Section 4VAC25-40-3000 - Fire doors to be provided

Universal Citation: 4 VA Admin Code 4VAC25-40-3000

Current through Register Vol. 41, No. 3, September 23, 2024

A. Fire doors shall be provided at shaft stations or other appropriate locations where necessary to prevent the spread of smoke or gas; the doors shall be equipped with latches operable from both sides. To confine or prevent the spread of toxic gases from a fire originating in an underground shop where maintenance work is routinely done on mobile equipment, one of the following measures shall be taken:

1. Use of control doors or bulkheads;

2. Routing of the mine shop air directly to an exhaust system;

3. Reversal of mechanical ventilation; or

4. Use of an automatic fire suppression system in conjunction with an alternate escape route.

The alternative used shall at all times provide at least the same degree of safety as control doors or bulkheads.

B. If used as an alternative, control doors and bulkheads shall:

1. Be constructed to serve as a barrier to fire, the effects of fire, and air leakage at each opening to the shop; and

2. Be constructed and maintained as follows:
a. So that, once closed, it will not reopen as a result of a differential in air pressure;

b. So that it can be opened from either side by one person or be provided with a personnel door that can be opened from either side;

c. To be clear of obstruction;

d. Provided with a means of remote or automatic closure unless a person specifically designated to close the door in the event of a fire can reach the door within three minutes;

e. If located 20 feet or more from exposed timber or other combustible material, the control doors or bulkheads shall provide protection at least equivalent to a door constructed of no less than one-quarter inch of plate steel with channel or angle-iron reinforcement to minimize warpage. The framework assembly of the door and the surrounding bulkhead, if any, shall be at least equivalent to the door in fire and air-leakage resistance and in physical strength; and

f. If located less than 20 feet from exposed timber or other combustibles, the control door or bulkhead shall provide protection at least equivalent to a door constructed of two layers of wood, each a minimum of three quarters of an inch in thickness. The wood grain of one layer shall be perpendicular to the wood grain of the other layer. The wood construction shall be covered on all sides and edges with no less than 24-gauge sheet steel. The framework assembly of the door and the surrounding bulkhead, if any, shall be at least equivalent to the door in fire and air-leakage resistance and in physical strength. Roll down steel doors with a fire resistance rating of 1-1/2 hours or greater, but without an insulation core, are acceptable, provided that an automatic sprinkler or deluge system is installed that provides even coverage of the door on both sides.

C. If routing of mine shop air to exhaust system is used as an alternative, routing the mine shop exhaust air directly to an exhaust system shall be done so that no person would be exposed to toxic gases in the event of a shop fire.

D. If mechanical ventilation is used as an alternative, reversal of mechanical ventilation shall be accomplished by a main fan. If the main fan is located underground:

1. The cable or conductors supplying power to the fan shall be routed through areas free of fire hazards; or

2. The main fan shall be equipped with a second, independent power cable or set of conductors from the surface. The power cable or conductors shall be located so that an underground fire disrupting power in one cable or set of conductors will not affect the other; or

3. A second fan capable of accomplishing ventilation reversal shall be available for use in the event of failure of the main fan; and

4. The mechanical ventilation shall provide rapid air reversal that allows persons underground time to exit in fresh air by the second escapeway or find a place of refuge and be done according to predetermined conditions and procedures.

E. If automatic fire suppression system and escape route is used as an alternative, the automatic fire suppression system and alternate escape route shall:

1. Be located in the shop area;

2. Be of the appropriate size and type for the particular fire hazards involved;

3. Be inspected at weekly intervals and properly maintained; and

4. In the case of the escape route, bypass the shop area so that the route will not be affected by a fire in the shop area.

Statutory Authority

§§ 45.1-161.3, 45.1-161.294 and 45.1-161.305 of the Code of Virginia.

Disclaimer: These regulations may not be the most recent version. Virginia may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.