Owners and operators of petroleum UST systems must provide release detection for tanks and piping as follows:

1. Tanks. Tanks must be monitored for releases as follows:

a. Tanks installed before September 15, 2010, must be monitored for releases at least every 30 days for releases using one of the methods listed in subdivisions 4 through 9 of 9VAC25-580-160 except that:
(1) UST systems that meet the performance standards in subdivisions 1 through 5 of 9VAC25-580-50 or subdivisions 1 through 4 of 9VAC25-580-60 may use both monthly inventory control requirements in subdivision 1 or 2 of 9VAC25-580-160, and tank tightness testing (conducted in accordance with subdivision 3 of 9VAC25-580-160) at least every five years until 10 years after the tank was installed; and

(2) Tanks with capacity of 550 gallons or less and tanks with a capacity of 551 to 1000 gallons that meet the tank diameter criteria in subdivision 2 of 9VAC25-580-160 may use manual tank gauging (conducted in accordance with subdivision 2 of 9VAC25-580-160) .

b. Tanks installed on or after September 15, 2010, must be monitored for releases at least every 30 days in accordance with subdivision 7 of 9VAC25-580-160.

2. Piping. Underground piping that routinely contains regulated substances must be monitored for releases in a manner that meets one of the following requirements:

a. Piping installed before September 15, 2010, must meet one of the following:
(1) Pressurized piping. Underground piping that conveys regulated substances under pressure must:
(a) Be equipped with an automatic line leak detector conducted in accordance with subdivision 1 of 9VAC25-580-170; and

(b) Have an annual line tightness test conducted in accordance with subdivision 2 of 9VAC25-580-170 or have monthly monitoring conducted in accordance with subdivision 3 of 9VAC25-580-170.

(2) Suction piping. Underground piping that conveys regulated substances under suction must either have a line tightness test conducted at least every three years and in accordance with subdivision 2 of 9VAC25-580-170, or use a monthly monitoring method conducted in accordance with subdivision 3 of 9VAC25-580-170. No release detection is required for suction piping that is designed and constructed to meet the following standards:
(a) The below-grade piping operates at less than atmospheric pressure;

(b) The below-grade piping is sloped so that the contents of the pipe will drain back into the storage tank if the suction is released;

(c) Only one check valve is included in each suction line;

(d) The check valve is located directly below and as close as practical to the suction pump; and

(e) A method is provided that allows compliance with subdivisions 2 a (2) (b), (c), and (d) of this subsection to be readily determined.

b. Piping installed or replaced on or after September 15, 2010, must meet one of the following:
(1) Pressurized piping must be monitored for releases at least every 30 days in accordance with subdivision 7 of 9VAC25-580-160 and be equipped with an automatic line leak detector in accordance with subdivision 1 of 9VAC25-580-170.

(2) Suction piping must be monitored for releases at least every 30 days in accordance with subdivision 7 of 9VAC25-580-160. No release detection is required for suction piping that meets the requirements of subdivisions 2 a (2) (a) through (e) of this section.

Statutory Authority: §§ 62-1.44.15 and 62.1-44.34:9 of the Code of Virginia; 42 USC § 6901 et seq.; 40 CFR "part"s 280 and 281.

Disclaimer: These regulations may not be the most recent version. Virginia may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.