Virginia Administrative Code
Title 9 - ENVIRONMENT
Agency 25 - STATE WATER CONTROL BOARD
Chapter 580 - UNDERGROUND STORAGE TANKS: TECHNICAL STANDARDS AND CORRECTIVE ACTION REQUIREMENTS
Part III - General Operating Requirements
Section 9VAC25-580-90 - Operation and maintenance of corrosion protection
Current through Register Vol. 41, No. 3, September 23, 2024
All owners and operators of metal UST systems with corrosion protection must comply with the following requirements to ensure that releases due to corrosion are prevented until the UST system is permanently closed or undergoes a change-in-service pursuant to 9VAC25-580-320:
1. All corrosion protection systems must be operated and maintained to continuously provide corrosion protection to the metal components of that portion of the tank and piping that routinely contain regulated substances and are in contact with the ground.
2. All UST systems equipped with cathodic protection systems must be inspected for proper operation by a qualified cathodic protection tester in accordance with the following requirements:
NOTE: The following codes of practice may be used to comply with subdivision 2 of this section:
3. UST systems with impressed current cathodic protection systems must also be inspected every 60 days to ensure the equipment is running properly. These systems only provide the necessary corrosion protection when in continuous operation. Such equipment shall be installed so that it cannot be inadvertently shut off.
4. For UST systems using cathodic protection, records of the operation of the cathodic protection must be maintained (in accordance with 9VAC25-580-120) to demonstrate compliance with the performance standards in this section. These records must provide the following:
Statutory Authority: §§ 62-1.44.15 and 62.1-44.34:9 of the Code of Virginia; 42 USC § 6901 et seq.; 40 CFR "part"s 280 and 281.