 8 - Emission Standards for Fuel Burning Equipment (Rule 4-8)
Section 9VAC5-40-900 - Standard for particulate matter
Universal Citation: 9 VA Admin Code 9VAC5-40-900
Current through Register Vol. 41, No. 3, September 23, 2024
A. Fuel burning equipment installations.
No owner or other person shall cause or permit to be discharged into the atmosphere from any fuel burning equipment installation any gaseous products of combustion containing particulate emissions in excess of the following limits.
1. In AQCR 1
through 6.
a. For fuel burning equipment
installations with total capacity less than 10 million (10 X
106) Btu per hour, the maximum allowable emission
ratio shall be 0.6 pounds of particulate per million Btu input.
b. For fuel burning equipment installations
with total capacity between 10 million (10 X 106)
and 10 billion (10,000 X 106) Btu per hour, the
maximum allowable emission ration, E, in pounds of particulate per million Btu
input, shall be determined by the following equation: E =
1.0906H-0.2594, where H is the total capacity in
millions of Btu per hour.
c. For
fuel burning equipment installations with total capacity in excess of 10
billion (10,000 X 106) Btu per hour, the maximum
allowable emission ratio shall be 0.1 pounds of particulate per million Btu
input.
2. In AQCR 7.
a. For fuel burning equipment installations
with total capacity less than 100 million (100 X
106) Btu per hour, the maximum allowable emission
ratio shall be 0.3 pounds of particulate per million Btu input.
b. For fuel burning equipment installations
with total capacity between 100 million (100 X 106)
and 10 billion (10,000 X 106) Btu per hour, the
maximum allowable emission ratio, E, in pounds of particulate per million Btu
input, shall be determined by the following equation: E =
.9000H-0.2386, where H is the total capacity in
millions of Btu per hour.
c. For
fuel burning equipment installations with total capacity in excess of 10
billion (10,000 X 106) Btu per hour, the maximum
allowable emission ratio shall be 0.1 pounds of particulate per million Btu
input.
B. Fuel burning equipment units.
1. The maximum
allowable particulate emissions for each fuel burning equipment unit shall be
the product of the rated capacity and the emission ratio (determined in
accordance with subsection A of this section).
2. The allowable particulate emissions for
each fuel burning equipment unit when operating at less than rated capacity
shall be the product of the emission ratio, actual heat input and efficiency
factor for the collection equipment. The efficiency factor for the collection
equipment of each unit shall be determined using procedures set forth in
9VAC5-40-920.
3. For fuel burning equipment installations
consisting of multiple fuel burning equipment units, except where all of the
units burn liquid or gaseous fuels, or both, exclusively, the maximum allowable
particulate emissions for each unit may be determined as provided in
9VAC5-40-910.
Statutory Authority
§ 10.1-1308 of the Code of Virginia.
Disclaimer: These regulations may not be the most recent version. Virginia may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.