Virginia Administrative Code
Title 9 - ENVIRONMENT
Agency 25 - STATE WATER CONTROL BOARD
Chapter 580 - UNDERGROUND STORAGE TANKS: TECHNICAL STANDARDS AND CORRECTIVE ACTION REQUIREMENTS
Part IV - Release Detection
Section 9VAC25-580-150 - Requirements for hazardous substance UST systems
Current through Register Vol. 41, No. 3, September 23, 2024
Owners and operators of hazardous substance UST systems must provide containment that meets the following requirements and monitor these systems using subdivision 7 of 9VAC25-580-160 at least every 30 days:
1. Secondary containment systems must be designed, constructed and installed to:
NOTE: The provisions of 40 CFR 265.193, Containment and Detection of Releases, may be used to comply with these requirements for tanks installed before September 15, 2010.
2. Double-walled tanks must be designed, constructed, and installed to:
3. External liners (including vaults) must be designed, constructed, and installed to:
4. Underground piping must be equipped with secondary containment that satisfies the requirements of this section (e.g., trench liners, double-walled pipe). In addition, underground piping that conveys regulated substances under pressure must be equipped with an automatic line leak detector in accordance with subdivision 1 of 9VAC25-580-170.
5. For hazardous substance UST systems installed before September 15, 2010, other methods of release detection may be used if owners and operators:
Statutory Authority: §§ 62.1-44.15 and 62.1-44.34:9 of the Code of Virginia; 42 USC § 6901 et seq.; 40 CFR Parts 280 and 281.