Virginia Administrative Code
Title 9 - ENVIRONMENT
Agency 25 - STATE WATER CONTROL BOARD
Chapter 790 - SEWAGE COLLECTION AND TREATMENT REGULATIONS
Part III - Manual of Practice for Sewerage Systems and Treatment Works
Article 5 - Sludge Processing and Management
Section 9VAC25-790-580 - Heat treatment
Current through Register Vol. 41, No. 3, September 23, 2024
A. The design of heat treatment systems shall be based on the anticipated sludge flow rate (gpm) with the required heat input dependent on sludge characteristics and concentration. The system should be designed for continuous 24-hour operation to minimize additional heat input to start up the system. Measures for the adequate control of odors shall be stipulated for review.
B. Design. Multiple units shall be provided unless nuisance-free storage or alternate stabilization methods are available, to avoid disruption to treatment works operation when units are not in service. If a single system is provided, standby grinders, fuel pumps, air compressor (if applicable), and dual sludge pumps shall be required.
C. Features. The process should provide heat stabilization in a reaction vessel within a range of 175°C or 350°F for 40 minutes to 205°C or 400°F for 20 minutes at pressure ranges of 250 to 400 psig, or provide for pasteurization at temperatures of 30°C or 85°F or more and gage pressures of more than one standard atmosphere (14.7 psia) for periods exceeding 25 days. The conventional heat drying system involves either direct or indirect contact between a dewatered sludge cake and hot gases in order to reduce the moisture content of the cake to 10% or less. The sludge cake temperature is typically 800°F or more during this process.
D. Incineration. Sludge incinerator ash may be used as either a material additive or an ingredient for the manufacture of construction materials and other products. Due to the large variation in incineration processes, equipment types, and configurations characteristic of currently available incineration systems, it is not feasible to describe a conventional design. Design of these systems should be based on pilot plant studies or data from comparable facilities.
Statutory Authority
§ 62.1-44.15 of the Code of Virginia.